FSM AG | Erich-Rieder-Straße 2 | D-79199 Kirchzarten | [email protected] | www.fsm.ag
27.04.2021
5 | 6
You can adapt the respective desired measuring range to your application via the DIP switches S1, S2 and S3. The respective
setting options can be found in the following table:
Basic measuring range
Measuring range
Position S1
Position S2
Position S3
10 hPa
0… 10 hPa
Off
Off
Off
0… 7,5 hPa
On
Off
Off
0… 5,0 hPa
Off
On
Off
0… 2,5 hPa
On
On
Off
-10… 10 hPa
Off
Off
On
-7,5… 7,5 hPa
On
Off
On
-5,0… 5,0 hPa
Off
On
On
-2,5… 2,5 hPa
On
On
On
100 hPa
0… 100 hPa
Off
Off
Off
0… 75 hPa
On
Off
Off
0… 50 hPa
Off
On
Off
0… 25 hPa
On
On
Off
-100… 100 hPa
Off
Off
On
-75… 75 hPa
On
Off
On
-50… 50 hPa
Off
On
On
-25… 25 hPa
On
On
On
3.3.3 Setting the output signal
You can adapt the respective desired analog output to your application via the DIP switch S4. The respective setting options
can be found in the following table:
Output signal
Position S4
0… 10 V / 4… 20 mA
Off
2… 10 V / 0… 20 mA
On
3.3.4 Setting the time constant
You can adapt the respective desired time constant to your application via the DIP switches S5 and S6. The respective setting
options can be found in the following table:
Time constant
Position S5
Position S6
50 ms
Off
Off
500 ms
On
Off
2000 ms / 2 s
Off
On
4000 ms / 4 s
On
On