background image

2.3  LED Status Indicators 

This option has five LED status indicators shown below. They indicate the operation status of the option as listed 
in Table 2.1. 

L.RUN

RUN

L.ERR

SD

RD

Figure 2.3    LED Status Indicators 

Table 2.1    LED Indications and Operation Status 

LED States 

L.RUN 

RUN

L.ERR 

SD

RD

Operation Status 

z

z

{

z

z

Normally communicating. 

z

z





z

Normally communicating. But sometimes a CRC error 
occurs due to electrical noise. 

z

z



{

z

Received data contains a CRC error, so this option 
cannot respond. 

z

z

{

{

z

Data destined for this station does not come. 

{

z





z

Responding to polling. But refresh data received 
contains a CRC error. 
The inverter trips with alarm 

GT

displayed. 

*1

{

z



{

z

Data destined for this station contains a CRC error. 
The inverter trips with alarm 

GT

displayed. 

*1

{

z

{



z

Station address incorrectly specified. 
Data destined for this station cannot be received due 
to electrical noise. 

{

z

z

{

z

/

{

Transmission speed (Baud rate) and/or station 
address out of the allowable range. 

z

z



(at 0.8-second 

intervals)



z

Transmission speed (Baud rate) or station address 
changed during CC-Link communication. 

{

z

{

{

{

This option cannot receive data due to broken wires, 
etc.
The inverter trips with alarm 

GT

displayed. 

*1

{



(at 0.4-second 

intervals)

{

{

{

The master station is compliant with CC-Link version 
1.xx and this slave station, with CC-Link version 2.xx. 
Or the inverter's function code o30 is set to "5 to 255." 

The inverter trips with alarm 

GT

displayed. 

{



(at 0.2-second 

intervals)

{

{

{

During normal communication, the option connection 
cable has been broken or the power to the inverter has 
been cut OFF. 
If the cable has been broken, the inverter trips with 
alarm

GT

displayed. 

{



(at 50 ms 

intervals)

z

{

{

When this option is turned ON, the inverter has been 
OFF or the option connection cable has been 
disconnected. 

{

{

{

{

{

This option is OFF or broken. 

If the inverter power is ON, it trips with alarm 

GT

displayed. 

z

: ON, 

{

: OFF, 



: Blinking (It may seem to be ON depending on the current transmission speed.) 

*1 Alarm 

GT

occurs when a communications error is detected after a normal communications link has been 

established once. 

 

  It is possible to change the 

GT

 occurrence conditions with inverter's function codes. For details, refer to 

Chapter 8 "INVERTER REACTION TO CC-Link COMMUNICATIONS ERRORS." 

7

Summary of Contents for OPC-E1-CCL

Page 1: ...e FRENIC Multi User s Manual and be familiar with the handling procedure for correct use Improper handling blocks correct operation or causes a short life or failure Deliver this manual to the end use...

Page 2: ...eproduced or copied without prior written permission from Fuji Electric FA Components Systems Co Ltd All products and company names mentioned in this manual are trademarks or registered trademarks of...

Page 3: ...roper handling might result in incorrect operation a short life or even a failure of this product Keep this manual in a safe place Related Publications Listed below are the other materials related to...

Page 4: ...on s terminal covers before turning the inverter s power ON Do not remove the covers while power is applied Otherwise electric shock could occur Do not operate switches with wet hands Doing so could c...

Page 5: ...apter 5 CONFIGURING INVERTER S FUNCTION CODES FOR CC Link COMMUNICATION Describes the inverter s function codes to be set for the CC Link communications link Also this chapter lists the related functi...

Page 6: ...FIGURING INVERTER S FUNCTION CODES FOR CC Link COMMUNICATION 18 Chapter 6 SETTING UP PROCEDURE 19 Chapter 7 LIST OF I O SIGNALS 20 7 1 Remote I O Signals 20 7 2 Remote Registers 22 7 3 List of Monitor...

Page 7: ...ed to the right side of the option See Figure 1 1 If you suspect the product is not working properly or if you have any questions about your product contact your Fuji Electric representative Figure 1...

Page 8: ...on 2 2 Terminating Resistor Switch The CC Link communications network requires insertion of line terminating resistors at its both ends When this option is mounted on the inverter at either end of the...

