![Fronius Primo GEN24 Operating Instructions Manual Download Page 45](http://html1.mh-extra.com/html/fronius/primo-gen24/primo-gen24_operating-instructions-manual_2339203045.webp)
Example 3
Description of the parameters
-
"P(f) Mode": On (with Hys-
teresis)
-
"Configuration Method":
Gradient
-
"Active Grid Support": Off
-
"Calculation Mode Under-
frequency": P
max
= P
m
-
P
n
(k*df)
-
"Calculation Mode Over-
frequency": P
max
= P
m
-
P
n
(k*df)
(1)
Momentary effective power when the
respective "Activation Threshold" is
reached: 60 % of P
n
(nominal power).
(2)
"Gradient Underfrequency": 80 %/Hz
(3)
"Activation Threshold Underfre-
quency": 49.7 Hz
(4)
"Lower Deactivation Threshold Under-
frequency": 49.9 Hz
(5)
"Upper Deactivation Threshold Under-
frequency": 50.1 Hz
(6)
"Gradient Overfrequency": 60 %/Hz
(7)
"Activation Threshold Overfrequency":
50.3 Hz
(8)
"Lower Deactivation Threshold Over-
frequency": 49.9 Hz
(9)
"Upper Deactivation Threshold Over-
frequency": 50.1 Hz
(10)
"Deactivation Time": 30 s
General power curve with overfrequency and underfrequency with hysteresis with gradients.