– 9 –
2
Wiring
9
Power supply
8
AC100-240V
Measured value input
Alarm output 2
6
7
ALM2
Alarm output 1
4
5
ALM1
Thermistor
Thermocouple
1
1
2
3
3
2
16
17
15
18
11
10
14
13
12
8
7
6
9
2
1
5
4
3
Note 1) Check the power supply voltage before installation.
Note 2) Tighten the terminal screw securely with fastening torque of 0.4N·m.
Terminal Connection Diagram (100 to 240 Vac)
Designation of Wiring Material
• Wire
Gauge: AWG28 (0.1mm2) to AWG16 (1.25mm2)
Strip-off length: 5 to 6 mm
• Rod terminal
Dimension of exposed conductor section:
2 x 1.5 mm or smaller
Length of exposed conductor section:
5 to 6 mm
AWG28 to AWG16
5 to 6 mm
1.5
MAX
2MAX
5 to 6 mm
To prevent disconnection or short circuit, never use the wire other than the
one stated above, and make sure to insert it toward the back of the terminal
block.
Fastening torque: 0.4N·m
Caution