Fuji Electric FRN0013C2S-4U Instruction Manual Download Page 9

Chapter 9  LIST OF PERIPHERAL EQUIPMENT AND OPTIONS 

Name of peripheral 

equipment 

Function and application 

Main peri

p

heral

 eq

ui

pm

ent 

Molded case 
circuit breaker 
(MCCB) 

Residual-current- 
operated protec-
tive device (RCD) 
/Earth leakage 
circuit breaker 
(ELCB)* 

* with overcurrent

protection 

MCCBs are designed to protect the power circuits between the power control 
board and inverter’s main terminals (L1/R, L2/S and L3/T for three-phase 
power, L1/L and L2/N for single-phase power) from overload or short-circuit 
which in turn prevents secondary disasters caused by the inverter malfunc-
tioning. 

RCDs/ELCBs function in the same way as MCCBs. Use the MCCBs and 
RCDs/ELCBs that satisfy the recommended rated current listed below. 

Recommended rated current (A) of 

MCCB and RCD/ELCB 

Power 

supply 

voltage

Applicable

motor 
rating 

(HP) 

Inverter type   

w/ DC reactor 

w/o DC reactor 

7.5 

FRN0025C2S-2U

30

50

10 

FRN0033C2S-2U

40

75

15 

FRN0047C2S-2U

50

100

Three-

phase

200 V

20 

FRN0060C2S-2U

75

125

7.5 

FRN0013C2S-4U

15 

30 

10 

FRN0018C2S-4U

20 

40 

15 

FRN0024C2S-4U

30 

50 

Three-

phase

400 V

20 

FRN0030C2S-4U

40 

60 

When connecting the inverter to the power supply, add a recommended 
molded case circuit breaker (MCCB) or a residual-current-operated protec-
tive device (RCD)/earth leakage circuit breaker (ELCB)* in the path of power 
supply. Do not use the devices with the rated current out of the recom-
mended range. 

*With overcurrent protection

Fire could occur.

Select the MCCB or RCD/ELCB with appropriate rated current and breaking 
capacity according to the power supply capacity.

Chapter 10  APPLICATION OF DC REACTORS (DCRs) 

Since the "Japanese Guideline for Suppressing Harmonics in Home and General-purpose Appli-
ances" issued by the Ministry of International Trade and Industry (Currently the Ministry of Economy, 
Trade and Industry) was revised in January 2004, the general-purpose inverters have no longer 
been subject to the guideline. Individual inverter manufacturers have voluntarily employed har-
monics suppression measures. It is recommended that DC reactors (DCRs) specified in Table 10.1 
be connected to the FRENIC-Mini series of inverters. 

Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]

Summary of Contents for FRN0013C2S-4U

Page 1: ...E INR SI47 1745 E It describes the FRENIC C2S Inverter types FRN0025 to 0060C2S 2U and FRN0013 to 0030C2S 4U For other descriptions refer to the original manual Improper handling might result in incor...

Page 2: ...commended wire sizes The recommended wire sizes for the main circuit ter minals for an ambient temperature of 50 C are indicated for two types of wire HIV single wire for the maximum allowable tempera...

Page 3: ...the cable from the inverter to the motor is very long a high frequency current may be generated by stray capacitance between the cables and result in an overcurrent trip of the inverter an increase i...

Page 4: ...5 37 21 11 00 1 0 Three phase 200 V 20 FRN0060C2S 2U 2 8 48 50 15 00 1 0 7 5 FRN0013C2S 4U 4 9 10 24 5 50 0 5 10 FRN0018C2S 4U 4 4 12 86 7 50 0 5 15 FRN0024C2S 4U 3 5 18 60 11 00 1 0 Three phase 400...

Page 5: ...DB5 5 4 80 55 20 0 138 FRN0018C2S 4U DB7 5 4 60 38 0 188 FRN0024C2S 4U DB11 4 40 55 0 275 Three phase 400 V FRN0030C2S 4U DB15 4 1 34 4 75 10 0 375 5 10 ED Braking resistor Continuous braking 100 bra...

Page 6: ...nclosure IP20 IEC 60529 1989 UL open type UL50 Cooling method Fan cooling Mass lbs 6 8 6 8 9 8 9 8 1 Fuji 4 pole standard motors 2 Refers to the rated capacity assuming the rated output voltage as 220...

Page 7: ...able safety standards UL508C IEC 61800 5 1 2007 under application Enclosure IP20 IEC 60529 1989 UL open type UL50 Cooling method Fan cooling Mass lbs 6 8 6 8 9 8 9 8 1 Fuji 4 pole standard motors 2 Re...

Page 8: ...RN0025C2S 2U Three phase 200 V FRN0033C2S 2U FRN0013C2S 4U Three phase 400 V FRN0018C2S 4U Power supply voltage Inverter type FRN0047C2S 2U Three phase 200 V FRN0060C2S 2U FRN0024C2S 4U Three phase 40...

Page 9: ...10 FRN0018C2S 4U 20 40 15 FRN0024C2S 4U 30 50 Three phase 400 V 20 FRN0030C2S 4U 40 60 When connecting the inverter to the power supply add a recommended molded case circuit breaker MCCB or a residua...

Page 10: ...h the following standards Low Voltage Directive EN61800 5 1 2007 EMC Directives EN61800 3 2004 A1 2012 Immunity Second environment Industrial Emission Category C2 Applicable only when an optional EMC...

Page 11: ...se 400 V 50 Hz 3 The values are calculated assuming the power supplies of three phase 480 V 50 Hz 4 The worst condition includes a phase loss in the supply line 11 4 Compliance with the Low Voltage Di...

Page 12: ...25 16 25 16 25 0 5 7 5 FRN0013C2S 4U 15 30 2 5 10 FRN0018C2S 4U 20 40 2 5 4 0 2 5 2 5 15 FRN0024C2S 4U 30 50 4 0 6 0 4 0 4 0 3 phase 400 V 20 FRN0030C2S 4U 40 60 6 0 10 6 0 6 0 0 5 MCCB Molded case ci...

Page 13: ...Power supply voltage Nominal applied motor HP Inverter type Fuse rating A 7 5 FRN0025C2S 2U 125 IEC60269 4 10 FRN0033C2S 2U 160 IEC60269 4 15 FRN0047C2S 2U 160 IEC60269 4 Three phase 200V 20 FRN0060C2...

Page 14: ...L certification means that UL has given certification for products to clear CSA Standards cUL certified products are equivalent to those compliant with CSA Standards 11 5 2 Considerations when using F...

Page 15: ...5 Install UL certified fuses rated 600Vac between the power supply and the inverter referring to the table below Required torque Ib in N m Wire size AWG or kcmil mm2 Control circuit Control circuit P...

Page 16: ...power source i e 3 phase 4 wire wye 480Y 277V so that the phase to ground rated system voltage is limited to 300V maximum 8 Maximum surrounding air temperature rating of 50 C Compact Inverter Instruc...

Reviews: