Single MPP Tracker mode with just one string on a Multi MPP Tracker inverter:
Connecting just one string to a Multi MPP Track-
er inverter
If only one string is used for connec-
tion to the inverter, connection DC+1
(pin 2) and DC+2 (pin 1) must be
bridged.
The cable cross section of the DC con-
necting line and bridging must be the
same. Bridging the DC terminal is not
necessary because it is bridged intern-
ally.
Set MPP TRACKER 2 to "OFF" when
starting for the first time (also possible
in the basic menu subsequently).
If the Multi MPP Tracker inverter is op-
erated in Single MPP Tracker mode,
the currents of the connected DC lines
are distributed evenly across both in-
puts.
Multi MPP
Tracker Inverter
– Fronius Primo
10.0–15.0
Multi MPP Tracker inverters have 2 independent DC inputs (MPP Tracker). These
inputs can be connected to a number of different modules.
MPP Tracker 1 has 4 DC+ terminals.
MPP Tracker 2 has 2 DC+ terminals.
There are a total of 6 DC- terminals.
Connecting 2-6 strings in Multi MPP Tracker mode:
DC-1
PV 1
PV 1
PV 2
DC+1
DC-2
DC+2
MPP1: each Terminal
I
max
= 15 A
1
DC
+1
DC
+2
DC
-1
DC
-2
2
1 2 3 4 1 2
3
1 2
4
Connecting two solar module fields to a Multi
MPP Tracker inverter
Connect the strings separately to the
two MPP Tracker inputs (DC+1/DC+2).
The DC- terminals can be used as de-
sired, since they are connected intern-
ally.
Set MPP TRACKER 2 to "ON" when
starting for the first time (also possible
in the basic menu subsequently).
38
Summary of Contents for Primo 10.0-1 208-240
Page 2: ......
Page 13: ...Preparation 13...
Page 14: ...14...
Page 21: ...AC 21...
Page 22: ...22...
Page 31: ...DC 31...
Page 32: ...32...
Page 42: ...2 2 1 max 0 28 in 7 mm 8 Fit the padlock to the anti theft device 42...
Page 50: ...50...
Page 51: ...51 EN US...
Page 52: ......