– 10 –

6-11

Password Setup (Ch11)

Sets the password. Passwords can be set at three levels.

6-12

Display (Ch12)

Sets the parameter mask function Optional parameters can be set not to display.
For details on the parameter mask function, refer to the "Operation Manual".

Note 1:  Displayed when the seventh digit of the model code is H, K, F, 2 or E, or the eleventh

digit is D.

Note 2:  Displayed when the ninth digit of the model code is not 0, or the 

eleventh digit is C.

Note 3:  Display changes according to the DO number and the selected alarm type.
Note 4:

Displayed when the fifth digit of the model code is not V or S and the sixth digit is A,

C, E or P.

Note 5:  “

SvL

” and “

Svh

” must be set so that SvL < Svh.

When the setting values of “

SvL

”  and “

Svh

”  are changed, check SV setting value 1

(“

Sv1 Ch3

”) through SV setting value 7 (“

Sv7 Ch3

”).

Note 6:

Set the same value as the one for the Normal/Reverse setting (“

rEv Ch2

”).

Note 7:

Displayed when the fifth digit of the model code is A or C.

Note 8:  Displayed when the fifth digit of the model code is V.
Note 9:  Displayed when the fifth digit of the model code is E or P.
Note 10:  Displayed when the seventh digit of the model code is G or J, or when the eleventh

digit is A.

Note 11: The number of parameters to be displayed varies depending on the number of DIs

that PXG has.

For more details on “41: DI soft start”, refer to the “Operation Manual”.

Note 12:  Displayed when the sixth digit of the model code is R or S.
Note 13:  The parameter uses this even if the terminal uses CT2 input.
Note 14:  Select the proper setup range for the output type.
Note 15:  Do not set 4 to 7.
Note 16:  Displayed when the fifth digit of the model code is V or S.
Note 17:  Displayed when the seventh digit of the model code is M, V, K, J, F or U.
Note 18:  Displayed when the sixth digit of the model code is E or P.
Note 19:  When the fifth digit of the model code is S or V, be sure to select PID control. Options

other than PID control cannot be used.

Note 20:  When changing the SV with the front key, do not change the “

Svn

”  parameter via

communication.Otherwise, the changed SV may not be stored correctly.

Note 21:  Do not change this parameter during the ramp soak operation.

Be sure to set “

PrG

” = “

oFF

” before changing the parameter.

7

Functions

This controller has five types of temperature control functions and three types of valve control
functions. Select according to type and use.

Temperature Control Functions

Valve Control Functions

7-1

ON/OFF (2-position) Control

Acts as an ON/OFF control when the PID parameter is set to "

P

" = 0.0 ("

Pid Ch 2

").

ON/OFF control switches the control output to ON (100%) or OFF (0%) according to the size rela-
tionship of PV and SV.The output hysteresis can be set under the parameter "

hYS

" ("

Pid Ch 2

").

Reverse Operation (heat control)

Method used to control the electrical heating furnace."Set the 

hYS

" to an appropriate value

according to the control target.

Normal Operation (cooling control)

Method used to control the cooling machine.

7-2

PID Controls

PID controls run as long as the parameter is set to "

P

 0.0 ("

Pid Ch 2

") and "

CTrL

" = PID ("

SYS

CH 7

"). The PID controls calculate PID based on the set values for parameters "

P

", "

i

", "

d

", and

"

Ar

", and output the calculated result (-3% to 103%).

Each parameter can be set either by manually tuning the values or by running auto-tuning (AT)
to automatically set the values.

Setting PID Control

7-3

Fuzzy PID Control

Related to normal PID controls, fuzzy PID control acts with small overshoot.
You will need to run auto-tuning to set the PID parameter when using fuzzy control.

Setting fuzzy PID control

Display

Parameter name

Function

Setting range

Initial 
value

Remarks

"

PAS1

" (PAS1)

Password1 setup

Sets password 1.

0000 to FFFF

0000

"

PAS2

" (PAS2)

Password2 setup

Sets password 2.

0000 to FFFF

0000

"

PAS3

" (PAS3)

Password3 setup

Sets password 3.

