Thicknesses of Annealed Copper Pipes

Nominal 

diameter

Outer 

diameter

Thickness

Maximum 

length

Maximum height 

(between indoor and out-

door)

1/4 in

6.35 mm

0.8 mm

20 m (66 ft)

15 m (49 ft)

3/8 in

9.52 mm

0.8 mm

 WARNING

To install a unit that uses R410A refrigerant, use dedicated tools and piping materials 
that have been manufactured speci

fi

 cally for R410A use. Because the pressure of 

R410A refrigerant is approximately 1.6 times higher than R22, failure to use dedicated 
piping material or improper installation can cause rupture or injury. Furthermore, it can 
cause serious accidents such as water leakage, electric shock, or 

fi

 re.

2.3. Power

 WARNING

Always use a special branch circuit and install a special receptacle to supply power to 
the room air conditioner.

Use a circuit breaker and receptacle matched to the capacity of the air conditioner.

Install a leakage circuit breaker in accordance with the related laws and regulations 
and electric company standards.

The circuit breaker is installed in the permanent wiring. Always use a circuit that can 
trip all the poles of the wiring and has an isolation distance of at least 3 mm between 
the contacts of each pole.

 CAUTION

The power source capacity must be the sum of the air conditioner current and the cur-
rent of other electrical appliances. When the current contracted capacity is insuf

fi

 cient, 

change the contracted capacity.
When the voltage is low and the air conditioner is dif

fi

 cult to start, contact the power 

company the voltage raised.

2.4. Electric requirement

 CAUTION

Be sure to install a breaker of the speci

fi

 ed capacity.

Regulation of cables and breaker differs from each locality, refer in accordance with 
local rules.

Voltage rating

1 ø 230 V (50 Hz)

Operating range

198-264 V

Cable

Cable size [mm

2

]

*1

Type

Remarks

Power supply cable

MAX.

2.5

Type 60245

IEC57

Earth 

(Ground), 1ø230V

MIN.

1.5

Connection cable

MAX.

2.5

Type 60245

IEC57

Earth 

(Ground), 1ø230V

MIN.

1.5

*1

  Selected sample: Select the correct cable type and size according to the country or 

region’s regulations. 

Max. wire length: Set a length so that the voltage drop is less than 2%. Increase the 
wire diameter when the wire length is long.

Breaker

Speci

fi

 cation

*2

Circuit breaker (over current)

Current : 20 (A)

Earth leakage breaker

Leakage current : 30mA 0.1sec or less

*

3

*2

  Select the appropriate breaker of the described specification according to the national 

or regional standards.

*3

 Select the breaker that enough load current can pass through it.

  Before starting work check that power is not being supplied to all poles of the indoor 

• 

unit and outdoor unit.
 Install all electrical works in accordance to the national standard.

• 

  Install the disconnect device with a contact gap of at least 3 mm in all poles nearby the 

• 

units. (Both indoor unit and outdoor unit)

•  Install the circuit breaker nearby the units.

2.5. Additional charge

Refrigerant suitable for a piping length of 15 m is charged in the outdoor unit at the factory.
When the piping is longer than 15 m, additional charging is necessary.
Between 15 m and 20 m, when using a connection pipe other than that in the table, charge 
additional refrigerant with 20 g/1 m as the criteria.
For the additional amount, see the table below.

Pipe length

15 m

20 m

Rate

Additional refrigerant

None

+100 g

20 g/m

 CAUTION

When adding refrigerant, add the refrigerant from the charging port at the completion 
of work.
The maximum length of the piping is 20 m. If the units are further apart than this, correct 
operation can not be guaranteed.

2.6. Accessories

The following installation accessories are supplied.
Use them as required.

Drain pipe

1

Installation manual

1

One set of following parts are necessary installation of this product.

Name

Connection pipe assembly
Connection cable
Wall pipe
Decorative tape
Vinyl tape
Wall cap
Saddle
Drain hose
Tapping screws
Sealant

3.  SELECTING THE MOUNTING POSITION

•  Decide the mounting position with the customer as follows.
•  Do not set to a place where there is oily smoke, oil is used in the factory, the unit can 

contact sea breeze, sul

fi

 de gases will be generated in the hot spring area, corrosive 

gases will be generated, animal may urine on the unit and ammonia will be generated 
and a dusty place.

