As a result of self-diagnosis, the message below is appeared on the LCD display, when there are trouble in the
transmitter. For each error, its cause and remedy are suggested.
Error display of
self-diagnosis
Display in normal
mode
Cause
Remedy
C1 ERR
~
C9 ERR
FL-1
Error of detecting unit
Check the wiring between the de-
tecting unit and transmitter.
If the error is not recovered, re-
place the detecting unit.
RAM ER
FL-1
Calculation parameter (RAM) error
5HSODFHPHQWRIDPSOL¿HU
PAR ER
Error of magnitude relation of tem-
perature data
AMP EP
FL-2
((3520HUURURQDPSOL¿HUVLGH
5HSODFHPHQWRIDPSOL¿HU
CEL EP
FL-3
EEPROM error on cell side
Replacement of detecting unit
AMP TMP
T. ALm
$PSOL¿HUWHPSHUDWXUHHUURU
Transmitter temperature is normal-
ized.
CEL TMP
T. ALm
Cell temperature error
OVER
Input pressure: J-2, saturation cur-
rent (Hi) or higher
Correction of input pressure
UNDER
Input pressure: J-1, saturation cur-
rent (Lo) or lower
Correction of input pressure
Menu D : Self-diagnosis
Self-diagnosis display shows the internal temperature
of the transmitter and the failure description.
d-1 AMPTMP : Internal temperature of the transmit-
ter
• Press the key on the screen
c
to display the
screen of internal temperature of the transmitter (
d
).
When a temperature alarm is issued, “TEMP” is
changed to “ALM.”
(This corresponds to “AMP TMP” of “Error display of
self-diagnosis” in the following table.)
If the temperature cannot be measured due to defec-
tive internal data, “IMPOSS” is displayed.
(This corresponds to any of “RAM ER”, “PAR ER” or
“AMP EP” of “Error display of self-diagnosis” in the
following table.)
d-2 ALMCHK : Display of self-diagnosis results
• Press the key on the screen
e
to show the self-di-
agnosis results (
f
).
Press the and keys to display errors sequential-
ly.
See the following table “Contents of message” for
the errors of the transmitter.