0000 to FFFF

0000

Display

Parameter name

Function

Setting range

Initial 
value

Remarks

"

dP01

" (dP01)

Parameter mask of 
each parameter

Sets the 
parameters to be 
displayed/not 
displayed.

0000 to FFFF

Value 
different 
depending 
on the 
model 
code

"

dP30

" (dP30)

Parameter mask of 
each parameter

Sets the 
parameters to be 
displayed/not 
displayed.

0000 to FFFF

Value 
different 
depending 
on the 
model 
code

Caution

The ramp soak function (

page 12), remote SV function (

page 15), and 

SV selection function (

page 16) cannot be combined.

ON/OFF (2-position) 
control

Turns the control output ON/OFF according to the size 
relationship of PV and SV Can build a control system 
out of simple elements such as SSR. Suitable when 
accuracy is not requested.

7-1

(page 10)

PID Controls

PID calculation and controls proceed according to the 
previously set PID parameters.
PID parameters can be set manually or through auto-
tuning (AT).
It is the most basic control in this equipment.

7-2

(page 10)

Fuzzy PID Control

PID control with function that reduces the amount of 
overshoot during control. It is effective when you want 
to suppress overshoot when SV is changed, even if you 
may take a long time to reach the target value.

7-3

(page 10)

Self-tuning Control

Automatically calculating PID control according to the 
control target or SV change. It is effective when the 
control conditions change frequently.

7-4

(page 11)

PID2 Control

In case which the power supply of the control target 
goes ON 

→ 

OFF 

→ 

ON, this PID2 control can suppress 

the amount of overshoot during control target turns OFF 

→ 

ON.

7-5

(page 11)

Servo Control 1 
(Servo 1)

Regulates the valve position according to [OPEN] and 
[CLOSE] of the contact output.

7-7

(page 11)

Servo Control 2 
(Servo 2)

Regulates the valve position according to [OPEN] and 
[CLOSE] of the contact output.It can also display the 
valve ís degree of openness according to the position 
position signal from the valve. However, it cannot be 
used to calculate the control output.

7-7

(page 11)

Position Feedback
(PFB Control)

Controls the valve according to a calculation performed 
on the opening signal.Regulates the valve position 
according to [OPEN] and [CLOSE] of the contact 
output.
It can be used when there is an opening signal coming 
from the valve.

7-8

(page 12)

Parameter

Set Value

"

P

"

0.0

"

rEv

rv--

"

hYS

"

arbitary (factory 
setting: 1 °C)

Parameter

Set Value

"

P

"

0.0

"

rEv

no--

"

hYS

"

arbitary (factory 
setting: 1 °C)

Point

During ON/OFF control, the I and D settings do not affect control.
The manual operation during ON/OFF control will become MV=100%
when the 

 key is pressed, and MV=0% when the 

 key is pressed.

If the hysteresis width is narrow, and PV and SV are nearly equal, the
output may frequently switch ON and OFF. Note that it may affect the
operation life of the contact output.

Refer to

For more details on auto-tuning, see "7-6 Auto-tuning" (page 11)

1

Display the system menu ("

SYS Ch 7

").

2

Display the control parameter ("

CTrL

") and choose PID controls ("

Pid

").

3

Press the 

 key to set the value.

1

Display the system menu ("

SYS [h 7

").

2

Display the controller parameter ("

[trL

") and choose fuzzy ("

FUZY

").

3

Press the 

 key to set the value.

Refer to

For more details on auto-tuning, see "7-6 Auto-tuning" (page 11)

PV

ON

OFF

control output

t

SV

process value

PV<SV

PV>SV

HYS

PV<SV

PV>SV

PV

ON

OFF

control output

t

SV

process value

HYS

Summary of Contents for PXG5

Page 1: ...errors or failures may be caused Periodic maintenance is recommended for continuous and safe use of this equipment Some parts installed on this equipment have a limited life and or may deteriorate with age The warranty period for this unit including accessories is one year if the product is used properly 2 Caution 2 1 Cautions when Installing Please avoid installing in the following locations Loca...