3.1. Outdoor unit

(1) If possible, do not install the unit where it will be exposed to direct sunlight. 

(If necessary, Install a blind that does not interfere with the air 

fl

 ow.)

(2)  Do not install the unit where a strong wind blows or where it is very dusty.
(3)  Do not install the unit where people pass.
(4)  Take you neighbors into consideration so that they are not disturbed by air blowing into their 

windows or by noise.

(5)  Provide the space shown in 

fi

 gure so that the air

fl

 ow is not blocked. Also for ef

fi

 cient 

operation, leave open three of the four directions front, rear, and both sides.

(6)  Install the unit where keep away more than 3 m from the antenna of TV set and Radio.
(7)  Outdoor unit should be set to a place where both drainage and itself will not be 

affected when heating.

 WARNING

Install at a place that can withstand the weight of the outdoor units and install positively 
so that the units will not topple or fall.

 CAUTION

Do not install where there is the danger of combustible gas leakage.
Do not install near heat sources.
If children under 10 years old may approach the unit, take preventive measures so that 
they cannot reach the unit.

9316421073_IM.indb   2

9316421073_IM.indb   2

2012-10-29   9:36:51

2012-10-29   9:36:51

Summary of Contents for 9316421073

Page 1: ...E UNITÀ ESTERNA A uso esclusivo del personale tecnico autorizzato ΕΓΧΕΙΡΙΔΙΟ ΕΓΚΑΤΑΣΤΑΣΗΣ ΕΞΩΤΕΡΙΚΗ ΜΟΝΑΔΑ Μόνο για εξουσιοδοτημένο τεχνικό προσωπικό MANUAL DE INSTALAÇÃO UNIDADE EXTERIOR Apenas para pessoal de assistência autorizado РУКОВОДСТВО ПО УСТАНОВКЕ ВНЕШНИЙ МОДУЛЬ Только для авторизованного обслуживающего персонала MONTAJ KILAVUZU DIŞ ÜNİTE Yalnızca yetkili servis personeli için AIR CONDI...

Page 2: ...n place The installation must be carried out in compliance with regulations in force in the place of installation and the installation instructions of the manufacturer This unit is part of a set constituting an air conditioner It must not be installed alone or with non authorized by the manufacturer The unit must be correctly earthed grounded and the supply line must be equipped with a differentia...

Page 3: ... works in accordance to the national standard Install the disconnect device with a contact gap of at least 3 mm in all poles nearby the units Both indoor unit and outdoor unit Install the circuit breaker nearby the units 2 5 Additional charge Refrigerant suitable for a piping length of 15 m is charged in the outdoor unit at the factory When the piping is longer than 15 m additional charging is nec...

Page 4: ...d prevent the screws from being properly tightened 5 Do not tighten the terminal screws too much otherwise the screws may break 6 See the table below for the terminal screw tightening torques Tightening torque M4 screw 1 2 to 1 8 N m 12 to 18 kgf cm M5 screw 2 0 to 3 0 N m 20 to 30 kgf cm 4 INSTALLATION DIAGRAM Do not directly install it on the ground otherwise it will cause failure To obtain bett...

Page 5: ...llowing work CAUTION Refrigerant must not be discharged into atmosphere After connecting the piping check the joints for gas leakage with gas leak detector 1 Check if the piping connections are secure 2 Check that the stems of 2 way valve and 3 way valve are closed fully 3 Connect the gauge manifold charge hose to the charging port of the 3 way valve side with the projection for pushing in the val...

Page 6: ...se by connecting the charging hose of gauge mani fold to the charging port of 3 way valve and opening the low pressure valve slightly 2 Close the valve stem of 2 way valve completely 3 Start the cooling operation or following forced cooling operation Keep on pressing the MANUAL AUTO button of the indoor unit for more than 10 seconds The operation in dicator lamp and timer indicator lamp will begin...

Reviews: