7.3 List of Monitor Item Codes
Table 7.1 lists the monitor item codes available in RWw0, 4 to 7.
Table 7.1 Monitor Item Codes
Code
Monitor item
Unit
Remarks
00
H
No monitoring (Fixed to 0)
--
01
H
Output frequency
0.01 Hz
02
H
Output current
0.01 A
03
H
Output voltage
0.1 V
04
H
No monitoring (Fixed to 0)
--
05
H
Reference frequency
0.01 Hz
06
H
Motor speed
1 r/min
07
H
Calculated torque
0.1%
08
H
DC link bus voltage
0.1 V
In units of 1 V
09
H
to 0C
H
No monitoring (Fixed to 0)
--
0D
H
Input power
0.01 kW
0E
H
Motor power consumption
0.01 kW
0F
H
Input terminal status
--
*1
10
H
Output terminate status
--
*2
11
H
Load factor
0.1%
Assuming the motor rated
torque as 100%
12
H
to 13
H
No monitoring (Fixed to 0)
--
14
H
Cumulative run time
1 hr
15
H
to 16
H
No monitoring (Fixed to 0)
--
17
H
Cumulative motor run time
1 hr
18
H
Current output from the inverter in RMS
(based on the inverter rating)
0.1%
Assuming the inverter rated
current as 100%
19
H
Input watt-hour
1 kWhr
1A
H
to 33
H
No monitoring (Fixed to 0)
--
34
H
PID command
0.1%
35
H
PID feedback
0.1%
36
H
PID deviation
0.1%
37
H
to
No monitoring (Fixed to 0)
--
*1 The format of the input terminal status signal is shown below. Individual bits denote the ON/OFF states of
input terminals on the actual control circuit terminal board. If terminals X1 through X5 are turned ON or OFF
by remote outputs RY2 to 6, the change of the ON/OFF states cannot be reflected on this monitor.
b15
b8
b7
b0
-
-
-
-
-
-
-
-
-
X5
X4
X3
X2
X1
REV FWD
-
㧦
Empty (Fixed to 0)
Figure 7.1 Input Terminal Status Signal Format
*2 The format of the output terminal status signal is shown below. Individual bits denote the ON/OFF states of
output terminals on the actual control circuit terminal board. Their states are changed in synchronization with
remote inputs RX2, 3, and 7.
b15
b8
b7
b0
-
-
-
-
-
-
-
30
-
-
-
-
-
-
Y2
Y1
-
㧦
Empty (Fixed to 0)
Figure 7.2 Output Terminal Status Signal Format
26