29
ENGLISH
(3) Control Supervisor object (Class 29 hex.)
This object monitors the current run command settings and the running status of the inverter, and configures the
running-related settings.
Instance Attribute
Name
Description
Value (hex.)
R/W Data size
1
03
Run1
Run forward command
00: OFF
01: ON
R/W Byte
04
Run2
Run reverse command
00: OFF
01: ON
R/W Byte
05
NetCtrl
Switching run command
source
00: Inverter
01: DeviceNet
R/W Byte
06
State
Current inverter status
01: Inverter running
02: Inverter not ready to
run
03: Inverter ready to run
04: Inverter running
05: During deceleration
06: Stop due to
communication broken
07: Tripped
R Byte
07
Running1
Running
forward
00:
Stopped/Running
reverse
01: Running forward
R Byte
08
Running2
Running
reverse
00:
Stopped/Running
forward
01: Running reverse
R Byte
09
Ready
Inverter ready to run/
Inverter running
(Synchronized with State
above)
00: State = Value except
below
01: State = 03 to 05
R Byte
0A
Faulted
Tripped state
00: Not tripped
01: Tripped
R Byte
0B
Warning
Warning. Fixed at 0.
00: No warning
R
Byte
0C
FaultRst
Reset of tripped (alarm) state
00
→
01: Request for reset
R/W
Byte
0F
CtrlFromNet
Current run command source
00: Inverter
01: DeviceNet
R Byte
10
DNFaultMode Inverter reaction to DeviceNet
communications errors
Refer to Chapter 9.
R/W
Byte