4.3.2. Multiple outdoor unit installation

• 

Provide at least 9/16in. (15mm) of space between the outdoor units if multiple units are 

installed.

• 

When routing the piping from the side of an outdoor unit, provide space for the piping.

• 

No more than 3 units must be installed side by side. When 3 units or more are 

arranged in a line, provide the space as shown in the following example 

when an 

obstruction is present also in the upward area.

When the upward area is open 

(Unit : in. (mm))

(1) Obstacles at rear only

11-13/16 

(300) or more

(2) Obstacles at front only

5-29/32 (150) 

or more

(3) Obstacles at front and rear only

19-11/16 (500) or more

59-1/16 (1500) or more

When an obstruction is present also in the upward area 

(Unit : in. (mm))

Obstacles at rear and above only

59-1/16 (1500)  

or more

19-11/16 (500)  

or more

Max. 11-13/16 (300)

59-1/16 (1500)  

or more

4.3.3. Outdoor units installation in multi row 

(Unit : in. (mm))

(1) Single parallel unit arrangement

5-29/32 (150) or more

23-5/8 (600) or more

39-3/8 (1000) or more

78-3/4 (2000) or more

(2) Multiple parallel unit arrangement

19-11/16 (500) or more

23-5/8 (600) or more

59-1/16 (1500) or more

118-1/8 (3000) or more

4.4. Transporting the unit

 

WARNING

Do not touch the fins.

 

Otherwise, personal injury could result.

 

CAUTION

When carrying the unit, hold the handles on the right and left sides and be careful. 

If the outdoor unit is carried from the bottom, hands or fingers may be pinched.

• 

Carry slowly in the manner as shown on “Fig. B” holding the handles “Fig. A” in right 
and left sides. (Be careful not to touch with hands or objects.)

• 

Be sure to hold the handles on the sides of the unit. Otherwise, the suction grilles on 
the sides of the unit may be deformed.

Fig. A

Handle

Suction grille

Handle

Suction grille

Fig. B

Front view

Rear view

4.5. Installation

(Unit : in. (mm))

5-3/16 

(132)

AIR

25-19/32 

(650)

4-11/16 

(119)

1-31/32 

(50)

1-31/32 

(50)

5/8 (16)

14-9/32 (363)

4 - Φ 12 Hole

•  Install 4 anchor bolts at the locations indicated with arrows in the above figure.
•  To reduce vibration, do not install the unit directly on the ground. Install it on a secure 

base (such as concrete blocks).

  The foundation shall support the legs of the unit and have a width of 1in. (50mm) or more.

•  Depending on the installation conditions, the outdoor unit may spread its vibration 

during operation, which may cause noise and vibration. Therefore, attach damping 
materials (such as damping pads) to the outdoor unit during installation.

•  Install the foundation, making sure that there is enough space for installing the 

connection pipes.

•  Secure the unit to a solid block using foundation bolts. (Use 4 sets of commercially 

available M10 bolts, nuts, and washers.)

•  The bolts should protrude 25/32 in. (20 mm). 

 

(Refer to the figure below.)

•  If overturning prevention is required, purchase the necessary commercially available 

items.

Bolt

25/32 in.  (20 mm)

Nut

Base

Fix securely with bolts on a solid block. (Use 4 sets of commercially available M10 bolt, 

nut and washer.)

9379069762_IM.indb   6

3/4/2016   09:03:12

Summary of Contents for 30RLXEH

Page 1: ...IT Français Español APPAREIL EXTÉRIEUR UNIDAD EXTERIOR INSTALLATION MANUAL For authorized service personnel only MANUEL D INSTALLATION MANUAL DE INSTALACIÓN Pour le personnel d entretien autorisé uniquement Únicamente para personal de servicio autorizado ...

Page 2: ...ofessional or improper installation of the product may cause serious accidents such as injury water leakage electric shock or fire If the outdoor unit is installed in disregard of the instructions in the installation manual it will void the manufacturer s warranty Do not turn on the power until all work has been completed Turning on the power before the work is completed can cause serious accident...

Page 3: ...ual To connect the indoor unit and outdoor unit use air conditioner piping and cables available locally as standard parts This manual describes proper connections using such installation set Do not use an extension cable Do not purge the air with refrigerants but use a vacuum pump to vacuum the installation There is no extra refrigerant in the outdoor unit for air purging Using the same vacuum pum...

Page 4: ...th R410A are as shown in the table Never use copper pipes thinner than those indicated in the table even if they are available on the market Thicknesses of Annealed Copper Pipes R410A Pipe outside diameter in mm Thickness in mm 1 4 6 35 0 032 0 80 3 8 9 52 0 032 0 80 1 2 12 70 0 032 0 80 5 8 15 88 0 039 1 00 3 4 19 05 0 047 1 20 3 3 Protection of pipes Protect the pipes to prevent the entry of moi...

