59
EN
Fronius Symo
15.0-3-M
17.5-3-M
20.0-3-M
Input data
MPP voltage range
320 - 800 V DC
370 - 800 V DC
420 - 800 V DC
Max. input voltage
(at 1,000 W/m² / -10 °C in an open circuit)
1000 V DC
Min. input voltage
200 V DC
Max. input current (MPP1 / MPP2)
(MPP1 + MPP2)
33.0 / 27.0 A
51.0 A
Max. short circuit current of the solar mod-
ules (I
SC PV
) (MPP1 / MPP2)
49.5 / 40.5 A
Max. feedback current
4)
49.5 / 40.5 A
Output data
Nominal output power (P
nom
)
15,000 W
17,500 W
20,000 W
Max. output power
15,000 W
17,500 W
20,000 W
Nominal grid voltage
3~ NPE 400 / 230 V or 3~ NPE 380 / 220
Min. grid voltage
150 V / 260 V
Max. grid voltage
280 V / 485 V
Nominal output current at 220 / 230 V
22.7 / 21.7 A
26.5 / 25.4 A
30.3 / 29 A
Max. output current
32 A
Nominal frequency
50 / 60 Hz
1)
Total harmonic distortion
< 1.5%
< 1.5%
< 1.25%
cos phi power factor
0 - 1 ind./cap.
2)
Max. output fault current per period
64 A / 2.34 ms
General data
Maximum efficiency
98%
European efficiency U
DCmin
/ U
DCnom
/
U
DCmax
96.2 / 97.6 / 97.1%
96.4 / 97.7 / 97.2%
96.5 / 97.8 / 97.3%
Overnight self-consumption
0.7 W & 117 VA
Cooling
Controlled forced-air ventilation
Degree of protection
IP 66
Dimensions h x w x d
725 x 510 x 225 mm
Weight
43.4 kg / 43.2 kg
Permissible ambient temperature
- 25 °C - +60 °C
Permitted humidity
0 - 100%
EMC device class
B
Overvoltage category DC / AC
2 / 3
Pollution level
2
Noise emission
65 dB(A) (ref. 1pW)
Protection devices
DC insulation measurement
Integrated
Response to DC overload
Operating point shift, power limitation
DC disconnector
Integrated
RCMU
Integrated
Summary of Contents for 25.0-3-S
Page 2: ...2 ...
Page 4: ...4 ...
Page 64: ...64 ...
Page 126: ...126 ...
Page 128: ...128 ...
Page 170: ...170 Entrada de sinal Ext Sig Tipo de acionamento Warning Tipo de conexão N C ...
Page 189: ...189 PT BR ...