3-3
Conflict between the Remote Keypad and the built-in keypad on the FRENIC-Mini
When a Remote Keypad is connected to the FRENIC-Mini, the built-in keypad on the
FRENIC-Mini is automatically disabled to avoid conflicts between them, with the following
exceptions (for safety considerations).
When keypad operation is enabled (F02 = 0, 2, or 3) and the STOP key priority is selected
(H96 = 1 or 3), the
key on the FRENIC-Mini is also enabled so that the FRENIC-Mini
can be stopped by either
key. The
key on the FRENIC-Mini is also enabled to
perform an alarm reset.
In any event, the 7-segment LED monitor on the FRENIC-Mini displays the same
information as that on the Remote Keypad.
3.3 Data
Copying
Menu #7 of "Data copying" allows you to read function code data out of FRENIC-Mini inverter (for
which function codes have already been set up), to store the function code data block into another
inverter, or to verify function code data. That is, this function compares the function code data saved
in the Remote Keypad with that stored in the inverter.
The following conditions and restrictions apply to data copying:
Some function code data cannot be copied (stored) into another inverter.
For safety considerations, some function code data cannot be copied to another inverter if the
specifications of the destination inverter are different from those of the source inverter. Which
function code data can or cannot be copied is summarized in the FRENIC-Mini Instruction Manual
(INR-SI47-0791-E), Chapter 5, the "Data copy" column of Section 5.1 "Function Code Tables," using
the following designations:
Y : Can be copied unconditionally.
Y
1
:
Cannot be copied if the rated capacity differs from the source inverter.
Y
2
:
Cannot be copied if the rated input voltage differs from the source inverter.
N : Cannot be copied in any situation.
(
The function codes marked with N cannot be verified,
either.
Set up manually function code data that cannot be copied individually as necessary, by using Menu
#1 "Data setting" in Programming mode.
If you cannot copy function code data:
Check whether the "
E
" or "
CPE
" indicator is blinking.
(1) "
E
" is blinking ("Write error"): The following cases can be thought of:
• The memory of the Remote Keypad contains no data. (You have not read the memory since
delivery or you have aborted a data read operation.)
• The memory of the Remote Keypad contains some invalid or abnormal data.
• The destination inverter type differs from the source inverter type.
• A write operation has been performed while the inverter is running.
• The inverter is in data protection mode.
• The "Enable editing of function code data from keypad" command (WE-KP) is off.
(2) "
CPE
" is blinking: The following cases can be thought of:
• The function codes stored in the Remote Keypad are not compatible with those stored in the
inverter. Non-standard function code data may have been stored, or the inverter may have
been upgraded in an incompatible manner. Consult your Fuji Electric sales office.