Maintenance and service

4.1 

Zero point correction

The zero position of a pressure sensor shifts over time due to external influences and the condition of the piezoresistive 

sensor element. It is therefore recommended to carry out a zero point correction before commissioning and at annual inter-
vals thereafter. To do this, connect the supply voltage to terminals 1 and 2 and then press the „S“ key. The current measured 
value is now zeroed.

  Danger

When working on the open device, always ensure that either the supply voltage is interrupted or suitable  

 

protective measures have been taken against contact with live parts.

4.2 Cleaning

Cleaning of the equipment can be done with a damp cloth. Remove external soiling from the housing, the connections and 
the display.

Notice

Do not use sprays, solvents, alcohol-based cleaners or abrasive cleaners to dampen the cloth. 
Remove soiling of the housing, the connectors and the display.

4.3 Repair

  

Notice

 

Repairs  may  only  be  carried  out  by  the  manufacturer  or  appropriately  authorized  and  qualified  personnel. 

 

 

If changes are made to the device independently, the warranty will expire.

Accessories and spare parts

The scope of accessories may vary depending on the order variation. All possible accessories are listed in Chapter 3.1 Scope 
of delivery. Spare parts are to be obtained exclusively from the manufacturer. The replacement of the spare parts may only be 
done by the manufacturer or an authorized technician.

Technical data

Technical data can be found in the corresponding data sheet, which is available at www.fsm.ag, or can be downloaded 
using the QR code below.

7 Disposal

 

Danger

 

Incorrect disposal can result in hazards for the environment. Device components and packaging materials must 

 

be disposed of in an environmentally friendly manner in accordance with the country-specific waste treatment and 

 

 

disposal regulations.

Summary of Contents for DS01+

Page 1: ...FSM AG Erich Rieder Straße 2 D 79199 Kirchzarten messtechnik fsm ag www fsm ag 27 04 2021 1 6 Operating instructions Pressure transducer DS01 ...

Page 2: ... and foreseeable misuse 3 1 4 Functions 3 2 Notes for your safety 3 3 Installation and start up 4 3 1 Scope of delivery 4 3 2 Assembly 4 3 3 Start up 4 3 3 1 Connection 4 3 3 2 Setting the measuring range 4 3 3 3 Setting the output signal 5 3 3 4 Setting the time constant 5 4 Maintenance and service 6 4 1 Zero point correction 6 4 2 Cleaning 6 4 3 Repair 6 5 Accessories and spare parts 6 6 Technic...

Page 3: ...ed use and foreseeable misuse The DS01 differential pressure transmitter is used to detect low pressures and convert them into a pressure proportional measuring signal The device may only be used in the specified measuring range Only differential pressures of non aggressive gases may be measured with the DS01 Notice Do not use the device in explosive atmospheres or for measurement of aggressive ga...

Page 4: ...of sources of interference or heat 3 3 Start up 3 3 1 Connection Connect the supply voltage as well as the output wiring according to the connection diagram For this purpose run the cables through the cable glands attached to the housing and connect them to the screw terminals provided In order to guarantee the specified accuracy the sensor should only be fully put into operation after a run in ti...

Page 5: ...Pa 0 100 hPa Off Off Off 0 75 hPa On Off Off 0 50 hPa Off On Off 0 25 hPa On On Off 100 100 hPa Off Off On 75 75 hPa On Off On 50 50 hPa Off On On 25 25 hPa On On On 3 3 3 Setting the output signal You can adapt the respective desired analog output to your application via the DIP switch S4 The respective setting options can be found in the following table Output signal Position S4 0 10 V 4 20 mA O...

Page 6: ...s solvents alcohol based cleaners or abrasive cleaners to dampen the cloth Remove soiling of the housing the connectors and the display 4 3 Repair Notice Repairs may only be carried out by the manufacturer or appropriately authorized and qualified personnel If changes are made to the device independently the warranty will expire 5 Accessories and spare parts The scope of accessories may vary depen...

Reviews: