Example 2
Description of the parameters
-
"P(f) Mode": On (without
Hysteresis)
-
"Configuration Method":
Stop frequency
-
"Active Grid Support": Off
(1)
Momentary effective power when the
respective "Activation Threshold" is
reached: 60 % of P
n
(nominal power).
(2)
"Activation Threshold Underfre-
quency": 49.7 Hz
(3)
"Stop Frequency - Underfrequency":
49.0 Hz
(4)
"Power at Stop Frequency - Underfre-
quency": 85 %
(5)
"Activation Threshold Overfrequency":
50.3 Hz
(6)
"Stop Frequency - Overfrequency":
51.3 Hz
(7)
"Power at Stop Frequency - Overfre-
quency": 20 %
General power curve with overfrequency and underfrequency without hysteresis with stop frequency.