Conformity to UL standards and Canadian standards

cUL certification

(Continued) 

*1  Denotes the relay contact terminals for [30A], [30B] and [30C].
*2  Denotes control terminals except for [30A], [30B] and [30C].

*3 Values in [ ] mean the size(AWG) of Grounding wire if exist.

6. To comply with CSA for 400VAC input models, transient surge suppression shall be installed

on the line side of this equipment and shall be rated 278V (phase to ground), 480V (phase to
phase), suitable for overvoltage category 3, and shall provide protection for a rated impulse
withstand voltage peak of 4kV.

7. All models rated 380-480 V input voltage ratings shall be connected to TN-C system power

source, i.e. 3-phase, 4-wire, wye (480Y/277V), so that the phase-to-ground rated system
voltage is limited to 300V maximum.

8. Maximum surrounding air temperature rating of 50 ºC.

Compact Inverter 

Instruction Manual 

Supplement for FRN-C2S-2U/4U

7.5 to 20HP

First Edition, March 2014 

Fuji Electric Co., Ltd. 

The purpose of this instruction manual is to provide accurate information in handling, setting up and 
operating of the FRENIC-Mini series of inverters. Please feel free to send your comments regarding 
any errors or omissions you may have found, or any suggestions you may have for generally im-
proving the manual.

In no event will Fuji Electric Co., Ltd. be liable for any direct or indirect damages resulting from the 
application of the information in this manual. 

Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]

Summary of Contents for FRN0013C2S-4U

Page 1: ...E INR SI47 1745 E It describes the FRENIC C2S Inverter types FRN0025 to 0060C2S 2U and FRN0013 to 0030C2S 4U For other descriptions refer to the original manual Improper handling might result in incor...

Page 2: ...commended wire sizes The recommended wire sizes for the main circuit ter minals for an ambient temperature of 50 C are indicated for two types of wire HIV single wire for the maximum allowable tempera...

Page 3: ...the cable from the inverter to the motor is very long a high frequency current may be generated by stray capacitance between the cables and result in an overcurrent trip of the inverter an increase i...

Page 4: ...5 37 21 11 00 1 0 Three phase 200 V 20 FRN0060C2S 2U 2 8 48 50 15 00 1 0 7 5 FRN0013C2S 4U 4 9 10 24 5 50 0 5 10 FRN0018C2S 4U 4 4 12 86 7 50 0 5 15 FRN0024C2S 4U 3 5 18 60 11 00 1 0 Three phase 400...

Page 5: ...DB5 5 4 80 55 20 0 138 FRN0018C2S 4U DB7 5 4 60 38 0 188 FRN0024C2S 4U DB11 4 40 55 0 275 Three phase 400 V FRN0030C2S 4U DB15 4 1 34 4 75 10 0 375 5 10 ED Braking resistor Continuous braking 100 bra...

Page 6: ...nclosure IP20 IEC 60529 1989 UL open type UL50 Cooling method Fan cooling Mass lbs 6 8 6 8 9 8 9 8 1 Fuji 4 pole standard motors 2 Refers to the rated capacity assuming the rated output voltage as 220...

Page 7: ...able safety standards UL508C IEC 61800 5 1 2007 under application Enclosure IP20 IEC 60529 1989 UL open type UL50 Cooling method Fan cooling Mass lbs 6 8 6 8 9 8 9 8 1 Fuji 4 pole standard motors 2 Re...

Page 8: ...RN0025C2S 2U Three phase 200 V FRN0033C2S 2U FRN0013C2S 4U Three phase 400 V FRN0018C2S 4U Power supply voltage Inverter type FRN0047C2S 2U Three phase 200 V FRN0060C2S 2U FRN0024C2S 4U Three phase 40...

Page 9: ...10 FRN0018C2S 4U 20 40 15 FRN0024C2S 4U 30 50 Three phase 400 V 20 FRN0030C2S 4U 40 60 When connecting the inverter to the power supply add a recommended molded case circuit breaker MCCB or a residua...

Page 10: ...h the following standards Low Voltage Directive EN61800 5 1 2007 EMC Directives EN61800 3 2004 A1 2012 Immunity Second environment Industrial Emission Category C2 Applicable only when an optional EMC...

Page 11: ...se 400 V 50 Hz 3 The values are calculated assuming the power supplies of three phase 480 V 50 Hz 4 The worst condition includes a phase loss in the supply line 11 4 Compliance with the Low Voltage Di...

Page 12: ...25 16 25 16 25 0 5 7 5 FRN0013C2S 4U 15 30 2 5 10 FRN0018C2S 4U 20 40 2 5 4 0 2 5 2 5 15 FRN0024C2S 4U 30 50 4 0 6 0 4 0 4 0 3 phase 400 V 20 FRN0030C2S 4U 40 60 6 0 10 6 0 6 0 0 5 MCCB Molded case ci...

Page 13: ...Power supply voltage Nominal applied motor HP Inverter type Fuse rating A 7 5 FRN0025C2S 2U 125 IEC60269 4 10 FRN0033C2S 2U 160 IEC60269 4 15 FRN0047C2S 2U 160 IEC60269 4 Three phase 200V 20 FRN0060C2...

Page 14: ...L certification means that UL has given certification for products to clear CSA Standards cUL certified products are equivalent to those compliant with CSA Standards 11 5 2 Considerations when using F...

Page 15: ...5 Install UL certified fuses rated 600Vac between the power supply and the inverter referring to the table below Required torque Ib in N m Wire size AWG or kcmil mm2 Control circuit Control circuit P...

Page 16: ...power source i e 3 phase 4 wire wye 480Y 277V so that the phase to ground rated system voltage is limited to 300V maximum 8 Maximum surrounding air temperature rating of 50 C Compact Inverter Instruc...

Reviews: