[Description]
• This parameter sets whether or not to perform the RCJ
(Cold junction compensation) for the thermocouple in-
put. Use the factory default setting (ON: performs the
RCJ) under normal conditions.
ON: Performs the RCJ (Cold junction compensation).
OFF: Does not perform the RCJ (Cold junction com-
pensation).
RCJ (Cold junction compensation) (Setting range: ON/OFF)
[Setting example] Changing the RCJ (Cold junction compensation) from ON to OFF
Press and hold the
SEL
key for five seconds.
will be displayed on the PV display.
Press the
key to display
.
Press the
SEL
key once.
The current setting (
) flashes on the SV display.
Press the
or
keys to display
.
Press the
SEL
key once.
will stop flashing and will be registered for
. After that, the
controller will operate with the RCJ (Cold junction compensation) being
.
If you want to display the operation status, press and hold the
SEL
key for two seconds.
Operating procedure
Display
1.
2.
3.
4.
5.
6.
• Set this parameter to OFF under the conditions that the
RCJ is not needed, such as when the RCJ is performed
outside of the PXR or when the temperature deviations
are recorded.