Replacing String Fuses
Safety
Preparation
Interrupt the connection to the AC supply lines using the inverter AC disconnector
Disconnect solar module strings from the Fronius String Control 100/12
Attach a clearly legible and easy-to-understand warning sign to prevent anyone from
switching it back on or from reconnecting any open or interrupted connections
Check to make sure that solar module strings are not charged
Short circuit the solar module strings
Remove the cover
Test the fuse holder at the terminals for continuity
Replacing String
Fuses
Find out and rectify the cause of the defective fuse
Finally...
Reattach the cover
Remove the short circuit of the solar module strings
Disconnect solar module strings from the Fronius String Control 100/12
Reestablish the connection to the AC supply lines using the inverter AC disconnector
WARNING!
Work performed incorrectly can cause serious injury and damage.
Only trained and qualified personnel may carry out the activities described in the
following. Follow the safety rules in these operating instructions.
WARNING!
An electric shock can be fatal. Danger from DC voltage from solar
modules.
-
Make sure that the input and output sides in front of the device are not
charged before conducting maintenance work.
-
Never remove a fuse while it is under load.
1
2
3
4
5
6
7
NOTE!
Only use fuses for solar modules that meet the proper requirements for
string fuses.
Fuse dimensions: Diameter 10 x 38 mm
1
2
3
1
2
3
4
Summary of Contents for String Control 100/12
Page 2: ...0...
Page 4: ...2...
Page 19: ...17 DE 1 3 4 2 3 1 3 5 4 2 4x 4x 4...
Page 47: ...45 DE...
Page 48: ...46...
Page 50: ...48...
Page 65: ...63 EN US 1 3 4 2 3 1 3 5 4 2 4x 4x 4...
Page 92: ...90...
Page 94: ...92...
Page 109: ...107 NL 1 3 4 2 3 1 3 5 4 2 4x 4x 4...
Page 137: ...135 NL...
Page 138: ...136...
Page 139: ...137 KO Fronius...
Page 140: ...138...
Page 143: ...141 KO 3...
Page 144: ...142...
Page 145: ...143 KO EMC EMC ESD A B EMC ESD 3 CE...
Page 146: ...144 2002 96 EC...
Page 151: ...149 KO Fronius 100 12 Fronius 100 12 13 14 15 16 1 2 3 4 5 6 8 7 12 9 10 11...
Page 154: ...152 1 3 4 2 3 1 3 5 4 2 4x 4x 4...
Page 156: ...154 Fronius 100 12 M16 3 0Nm 2 0Nm M20 6 0Nm 4 0Nm M25 8 0Nm 5 0Nm M32 10 0Nm 6 5Nm...
Page 159: ...157 KO DC DC IN...
Page 161: ...159 KO PV PV PV DC OUT...
Page 164: ...162 PV 20A 12 PV 50A 100A 10 x 38mm PV PV DC PV 1 2...
Page 174: ...172 Fronius 100 12 Fronius 100 12 PV DC 1 1 1 1 2 3 4 5 1...
Page 176: ...174 2 PV Fronius 100 12 Fronius 100 12 Fronius 5 10 PV Ah...
Page 180: ...178...
Page 181: ...179 KO...