Chapter 5 CONFIGURING INVERTER'S FUNCTION CODES FOR DeviceNet
COMMUNICATION
Before starting DeviceNet communication between the inverter equipped with the communications card and the
DeviceNet master device, configure the inverter's function codes listed in Table 5.1.
Table 5.2 lists other related function codes to be configured if necessary.
Table 5.1 Inverter's Function Codes for DeviceNet Communication
Function
codes
Description
Factory
default
setting
Function code data
Remarks
o31
*1 Select output assembly
instance
(From master to inverter)
0
Available data is:
20 :
Basic
speed
control
output
0, 21 : Extended speed control output
100 : Fuji
drive
assembly
output
102 : User defined assembly output
104 : Request for Access to Function
Codes
See Chapter 7.
The factory default is
"Extended speed
control output."
o32
*1 Select input assembly
instance
(From inverter to master)
0
Available data is:
70
: Basic speed control input
0, 71 : Extended speed control input
101 : Fuji
drive
assembly
input
103 : User defined assembly input
105 : Response to Function Codes
Access Request
See Chapter 7.
The factory default is
"Extended speed
control input."
y98
*2 Select run/frequency
command source
0
Available data is:
Frequency
command
Run
command
0
Inverter Inverter
1
DeviceNet Inverter
2
Inverter DeviceNet
3
DeviceNet DeviceNet
If there is no special
problem with your
system, setting y98 =
3 is recommended.
*1 After configuring the function code o31 or o32, restart the inverter to validate the new settings. For details about these
function codes, refer to Chapter 7 "I/O MESSAGE."
Input and output assembly instances should not be necessarily set to the same instance type. (Ex. Output assembly
instance = Extended speed control output, Input assembly instance = User defined assembly input.)
*2 If the extended speed control output is selected (o31 = 0 or 21), only bit operation in the instance can select the
run/frequency command sources, so no prior configuration of y98 is required. For details, refer to Section 7.2.2
"Extended Speed Control Instance."
Table 5.2 Other Related Function Codes
Function
codes
Description
Factory default
setting
Function code
setting range
Remarks
o27
*1 Select the inverter’s operation mode to
apply when a DeviceNet
communications error occurs.
0 0
to
15
o28
*1 Set the operation timer to apply when a
DeviceNet communications error occurs.
0.0 s
0.0 to 60.0 s
o40 to o43
*2
Assign the function code writing data
cyclically.
0
(No assignment)
0000 to FFFF (hex)
o48 to o51
*2
Assign the function code reading data
cyclically.
0
(No assignment)
0000 to FFFF (hex)
Valid only when
"User defined
assembly
input/output" is
selected (o31 = 102,
o32 = 103).
*1 For details about function codes o27 and o28, refer to Chapter 9 "INVERTER REACTION TO DeviceNet
COMMUNICATIONS ERRORS."
*2 For details about function codes o40 to o43 and o48 to o51, refer to Section 7.2.4 "User Defined Assembly Instance."