17
EN
Wiring diagram variant 1: Signal contact for overvoltage protection
Depending on the setting in the Basic menu, the DC OVP option (overvoltage protection)
either outputs a warning or an error on the display. Further information on the DC OVP op-
tion can be found in the installation instructions.
Wiring diagram variant 2: S0 meter
A meter for recording the self-consumption of each S0 can be connected directly to the in-
verter. This S0 meter can be positioned directly at the feed-in point or in the consumption
branch. As one of the settings on the Fronius Datamanager website, a dynamic power re-
duction can be set under the "EVU Editor" menu subitem (see Fronius Datamanager op-
erating instructions under
www.fronius.com/QR-link/4204260173EA)
IMPORTANT!
In order to connect an S0 meter to the inverter, it may be necessary to up-
date the inverter firmware.
Requirements for the S0 meter:
-
Must comply with the IEC62053-31 Class B standard
-
Max. voltage 15 V DC
-
Max. current when ON 15 mA
-
Min. current when ON 2 mA
-
Max. current when OFF 0.15 mA
Recommended max. pulse rate of the S0 meter:
PV output kWp [kW]
Max. pulse rate per kWp
30
1000
20
2000
10
5000
≤
5.5
10,000
Pin 1
Pin 2
Pin 1
Pin 2
S0 +
S0 -