30
Output offset value (Setting range: -100.0 to 100.0 %)
Anti-reset windup (Setting range: 0 to 100%FS)
[Description]
• The anti-reset windup (
) is automatically set to an
optimum value by the auto-tuning operation.
By setting
, the amount of overshoot can be adjusted.
[Note]
By making use of the fuzzy control system equipped with
PXR, the amount of overshoot can be minimized without
setting
and
.
[Setting example] Changing the anti-reset windup from 60˚C to 80˚C.
Press and hold the
SEL
key for three seconds.
will be displayed on the PV display.
Press the
key to display
.
Press the
SEL
key once.
The current setting (
) flashes on the SV display.
Press the
or
keys to display
.
Press the
SEL
key once.
will stop flashing and will be registered for
. After that, the
controller will operate with the anti-reset windup being 80˚C.
If you want to display the operation status, press and hold the
SEL
key for two seconds.
Operating procedure
Display
1.
2.
3.
4.
5.
PV
SV
}
}
}
AR value
AR value
In this range, the integral
operation is not performed.
In this range, the integral
operation is performed.
In this range, the integral
operation is not performed.
6.