power and by "Cos
φ
Minimum". For the characteristic curves, the data points
must be entered in the X
‑
axis (effective power) and in the Y
‑
axis (Cos
φ
).
Point
Parameter
Range of val-
ues
Description
1
"Active Power
(% of Nominal
Apparent
Power)"
0 %
‑
100 %
Effective power in percent
[%] related to the nominal ap-
parent power S
n
.
"cos
φ
- Power
Factor"
0
‑
1
Set value of Cos
φ
.
"Direction / Ex-
citation"
The current direction corres-
ponds to the generator
counter arrow system.
Under-Excited
Under-excited operation = in-
ductive operation = reactive
power is drawn = reactive cur-
rent is fed in ahead of the
active current.
Over-Excited
Over-excited operation = ca-
pacitive operation = reactive
power is supplied = reactive
current is fed in lagging the
active current.
2
"Active Power
(% of Nominal
Apparent
Power)"
0 %
‑
100 %
Effective power in percent
[%] related to the nominal ap-
parent power S
N
.
"cos
φ
- Power
Factor"
0
‑
1
Set value of Cos
φ
.
"Direction / Ex-
citation"
The current direction corres-
ponds to the generator
counter arrow system.
Under-Excited
Under-excited operation = in-
ductive operation = reactive
power is drawn = reactive cur-
rent is fed in ahead of the
active current.
Over-Excited
Over-excited operation = ca-
pacitive operation = reactive
power is supplied = reactive
current is fed in lagging the
active current.
64