11
WWW.FUHR.DE
multitronic
881/881GL
Terminal/
Function
Assignment
Grid
1(GND) + 2(+12 V)
Stabilized power supply 12 V DC ±4 %.
Outputs
3 + 4
Switching output
Output, e. g. for electric swing door drives
Make contact
After motorized opening of the
multitronic
lock, the contact is switched for 2 seconds.
5 + 6
Alarm output
Output locking position, e. g. for alarm systems
Break contact
Feedback signal door locked/unlocked. After opening of the
multitronic
lock and/or opening of
the door leaf, the contact is switched.
Inputs
7 + 8
Door opening
Input
6–12 V AC / 6–24 V DC
For
non-isolated opening pulses
by access control systems, e. g. of intercom or building control
systems for short-time unlocking or day latch function.
Pending signal > 1 second: After opening the door leaf or after 5 seconds, the lock’s latch protrudes.
The locking elements remain retracted.
9 + 10
Door opening
Input potential-free
For
potential-free opening pulses
by access control systems for short-time and permanent
unlocking.
For the duration of the pending signal, all locking elements of the
multitronic
lock remain retracted,
e. g. for permanent unlocking, controlled by time switch.
11 + 12
Door opening
Input potential-free
For
potential-free opening pulses
by access control systems for short-time unlocking or day latch
function.
Pending signal > 1 second: After opening the door leaf or after 5 seconds, the lock’s latch protrudes.
The locking elements remain retracted.
13 – 15
Already occupied by the electricity and data transmission.
16 + 17
Deactivation
Input potential-free
For the duration of the pending signal, all motor opening functions (control: radio receiver and input
terminals 7–12 / control in motor drive: terminals 4 and 7) are deactivated, e. g. to prevent the
motorized door opening after arming an alarm system.
Jumper DRT
When the
jumper DRT is removed
, the output at terminal 3 + 4 remains connected as long as a
conti nuous signal at terminal 9 + 10 is applied.
Jumper TGF
When the
jumper TGF is removed
, the locking elements, however not the latch, is retracted when
switching the input at terminal 11+12 with a signal > 1 sec.
Radio receiver
For
opening pulses via FUHR rolling code access control systems
, refer to page 4 ff.
5.1 Explanation of the control unit
1
EN