Page 2: ... relay If the output operation frequency is high selecting a SSR SSC drive output type is recommended Proportionate cycles Relay output 30 seconds or more SSR SSC drive output 1 second or more When inductive loads such as magnetic opening closing equip ment etc as relay output equipment are connected use of Z trap manufactured by Fuji Electric Device Technology Co Ltd is recommended in order to pr...

Page 3: ...orque of about 0 8 N m Do not attach anything to unused terminals Do not use relay terminals PC loader interface PXG9 TOP TOP 13 24 37 48 61 72 49 60 1 12 25 36 waterproof packing panel terminal screw M3 96 96 79 5 10 2 91 5 115 5 MAX t 6 2 31 32 33 34 35 36 7 8 9 1 2 3 4 5 6 10 11 12 mounting fixture fastening torque 0 15 N m 25 26 27 28 29 30 Panel thickness 1 to 8 mm PC loader interface 25 36 1...

Page 4: ...ance bulb input 33 34 35 36 Current voltage input Voltage mV input 33 34 35 36 Measurement value input 29 30 29 30 RSV2 input CT2 input 25 26 27 28 DIO COM DI3 DI5 DI4 Digital input 25 26 27 28 DIO COM DI3 DI5 DI4 Digital input 25 26 27 28 29 30 DIO COM DI3 DI5 DI4 DO4 DO5 Digital input output 5 6 Power supply Note 3 Note 1 Note 2 50 60Hz 31 32 DI COM DI1 3 4 3 4 3 4 5 6 1 2 DI COM DI1 3 4 1 2 RS4...

Page 5: ...e SV display shows the input output values For more details on PASS PASS see 5 6 Key Lock and Password page 6 For more details on Note in the Remarks column see 6 Parameter List page 6 5 3 Basic Operations Pressing the key or the key switches between modes Pressing in monitor mode or setup mode allows you to choose menu items Changing SV set values Changing MV control output values 5 4 Operations ...

Page 6: ...channel and the authority of passwords 1 to 3 Note When FEFE FEFE is entered as PASS PASS all of the channels OPE ch to DSP ch can be displayed and set This super password function is useful when you forget the set passwords oPE ch PAS1 permissions PASS PAS1 PAS2 permissions PASS PAS2 PAS3 permissions PASS PAS3 Pid ch PLT ch PrG ch Mon ch SET ch SyS ch ALM ch CoM ch PFb ch PAS ch dSP ch Password l...

Page 7: ... Sets the integration time 0 to 3200 sec 240 sec d7 d7 Differential time 7 Sets the differential time 0 0 to 999 9 sec 60 0 sec hyS7 hyS7 ON OFF control hysteresis 7 Sets the hysteresis when using the ON OFF control 0 to 50 FS 1 C oL7 CoL7 Cooling proportional band 7 Sets the cooling proportional band 0 0 to 100 0 1 0 Note4 Parameter display symbol Parameter name Function Setting range Initial val...

Page 8: ...SV input filter Sets the time constant for the RSV input filter 0 0 to 120 0 sec 0 0 sec Note1 fixed at 0 8bit PV input underflow 9bit PV input overflow 10bit underrange 11bit overrange 12bit RSV underrange 13bit RSV overrange 14bit range setting error 15bit EEPROM error 0bit PFB input underflow 1bit PFB input overflow RST RST RST RST 1r C1r OUT1 range Sets the range of the control output OUT1 0 5...

Page 9: ...r alarm function bit2 non excitation output alarm function bit3 hold reset function RST PrCS PrCS Control target Allows you to select the control target SRV1 Servo control 1 SRV2 Servo control 2 PFB Position feedback control PFb Srv1 with PFB without PFB Note16 Stmd STMd Start mode Sets the operation mode when starting up Auto auto mode startup Man manual mode startup Rem remote mode startup STby ...

Page 10: ...ou will need to run auto tuning to set the PID parameter when using fuzzy control Setting fuzzy PID control Display Parameter name Function Setting range Initial value Remarks PAS1 PAS1 Password1 setup Sets password 1 0000 to FFFF 0000 PAS2 PAS2 Password2 setup Sets password 2 0000 to FFFF 0000 PAS3 PAS3 Password3 setup Sets password 3 0000 to FFFF 0000 Display Parameter name Function Setting rang...

Page 11: ...re changing back to self tuning 1 Display the system menu SYS Ch 7 2 Display the control parameter CTrL and choose PID2 Pid2 3 Press the key to set the value dead time t process value tuning SV lag time suppress overshoot ON OFF control equipment power t SV process value control loop close close open PV At set value Behavior Function oFF Stop Finish Stops or finishes auto tuning on Normal type The...

Page 12: ...et CAL to 3 in step 3 above This setting will automatically open and close the valve to adjust it auto matically Caution To manually adjust the valve carry out step 1 through step 7 as written above If the valve is not connected or connected incorrectly it can still be adjusted but will not achieve accurate results There is no open circuit judgment function for the valve opening feed back signal C...

Page 13: ...SV 1 2nd ramp 3rd ramp 4th ramp SV 2 SV 3 SV 4 Dis play Function Name Behavior ON OFF Judgment conditio n 0 No function Nothing happen 1 Switchover between standby ON OFF Switches between standby on and off Standby Standby Cancel Edge 2 Switchover between auto manual Switches between auto and manual control output Manual Auto Edge 3 Switchover between local remote Switches between local and remote...

Page 14: ...ting DO1 to DO5 Function Wire burnout circuit alarm 41 Loop break alarm 1 44 Heater burnout alarm 1 Wire break short circuit alarm 47 Load short circuit alarm Dis play Function Name Behavior ON OFF Judgment conditio n Settings complete Using them as alarms 1 to 31 Using them as events 35 to 102 or timers 32 to 34 1 Setting the System Menu 2 Setting the Alarm Menu 3 Setting the alarm menu page 14 D...

Page 15: ...2 Display hysteresis 1 A1hY and set the hysteresis 3 Display delay time 1 dLY1 and set the delay 4 Display delay time units 1 dL1U and set the units to minutes or seconds 5 Set the values for alarm 2 to alarm 5 as necessary 6 Press the key to set the value 1 Display the operation menu oPE Ch1 2 Set the alarm 1 set value AL1 or AL1L and AL1H The parameters displayed will vary according to the type ...

Page 16: ...time SFTM and set the time 4 Press the key to set the value 5 Turn off the power once and then re start the controller to begin soft start When the soft start function is turned on the lower display will alternate show ing SoFT and SV Note Do not use auto tuning at the same time 1 Display the setup menu SET h 6 2 Display FALT output 1 set value FLo1 and set the output value For dual control set FL...

Page 17: ...alue 1 Display the operation menu oPE Ch1 2 Display the selected PID number PLn1 and choose the PID No 3 Press the key to set the value 1 Display the palette menu PLT Ch 3 2 Display max selected PID number PL1M and set the PID number by choosing it with the user key 3 Display the user key function setting UKEy and set it to PID selection function 4 On the PV SV display pressing the user key will s...

Page 18: ... 7 and STbY is ON Normal control The controller does not have to be restarted Parameters may not be displayed q Check the settings of dP01 to dP30 w Check the password function Normal control The controller does not have to be restarted Input type Measurement range C Measurement range F Smallest input increment C Input code Resistance bulb JIS IEC Pt 100Ω 0 to 150 32 to 302 0 1 1 0 to 300 32 to 57...

Page 19: ...thout hold alarm may turn ON when starting up Caution When alarm action code is changed alarm set value may also become dif ferent from previous settings When alarm action type code is changed turn off the power once and then re start the controller before starting control Aln AL1 to AL5 show the alarm set values ALnh AL1h to AL5h show the alarm set values ALnL AL1L to AL5L show the alarm set valu...

Page 20: ... mV input voltage input current input 0 3 FS 1digit Indication resolution 0 3 FS or less Digital Output Relay contact output DO1 to DO3 1a contact 220V AC 30V DC 3A resistance load Transistor Output DO4 DO5 Open collector 30V DC 100mA max 2 contacts Judged ON 1V DC or less Digital input Contact or Transistor type Max 5 inputs 30V DC 3mA 1 input Judged ON 1kΩ or less contact or 5V DC or less transi...

Reviews: