You can adapt the respective desired measuring range to your application via the DIP switches S1, S2 and S3. The respective 
setting options can be found in the following table:

Basic measuring range

Measuring range

Position S1

Position S2

Position S3

10 hPa

0… 10 hPa 

Off

Off

Off

0… 7,5 hPa 

On

Off

Off

0… 5,0 hPa 

Off

On

Off

0… 2,5 hPa 

On

On

Off

-10… 10 hPa 

Off

Off

On

-7,5… 7,5 hPa 

On

Off

On

-5,0… 5,0 hPa 

Off

On

On

-2,5… 2,5 hPa 

On

On

On

100 hPa

0… 100 hPa 

Off

Off

Off

0… 75 hPa 

On

Off

Off

0… 50 hPa 

Off

On

Off

0… 25 hPa 

On

On

Off

-100… 100 hPa 

Off

Off

On

-75… 75 hPa 

On

Off

On

-50… 50 hPa 

Off

On

On

-25… 25 hPa 

On

On

On

3.3.3  Setting the output signal

You can adapt the respective desired analog output to your application via the DIP switch S4. The respective setting options 
can be found in the following table:

Output signal

Position S4

0… 10 V / 4… 20 mA

Off

2… 10 V / 0… 20 mA

On

3.3.4  Setting the time constant

You can adapt the respective desired time constant to your application via the DIP switches S5 and S6. The respective setting 
options can be found in the following table:

Time constant

Position S5

Position S6

50 ms

Off

Off

500 ms

On

Off

2000 ms / 2 s

Off

On

4000 ms / 4 s

On

On

Summary of Contents for DS01+

Page 1: ...FSM AG Erich Rieder Straße 2 D 79199 Kirchzarten messtechnik fsm ag www fsm ag 27 04 2021 1 6 Operating instructions Pressure transducer DS01 ...

Page 2: ... and foreseeable misuse 3 1 4 Functions 3 2 Notes for your safety 3 3 Installation and start up 4 3 1 Scope of delivery 4 3 2 Assembly 4 3 3 Start up 4 3 3 1 Connection 4 3 3 2 Setting the measuring range 4 3 3 3 Setting the output signal 5 3 3 4 Setting the time constant 5 4 Maintenance and service 6 4 1 Zero point correction 6 4 2 Cleaning 6 4 3 Repair 6 5 Accessories and spare parts 6 6 Technic...

Page 3: ...ed use and foreseeable misuse The DS01 differential pressure transmitter is used to detect low pressures and convert them into a pressure proportional measuring signal The device may only be used in the specified measuring range Only differential pressures of non aggressive gases may be measured with the DS01 Notice Do not use the device in explosive atmospheres or for measurement of aggressive ga...

Page 4: ...of sources of interference or heat 3 3 Start up 3 3 1 Connection Connect the supply voltage as well as the output wiring according to the connection diagram For this purpose run the cables through the cable glands attached to the housing and connect them to the screw terminals provided In order to guarantee the specified accuracy the sensor should only be fully put into operation after a run in ti...

Page 5: ...Pa 0 100 hPa Off Off Off 0 75 hPa On Off Off 0 50 hPa Off On Off 0 25 hPa On On Off 100 100 hPa Off Off On 75 75 hPa On Off On 50 50 hPa Off On On 25 25 hPa On On On 3 3 3 Setting the output signal You can adapt the respective desired analog output to your application via the DIP switch S4 The respective setting options can be found in the following table Output signal Position S4 0 10 V 4 20 mA O...

Page 6: ...s solvents alcohol based cleaners or abrasive cleaners to dampen the cloth Remove soiling of the housing the connectors and the display 4 3 Repair Notice Repairs may only be carried out by the manufacturer or appropriately authorized and qualified personnel If changes are made to the device independently the warranty will expire 5 Accessories and spare parts The scope of accessories may vary depen...

Reviews: