[Description]
• These parameters set the setting range of the SV (Setting
value).
• Both the SV under ramp-soak operation and the SV switched
by the DI1 function are affected by the SV limiter.
• The SV upper and lower limiters (
,
) can be set
within the range of the measuring values (
,
).
SV (Setting value) lower limiter (Setting range: 0 to 100%FS)
SV (Setting value) upper limiter (Setting range: 0 to 100%FS)
[Note]
• Before setting the parameters of
and
, be sure
to set the following parameters.
• Setting the lower limit of the measured range (
)
• Setting the upper limit of the measured range (
)
• Setting the of decimal places point position (
)
• After changing the parameters of
,
, and
, power off the PXR, and then on. Then, set the pa-
rameters of
and
again.
• Before setting the SV, set the parameters of
and
.
• Be sure to set the values of
and
so that
is larger than
or
is the same as
.
• Although the displayed SV is affected by the limiter imme-
diately after setting
and
, the set values of
to
are not affected.
• When the SV limiter is set during ramp-soak operation or
switching the SV with the DI1 function, the SV (SV0) that
is set manually and the displayed SV are affected by the SV
limiter. So, after setting the ramp-soak operation to OFF,
or returning the switched SV to the original SV, the PXR
operates with the SV0 affected by the SV limiter.
Lower limit of
measuring range
(P-SL)
SV lower
limiter
(SV-L)
Setting value
(SV)
SV upper
limiter
(SV-H)
Upper limit of
measuring range
(P-SU)
Measured value
(PV)
Setting range of the SV (Setting value)
Setting range of SV limiter [Measuring range (FS)]
[Setting example] Setting the upper limiter to 100
°
C
Press and hold the
SEL
key for five seconds.
will be displayed on the PV display.
Press the
key to display
.
Press the
SEL
key once.
The current setting (
) flashes on the SV display.
Press the
or
keys to display
.
Press the
SEL
key once.
will stop flashing and will be registered for
. After that, the
upper limit of the SV will be 100
°
C.
If you want to display the operation status, press and hold the
SEL
key for two seconds.
Operating procedure
Display
1.
2.
3.
4.
5.
6.