General settings
Parameter
Range of val-
ues
Description
"Mode"
Reactive power mode selection option.
The following modes are described in the
subchapters.
Off
No reactive power is fed in.
Cos
φ
- Con-
stant Power
Factor
Constant Cos
φ
.
Q Absolute -
Constant Re-
active Power
Constant reactive power in [Var].
Q Relative -
Constant Re-
active Power
Constant reactive power in percent [%] of
S
n
.
Cos
φ
(P) -
Power depend-
ent Power
Factor Charac-
teristic
Effective power-dependent Cos
φ
control.
Q(P) - Power
dependent Re-
active Power
Characteristic
Effective power-dependent reactive power
control.
Q(U) - Voltage
dependent Re-
active Power
Characteristic
Mains voltage dependent reactive power
control.
"P/Q Priority"
Q Priority
When the maximum apparent power is
reached, the setting "Q Priority" leads to a
reduction of the effective power in favour
of reaching the reactive power specifica-
tion.
P Priority
The setting "P Priority" leads to a reduc-
tion of the reactive power in favour of
reaching the available effective power
when the maximum apparent power is
reached.
"Cos
φ
Minim-
um"
0
‑
1
Minimum cos
φ
, which together with the
maximum apparent power forms an addi-
tional limitation of the reactive power at
low effective power.
60