8.1.2  Three-phase 400 V class series 

Item

Specifications

Type (FRN_ _ _ _ C2S-4U) 

0013 

0018 

0024 

0030 

Applicable motor rating (HP) *1 

7.5 

10 

15 

20 

Rated capacity (kVA) *2 

9.9 

13 

18 

22 

Rated voltage (V) *3 

Three-phase, 380 to 480 V (with AVR function) 

Rated current (A) 

13.0 

18.0 

24.0 

30.0 

Overload capability 

150% of rated output current for 1 min or 200% of rated output 
current for 0.5 min 

Out

put Rating

Rated frequency (Hz) 

50

60 Hz 

Phases, voltage, fre-
quency 

Three-phase, 380 to 480 V, 50/60 Hz 

Voltage and frequency 
variations 

Voltage: +10 to -15% (Interphase voltage unbalance: 2% or less) 
*5, Frequency: +5 to -5%

(w/ DCR) 

10.6 

14.4 

21.1 

28.8 

Rated cur-
rent (A) *6 

(w/o DCR)

17.3 

23.2 

33.0 

43.8 

Input

 Ra

ting

Required power supply 
capacity (kVA) *7 

7.4

10

15

20

Torque (%) *8 

20 

DC braking 

Braking starting frequency*9: 0.0 to 60.0 Hz,  
Braking time: 0.0 to 30.0 s, Braking level: 0 to 100% 

Braking 

Braking transistor 

Built-in 

Applicable safety standards 

UL508C, IEC 61800-5-1: 2007 (under application) 

Enclosure 

IP20 (IEC 60529:1989), UL open type (UL50) 

Cooling method 

Fan cooling 

Mass (lbs) 

6.8

6.8

9.8

9.8

*1 Fuji 4-pole standard motors
*2  Refers to the rated capacity assuming the rated output voltage as 440 V for three-phase 400V series.
*3  Output voltages cannot exceed the power supply voltage.

*5

2004)

:

3

-

61800

IEC

to

(Refer

67

(V)

voltage

average

phase

-

3

(V)

e

Min.voltag

-

(V)

voltage

Max.

(%)

unbalance

voltage

Interphase

If this value is 2 to 3%, use an optional AC reactor (ACR). 

*6  Refers to the estimated value to apply when the power supply capacity is 500 kVA (inverter capacity x 10 when the

inverter capacity exceeds 50 kVA) and the inverter is connected to the %X = 5% power supply. 

*7  Refers to the value to apply when a DC reactor (DCR) is used.
*8  Refers to the average braking torque to apply when the motor running alone decelerates from 60 Hz with the AVR

control being OFF. (It varies with the efficiency of the motor.) 

*9  Available only for induction motor drive.

Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]

Summary of Contents for FRN0013C2S-4U

Page 1: ...E INR SI47 1745 E It describes the FRENIC C2S Inverter types FRN0025 to 0060C2S 2U and FRN0013 to 0030C2S 4U For other descriptions refer to the original manual Improper handling might result in incor...

Page 2: ...commended wire sizes The recommended wire sizes for the main circuit ter minals for an ambient temperature of 50 C are indicated for two types of wire HIV single wire for the maximum allowable tempera...

Page 3: ...the cable from the inverter to the motor is very long a high frequency current may be generated by stray capacitance between the cables and result in an overcurrent trip of the inverter an increase i...

Page 4: ...5 37 21 11 00 1 0 Three phase 200 V 20 FRN0060C2S 2U 2 8 48 50 15 00 1 0 7 5 FRN0013C2S 4U 4 9 10 24 5 50 0 5 10 FRN0018C2S 4U 4 4 12 86 7 50 0 5 15 FRN0024C2S 4U 3 5 18 60 11 00 1 0 Three phase 400...

Page 5: ...DB5 5 4 80 55 20 0 138 FRN0018C2S 4U DB7 5 4 60 38 0 188 FRN0024C2S 4U DB11 4 40 55 0 275 Three phase 400 V FRN0030C2S 4U DB15 4 1 34 4 75 10 0 375 5 10 ED Braking resistor Continuous braking 100 bra...

Page 6: ...nclosure IP20 IEC 60529 1989 UL open type UL50 Cooling method Fan cooling Mass lbs 6 8 6 8 9 8 9 8 1 Fuji 4 pole standard motors 2 Refers to the rated capacity assuming the rated output voltage as 220...

Page 7: ...able safety standards UL508C IEC 61800 5 1 2007 under application Enclosure IP20 IEC 60529 1989 UL open type UL50 Cooling method Fan cooling Mass lbs 6 8 6 8 9 8 9 8 1 Fuji 4 pole standard motors 2 Re...

Page 8: ...RN0025C2S 2U Three phase 200 V FRN0033C2S 2U FRN0013C2S 4U Three phase 400 V FRN0018C2S 4U Power supply voltage Inverter type FRN0047C2S 2U Three phase 200 V FRN0060C2S 2U FRN0024C2S 4U Three phase 40...

Page 9: ...10 FRN0018C2S 4U 20 40 15 FRN0024C2S 4U 30 50 Three phase 400 V 20 FRN0030C2S 4U 40 60 When connecting the inverter to the power supply add a recommended molded case circuit breaker MCCB or a residua...

Page 10: ...h the following standards Low Voltage Directive EN61800 5 1 2007 EMC Directives EN61800 3 2004 A1 2012 Immunity Second environment Industrial Emission Category C2 Applicable only when an optional EMC...

Page 11: ...se 400 V 50 Hz 3 The values are calculated assuming the power supplies of three phase 480 V 50 Hz 4 The worst condition includes a phase loss in the supply line 11 4 Compliance with the Low Voltage Di...

Page 12: ...25 16 25 16 25 0 5 7 5 FRN0013C2S 4U 15 30 2 5 10 FRN0018C2S 4U 20 40 2 5 4 0 2 5 2 5 15 FRN0024C2S 4U 30 50 4 0 6 0 4 0 4 0 3 phase 400 V 20 FRN0030C2S 4U 40 60 6 0 10 6 0 6 0 0 5 MCCB Molded case ci...

Page 13: ...Power supply voltage Nominal applied motor HP Inverter type Fuse rating A 7 5 FRN0025C2S 2U 125 IEC60269 4 10 FRN0033C2S 2U 160 IEC60269 4 15 FRN0047C2S 2U 160 IEC60269 4 Three phase 200V 20 FRN0060C2...

Page 14: ...L certification means that UL has given certification for products to clear CSA Standards cUL certified products are equivalent to those compliant with CSA Standards 11 5 2 Considerations when using F...

Page 15: ...5 Install UL certified fuses rated 600Vac between the power supply and the inverter referring to the table below Required torque Ib in N m Wire size AWG or kcmil mm2 Control circuit Control circuit P...

Page 16: ...power source i e 3 phase 4 wire wye 480Y 277V so that the phase to ground rated system voltage is limited to 300V maximum 8 Maximum surrounding air temperature rating of 50 C Compact Inverter Instruc...

Reviews: