Max. ambient temperatures:
-40°F to +140°F
(-40°C to +60°C)
Relative humidity:
0 - 100%
The air flow direction within
the inverter is from right to
top (cold air intake on the
right, hot air outflow at the
top).
When installing the inverter in a switch cabinet or similar closed environment, it
is necessary to make sure that the hot air that develops will be dissipated by
forced-air ventilation
If you wish to install the inverter on the outer walls of a cattle shed, it is import-
ant to maintain a minimum clearance of 6 ft. 7 in. (2 m) between all sides of the
inverter and air vents and other openings.
The place of installation should not be exposed to ammonia, corrosive gases,
salts, or acids.
Example: Install-
ation of several
inverters
12