39
EN
Version
Displays the version and serial numbers of the PC boards in the inverter (e.g. for service
purposes)
Grid monitoring:
GMTi - start-up time of inverter in s
GMTr - reconnection time in s following a grid fault
ULL - mean grid voltage over 10 minutes in V.
LLTrip - trip time for long-term voltage monitoring
Grid voltage limits:
UILmax - upper inner grid voltage in V
UILmin - lower inner grid voltage in V
Grid frequency limits:
FILmax - upper inner grid frequency in Hz
FILmin - lower inner grid frequency in Hz
Q-mode:
Current cos phi power factor setting
(e.g. Constant Cos(phi) / Constant Q / Q(U) characteristic / etc.)
AC power limit:
Max. P AC - manual power reduction
AC voltage derating:
Status - ON / OFF voltage-dependent power reduction
GVDPRe - threshold from which the voltage-dependent power
reduction begins
GVDPRv - reduction gradient used to reduce the power, e.g.
10% per volt above the GVDPRe threshold.
Message - activates the sending of an info message via Fronius
Solar Net
Fault Ride Through:
Status – Default setting: OFF
If the function is activated, the inverter does not switch off im-
mediately in the event of a short-term AC voltage dip (outside of
the limits specified by the grid supplier), but instead continues
to feed in power for a defined period.
DB min – Default setting: 90%
"Dead Band Minimum" setting in per cent
DB max - Default setting: 120%
"Dead Band Maximum" setting in per cent
k-Fac. - Default setting: 0
Display area
Display / Display Software / Integrity Checksum / Memory Card
/ Memory Card #1 / Power Stage / Power Stage Software / EMI
Filter / Power Stage #3 / Power Stage #4