– 13 –
Delay start
Ramp soak can be automatically started (RUN) after a certain period of time has elapsed
since the power of the controller is turned on.
This function is enabled by setting the digital input function (DI n) and the digital output function
(DonT), and setting the delay time to set with dLYn.
The following steps will explain how to assign the delay start to DI 1, Do1 and to set the delay
time to five minutes.
PV start
When the ramp soak starts (RUN), this function searches the first point where the measure-
ment value (PV) and the program pattern match, and starts operation at that pooint.
If the measurement value does not match the pattern as with PV=
➂
, the normal operation
starts.
7-10
Digital Input Function
Each of the digital inputs (DI1 to DI3) can be assigned the following functions. The specified
function will run when an external DI signal enters the input.
The following steps will explain an example of how to set DI1 to switchover between standby
ON/OFF.
1
Display the system menu (
S
S
S
Sy
y
y
ys
s
s
s
C
C
C
Ch
h
h
h7
7
7
7
).
2
Display the Di1 function selection ("
d
d
d
di
i
i
i1
1
1
1
"), and set 44 ("
4
4
4
44
4
4
4
").
3
Display the DO1 output event type setting ("
d
d
d
do
o
o
o1
1
1
1T
T
T
T
"), and set 35 ("
3
3
3
35
5
5
5
").
4
Display the Alarm menu (
A
A
A
AL
L
L
LM
M
M
M
C
C
C
Ch
h
h
h8
8
8
8
).
5
Display the ALM1 delay time ("
d
d
d
dL
L
L
LY
Y
Y
Y1
1
1
1
"), and set 5 ("
5
5
5
5
").
6
Display the ALM1 delay time unit ("
d
d
d
dL
L
L
L1
1
1
1U
U
U
U
"), and set the minute ("
M
M
M
Mi
i
i
in
n
n
n
").
Dis
play
Function Name
Behavior
ON
OFF
Judgement
condition
"
0
0
0
0
"
No function
Nothing happen
–
–
–
"
1
1
1
1
"
Switchover between
standby ON/OFF
Switches between standby on and off
Standby
Standby
Cancel
Edge
"
2
2
2
2
"
Switchover between
auto/manual
Switches between auto and manual control output
Manual
Auto
Edge
"
3
3
3
3
"
Switchover between
local/remote
Switches between local and remote SV
Remote
Local
Edge
"
4
4
4
4
"
No function
Do not set
–
–
–
"
5
5
5
5
"
No function
Do not set
"
6
6
6
6
"
Auto-tuning
(standard) Start
Starts standard auto-tuning
Start
Finish
Edge
"
7
7
7
7
"
Auto-tuning (low
PV) Start
Starts low PV auto-tuning
Start
Finish
Edge
"
8
8
8
8
"
No function
Do not set
–
–
–
"
9
9
9
9
"
No function
Do not set
"
1
1
1
10
0
0
0
"
Ramp SV on/off
Enables or disables ramp SV.
Disable
Enable
Edge
"
1
1
1
11
1
1
1
"
Ramp SV HOLD
Switches between ramp SV HOLD and HOLD
cancel
HOLD
HOLD
cancel
Edge
"
1
1
1
12
2
2
2
"
Ramp Soak OFF
Turns ramp soap off
OFF
–
Edge
"
1
1
1
13
3
3
3
"
Ramp Soak RUN/
HOLD
Switches between RUN and HOLD.
RUN
HOLD
Edge
"
1
1
1
14
4
4
4
"
No function
Do not set
–
–
–
"
1
1
1
15
5
5
5
"
Latch release (all)
Cancels all of the sources currently acting as
latches.
–
–
Edge
"
1
1
1
16
6
6
6
"
Latch release
(DO1)
Cancels the source currently acting as a latch on
DO1.
Cancel
–
Edge
"
1
1
1
17
7
7
7
"
Latch release
(DO2)
Cancels the source currently acting as a latch on
DO2.
"
1
1
1
18
8
8
8
"
Latch release
(DO3)
Cancels the source currently acting as a latch on
DO3.
"
1
1
1
19
9
9
9
"
No function
Do not set
–
–
–
"
2
2
2
20
0
0
0
"
No function
Do not set
D L Y n
TM1S
TM1r
TM2S
TM2r
TM3r
TM3S
TM4r
TM4S
1st ramp
SV-1
2nd ramp
3rd ramp
4th ramp
SV-2
SV-3
SV-4
Start of
➂
PV=
➀
PV=
➁
PV=
➂
Start of
➁
Start of
➀
SV
"
2
2
2
21
1
1
1
"
Start timer (DO1)
Starts the specified timer for DO1.
Timer
ON
Timer
OFF
Level
"
2
2
2
22
2
2
2
"
Start timer (DO2)
Starts the specified timer for DO2.
"
2
2
2
23
3
3
3
"
Start timer (DO3)
Starts the specified timer for DO3.
"
2
2
2
24
4
4
4
"
No function
Do not set
–
–
–
"
2
2
2
25
5
5
5
"
No function
Do not set
"
2
2
2
26
6
6
6
"
SV No. + 1
When selecting SV No., increases the SV No. by 1.
+1
–
Level
"
2
2
2
27
7
7
7
"
SV No. + 2
When selecting SV No., increases the SV No. by 2.
+2
–
Level
"
2
2
2
28
8
8
8
"
SV No. + 4
When selecting SV No., increases the SV No. by 4.
+4
–
Level
"
2
2
2
29
9
9
9
"
PID No. + 1
When selecting PID No., increases the PID No. by
1.
+1
–
Level
"
3
3
3
30
0
0
0
"
PID No. + 2
When selecting PID No., increases the PID No. by
2.
+2
–
Level
"
3
3
3
31
1
1
1
"
PID No. + 4
When selecting PID No., increases the PID No. by
4.
+4
–
Level
"
3
3
3
32
2
2
2
"
No function
Do not set
–
–
–
"
3
3
3
33
3
3
3
"
No function
Do not set
"
3
3
3
34
4
4
4
"
No function
Do not set
"
3
3
3
35
5
5
5
"
SV No.+1,
PID No.+1
When selecting SV No. and PID No., increases the
SV No. and PID No. by 1.
+1
–
Level
"
3
3
3
36
6
6
6
"
SV No.+2,
PID No.+2
When selecting SV No. and PID No., increases the
SV No. and PID No. by 2.
+2
–
Level
"
3
3
3
37
7
7
7
"
SV No.+4,
PID No.+4
When selecting SV No. and PID No., increases the
SV No. and PID No. by 4.
+4
–
Level
"
3
3
3
38
8
8
8
"
Pattern No.+1
When selecting pattern No., increases the Pattern
No. by +1
+1
–
Level
"
3
3
3
39
9
9
9
"
Pattern No.+2
When selecting pattern No., increases the Pattern
No. by +2
+2
–
Level
"
4
4
4
40
0
0
0
"
Pattern No.+4
When selecting pattern No., increases the Pattern
No. by +4
+4
–
Level
"
4
4
4
41
1
1
1
"
Soft start
Starts the soft start
Soft
start
ON
–
Edge
"
4
4
4
42
2
2
2
"
Ramp soak RUN
Sets the ramp soak to RUN.
RUN
–
Edge
"
4
4
4
43
3
3
3
"
Ramp soak HOLD
Sets the ramp soak to HOLD.
HOLD
–
Edge
"
4
4
4
44
4
4
4
"
Delay start(DO1)
Enables delay start with the delay time = dLY1.
Delay start
enable
–
"
4
4
4
45
5
5
5
"
Delay start(DO2)
Enables delay start with the delay time = dLY2.
Delay start
enable
–
"
4
4
4
46
6
6
6
"
Delay start(DO3)
Enables delay start with the delay time = dLY3.
Delay start
enable
–
"
4
4
4
47
7
7
7
"
No function
Do not set this.
–
–
–
"
4
4
4
48
8
8
8
"
No function
Do not set this.
–
–
–
1
Display the system menu ("
S
S
S
SY
Y
Y
YS
S
S
S
[
[
[
[h
h
h
h
7
7
7
7
").
2
Display the DI1 parameter ("
d
d
d
di
i
i
i1
1
1
1
") and choose 1 ("
1
1
1
1
").
This chooses to switchover between standby ON and OFF.
3
Press the
key to set the value.
Caution
When “Switchover between local and remote” (DI setting value =3) is used for the
digital input function, the operation before turning off the power of the main unit
affects the DI operation when the power turns on again.
(For the DI operation when the power turns on under each state, see the table
below.)
No.
Operation before turning off power of the main unit
DI status
while the
power of the
main unit is on
DI behavior while
the power of the
main unit is on
Operation
Operation
status
1
DI On when rEM parameter = LoCL
Remote SV
operation
DI On
Remote SV operation
DI Off
Local SV operation
2
Switches to rEM parameter = rEM by
key operation
DI On
Remote SV operation
DI Off
Remote SV operation
3
Switches desired parameter setting
value via communication during rEM
parameter = rEM
DI On
Remote SV operation
DI Off
Remote SV operation
4
DI Off when rEM parameter = rEM
Local SV
operation
DI On
Remote SV operation
DI Off
Remote SV operation
5
Switches to rEM parameter = LoCL by
key operation
DI On
Remote SV operation
DI Off
Local SV operation
6
Switches desired parameter setting
value via communication during rEM
parameter = LoCL
DI On
Remote SV operation
DI Off
Local SV operation
Dis
play
Function Name
Behavior
ON
OFF
Judgement
condition