Page 5: ...eaker If children under 10 years old may approach the unit take preventive measures so that they cannot reach the unit Keep the length of the piping of the indoor and outdoor units within the allowable range For maintenance purposes do not bury the piping 4 2 Drain installation CAUTION In places where the outdoor temperature drops to 32 F 0 C or lower the drain water may freeze and may stop up the...

Page 6: ... the bottom hands or fingers may be pinched Carry slowly in the manner as shown on Fig B holding the handles Fig A in right and left sides Be careful not to touch with hands or objects Be sure to hold the handles on the sides of the unit Otherwise the suction grilles on the sides of the unit may be deformed Fig A Handle Suction grille Handle Suction grille Fig B Front view Rear view 4 5 Installati...

Page 7: ... Prevent mineral oil from getting into the system as this would reduce the lifetime of the units While brazing the pipes be sure to blow dry nitrogen gas through them The maximum lengths of this product are shown in the table If the units are further apart than this correct operation cannot be guaranteed 5 3 1 Flaring Use special pipe cutter and flare tool exclusive for R410A 1 Cut the connection ...

Page 8: ...nd cause damage or injury After the installation make sure there is no refrigerant leakage If the refrigerant leaks into the room and becomes exposed to a source of fire such as a fan heater stove or burner it produces a toxic gas Do not subject the pipes to strong shocks during the sealing test It can rupture the pipes and cause serious injury CAUTION Do not block the walls and the ceiling until ...

Page 9: ...does not include the concurrent use of other devices Do not start operation until the refrigerant is charged completely The compressor will fail if it is operated before the refrigerant piping charging is complete Transmission cable between indoor unit and outdoor unit is 240 V Be sure not to remove thermistor sensor etc from power wiring and connection wiring Compressor may fail if operated while...

Page 10: ... a protection sleeve for the conduits can be inserted at the knock out hole If you do not use a wire conduit be sure to protect the wires to prevent the edge of the knock out hole from cutting the wires It is recommended to apply anti rust paint to the edge of the knock out hole Knock out holes are provided for wiring Fig A Knock out holes are provided 2 each in the same size in front lateral and ...

Page 11: ...tion for using an insulation material with equal heat transmission rate or below 0 040 W m k Relative humidity in mm Insulation material Minimum thickness in mm 70 or more 75 or more 80 or more 85 or more Pipe diameter 1 4 6 35 5 16 8 13 32 10 16 32 13 21 32 17 3 8 9 52 11 32 9 7 16 11 18 32 14 23 32 18 1 2 12 70 13 32 10 15 32 12 19 32 15 3 4 19 5 8 15 88 13 32 10 15 32 12 5 8 16 25 32 20 If the ...

Page 12: ...uring abnormal air conditioner operation 3 PUMP DOWN L1 Orange Lights on during pump down operation 4 LOW NOISE MODE L2 L3 Orange Lights on during Low noise function when field setting is activated Lighting pattern of L2 and L3 indicates low noise level See page 13 5 PEAK CUT L4 L5 L6 Orange Lights on during Peak cut function when local setting is activated Lighting pattern of L4 L5 and L6 indicat...

Page 13: ...e PEAK CUT L4 L5 L6 Level 1 Blink Level 2 Blink Sign Lights off The noise of Level 2 is lower than the one of Level 1 6 Press ENTER button SW3 and fix it PEAK CUT L4 L5 L6 Level 1 Level 2 Sign Lights off Lights on 7 Return to Operating status display Normal operation by pressing EXIT button SW4 In case of missing how many times SELECT and ENTER button are pressed restart from the beginning of oper...

Page 14: ...ction 10 1 External input 10 1 1 Wiring of connector ON OFF of the Low noise mode and Peak cut mode functions can be enabled with an external field device When installing connection cable specified part optional parts must be used Refer to section 9 2 Table Settings List for the required function The function must be set for the external input to work Input Connector No Optional parts Low noise mo...

Page 15: ...ete the outdoor units and the connected indoor units will start operating Room temperature control will not activate during test operation continuous operation If a knocking sound can be heard in the liquid compression of the compressor stop the unit immediately and then energize the crank case heater for a sufficient length of time before restarting the operation 11 2 1 Setting method on outdoor ...

Page 16: ...r Heat sink temp sensor error 2 8 4 Current sensor error Current sensor 1 error stoppage permanently 2 8 6 Pressure sensor error High pressure switch 1 error 2 8 6 Pressure sensor error 2 9 4 Trip detection Trip detection 2 9 5 Compressor motor control error Rotor position detection error stoppage permanently 2 9 7 Outdoor unit fan motor 1 error Duty error 2 9 8 Outdoor unit fan motor 2 error Duty...

Page 17: ...D display lights on as shown in the above figure and the fans and the compressor start operating If the PUMP DOWN button is pressed while the compressor is operating the compressor will stop then start again in about 3 minutes 4 LED display will change as shown below about 3 minutes after the compressor starts Fully close the 3 way valve on the liquid pipe side at this stage POWER MODE ERROR PUMP ...

Reviews: