Chapter 12 SPECIFICATIONS
12.1 General Specifications
For items not contained in the following table, the specifications of the inverter apply.
Item
Specifications
Input power voltage
21.6 to 27.0 V
Power consumption
Max. 150 mA, 24 VDC
Operating ambient temperature
-10 to +50
q
C
Operating ambient humidity
5 to 95% RH (There shall be no condensation.)
External dimensions
79.6 x 127 x 47.5 mm
Applicable inverter
FRENIC-Multi, ROM version 0700 or later
12.2 CC-Link Specifications
For the items not contained in the following table, the CC-Link specifications apply.
Item
Specifications
Name
CC-Link interface option
Station type
Remote device station
Number of units
connectable
Max. 42 units (one station occupied/unit), compatible with other options
Number of stations
occupied
1
CC-Link version
The option complies with CC-Link versions 1.10 and 2.00. It can be configured
with the function code o30 as follows:
1 station occupied (CC-Link version 1.10): o30 = 0 or 1
1 station occupied with 2X setting (CC-Link version 2.00): o30 = 2
1 station occupied with 4X setting (CC-Link version 2.00): o30 = 3
1 station occupied with 8X setting (CC-Link version 2.00): o30 = 4
Setting invalid: o30 = Other than the above data
Terminal block for
connection
5-pin terminal block (M3×5 screws)
Communications cable
CC-Link dedicated cable
- Use the CC-Link dedicated cable in CC-Link system.
- Using a cable other than a CC-Link dedicated cable does not assure the
CC-Link system performance.
- For further information about the CC-Link dedicated cable specifications and
inquiries, visit the CC-Link Partner Association's website at:
http://www.cc-link.org/eng/t_html/top.html
Station address
1 to 64. The station address can be specified with the inverter's function code o31.
Transmission speed
(Baud rate)
10 Mbps (o32 = 4), 5 Mbps (o32 = 3), 2.5 Mbps (o32 = 2), 625 kbps (o32 = 1),
156 kbps (o32 = 0)
The transmission speed can be specified with the inverter's function code o32.
LED status indicators
L.RUN: Lights when the option is normally receiving refresh data. It goes off
if data transmission is interrupted for a certain period of time.
L.ERR: Lights when a communications error has occurred. It blinks if the
station address (o31) or the transmission speed (o32) is changed
when the power is on.
RUN:
Lights during normal communication. It blinks when mismatch in
CC-Link version settings is found or the connection between the
inverter and the option is cut.
SD:
Lights during data transmission.
RD:
Lights during data reception.
40