Page 9: ...peed Baud rate or station address changed during CC Link communication z This option cannot receive data due to broken wires etc The inverter trips with alarm GT displayed 1 at 0 4 second intervals Th...

Page 10: ...er to the FRENIC Multi Instruction Manual INR SI47 1094 E Chapter 2 Section 2 4 Mounting and Connecting a Keypad 2 5 Power Supply Terminal Block and CC Link Terminal Block The power supply terminal bl...

Page 11: ...so could cause a fire accident or injury Prevent lint paper fibers sawdust dust metallic chips or other foreign materials from getting into the inverter and the option Otherwise a fire or an accident...

Page 12: ...face PCB on the inverter Use the short cable for inverters with a capacity of 3 7 kW or below and the long cable for the ones with a capacity of 5 5 kW or above 3 Mount the terminal cover For details...

Page 13: ...e front side of the option then secure the keypad and option to the inverter with the option fixing screw that comes with the option When using the keypad at a remote site secure the option without th...

Page 14: ...PCB on the inverter in step 2 above to the CN1 connector on the interface option printed circuit board interface option PCB 9 Mount the option terminal cover First fit the bosses on the top of the cov...

Page 15: ...therwise an accident could occur 4 1 Basic Connection Diagram L1 R U V W L2 S L3 T G FRENIC Multi OPC E1 CCL 0V 24V DB DA DG SLD FG CC Link cable CC Link terminal block Power supply terminal block Mot...

Page 16: ...B 2 5 3 ST 5 08 Table 4 1 Pin Assignment on Power Supply Terminal Block Figure 4 2 Connectors on the Power Supply Terminal Block 1 2 3 Pin Terminal name Description Remarks 1 24 V Power supply 24 VDC...

Page 17: ...ing Manual is available as a free download from the CC Link Partner Association s website at http www cc link org eng t_html siryo html 2 Wiring around the CC Link terminal block The terminal block us...

Page 18: ...0 5 to 0 6 N m Figure 4 5 Recommended Strip Length of the Cable Wire End for Terminal Connection 3 When two or more inverters are connected DA DB DG SLD FG DA DB DG SLD FG DA DB DG SLD FG Master OPC E...

Page 19: ...on of the option causing a trip with GT alarm The GT alarm can be reset after this option is turned ON 2 Power OFF It is recommended that this option be turned OFF at the same time as or after the inv...

Page 20: ...valid 0 156 kbps 1 625 kbps 2 2 5 Mbps 3 5 Mbps 4 10 Mbps o32 3 Transmission speed 5 to 255 Invalid 1 For details about the function codes o27 and o28 refer to Chapter 8 INVERTER REACTION TO CC Link C...

Page 21: ...OPTION See Chapter 3 MOUNTING THE CC Link INTERFACE OPTION See Chapter 4 WIRING AND CABLING See Chapter 2 Section 2 2 Terminating Resistor Switch See Chapter 5 CONFIGURING INVERTER S FUNCTION CODES FO...

Page 22: ...Ww1 to the inverter s RAM Upon completion of writing the Frequency setting completed signal RXD is turned ON RYE Not used RYF 4 Command code execution request Turning this signal ON executes processin...

Page 23: ...OFF turns this signal OFF RXD Frequency setting completed This signal is turned ON when turning the Frequency command RYD ON has written the reference frequency into the inverter Turning the Frequenc...

Page 24: ...ssary After writing into RWw2 and RWw3 turn the RYF ON If no write data is required zero 0 should be written into RWw3 RWw4 Monitor code 3 RWw5 Monitor code 4 RWw6 Monitor code 5 RWw7 Monitor code 6 W...

Page 25: ...RWw10 12 14 16 and 18 and their respective registers RWw11 13 15 17 and 19 the RYF should be turned ON If no write data is required zero 0 should be written into each of RWw11 13 15 17 and 19 CC Link...

Page 26: ...s of RWr8 See Chapter 9 for alarm codes RWr9 Output frequency at an alarm occurrence This register stores the output frequency applied at the occurrence time of the alarm specified in RWw8 Unit 0 01 H...

Page 27: ...on 1 10 RWw0 to RWw3 are available In CC Link version 2 00 with 2X setting RWw0 to RWw7 are available with 4X setting RWw0 to RWwF RWw9 for this option are available with 8X setting RWw0 to RWw1F RWw1...

Page 28: ...inverter in RMS based on the inverter rating 0 1 Assuming the inverter rated current as 100 19H Input watt hour 1 kWhr 1AH to 33H No monitoring Fixed to 0 34H PID command 0 1 35H PID feedback 0 1 36H...

Page 29: ...Lower byte Latest alarm code Higher byte Last alarm code The contents of alarm codes are detailed in Chapter 9 Read from the 2nd and 3rd last alarm codes 0075H Reads the content of the 2nd and 3rd las...

Page 30: ...cation dedicated function codes S01 S05 and S06 are read only Attempting to write to those function codes will result in a Not allowed to write error Response code 0001H These function codes are funct...

Page 31: ...ecelerate to a stop Issue GT after stopping The inverter s function code F08 specifies the deceleration time 11 0 0 s to 60 0 s After the time specified by o28 decelerate to a stop Issue GT after stop...

Page 32: ...vercurrent during deceleration E 24 18H Motor 2 overload N 3 03H Overcurrent During running at constant speed E 25 19H Inverter overload NW 5 05H Ground fault GH 31 1FH Memory error GT 6 06H Overvolta...

Page 33: ...In program examples given in this chapter the network parameters of the master unit are set as listed in Table 10 1 Table 10 1 Network Parameter Settings of the Master Unit Parameter Settings Start I...

Page 34: ...02F to Y1020 RY F to RY 0 Y103F to Y1030 RY 1F to RY 10 Y104F to Y1040 Y105F to Y1050 Figure 10 2 Relationship between Master Station Devices and Remote I Os 2 Remote registers Figure 10 3 shows the r...

Page 35: ...X00 Unit failure PLS M302 Permission to write settings M302 SET M303 Request to write settings M303 SET Y06 Link start request X06 RST Y06 Cancel of link start request RST M303 Link startup completed...

Page 36: ...M0 SET M301 M300 SET Y100F RST Y100F MOV W2 D2 RST M302 END Turn command code execution request RYF OFF When the command code execution completed signal RXF is turned ON the response code RWr2 is rea...

Page 37: ...rom the Inverter s Function Code Data The program example shown below reads out the F07 data Acceleration time 1 from FRENIC Multi station 1 Read out data link status of slave stations X0 Unit failure...

Page 38: ...xecution request RYF ON X0F X1 X20 BMOV SW80 K4M0 K4 MOV H87 W102 Unit ready Host station being linked Writing ON M302 PLS M300 M0 SET M301 M300 SET Y100F RST Y100F MOV W2 D2 RST M302 END Turn command...

Page 39: ...X1 X20 BMOV SW80 K4M0 K4 MOV K5000 W101 Unit ready Host station being linked Writing ON M302 PLS M300 M0 SET M301 M300 SET Y100D RST Y100D MOV W2 D2 RST M302 END Write reference frequency into RWw1 M3...

Page 40: ...code execution request RYF OFF When the command code execution completed signal RXF is turned ON read out alarm code RWr3 and response code RWr2 into D1 and D2 respectively M301 X100F Command code ex...

Page 41: ...the RS 485 Communication User s Manual Chapter 5 Is data written into the buffer memory areas RX RY RWw RWr as assigned to addresses YES Check writing to the I O memory areas NO YES 2 Network error G...

Page 42: ...ion 2 00 o30 4 Setting invalid o30 Other than the above data Terminal block for connection 5 pin terminal block M3 5 screws Communications cable CC Link dedicated cable Use the CC Link dedicated cable...

Page 43: ...operating of CC Link Interface Option OPC E1 CCL for the FRENIC Multi series of inverters Please feel free to send your comments regarding any errors or omissions you may have found or any suggestions...

Page 44: ...Components Systems Co Ltd Mitsui Sumitomo Bank Ningyo cho Bldg 5 7 Nihonbashi Odemma cho Chuo ku Tokyo 103 0011 Japan Phone 81 3 5847 8011 Fax 81 3 5847 8172 URL http www fujielectric co jp fcs 2006...

Reviews: