NOTE!
When connecting aluminum cables:
▶
Follow all national and international guidelines regarding the connection of aluminum
cables.
▶
Follow the instructions of the cable manufacturer, especially the note about whether
an annual check to ensure that the cables are firmly attached should be performed.
NOTE!
Form a min. 4 in. (100 mm) cable loop with all cables.
NOTE!
To ensure that the inverter operates without any problems:
▶
Make sure that the grid's neutral conductor is grounded. For insulated networks
(without grounding), this is not the case, and operation of the inverter is not possible.
▶
A neutral conductor is required for measurement purposes when operating the
inverter. The neutral conductor must have a current carrying capacity of at least 1 A.
Permitted cables
AC cables with the following design can be connected to the AC terminals of the inverter:
Cu / Al Cu
-
Copper (Cu) or aluminum (Al): round, solid
-
Copper: round, stranded, up to conductor class 4
AC & DC = copper cables (Cu)
The following wire combinations can be used for wiring.
Select a sufficiently large cable cross-section based on the actual device output!
AWG
roun
d
AWG
stran-
ded
AWG
stranded/round
AWG
round/round
AWG
stranded/stranded
4
2)
6
2)
6/6
4)
6/12
2)
6/14
2)
6/16
3)
8
2)
8
1)
8/10
1)
8/12
1)
8/14
1)
8/12
2)
8/10
2)
8/12
1)
8/14
1)
8/16
3)
10
2)
10
1)
10/10
1)
10/12
1)
10/14
1)
10/10
1)
10/12
1)
10/14
1)
10/16
3)
12
2)
12
1)
12/10
1)
12/12
1)
12/14
1)
12/16
1)
12/10
1)
12/12
1)
12/14
1)
12/16
1)
14
2)
14
1)
14/10
1)
14/12
1)
14/14
1)
14/16
1)
14/10
1)
14/12
1)
14/14
1)
14/16
1)
16
3)
16
3)
16/14
1)
16/16
1)
16/10
3)
16/12
1)
16/14
1)
16/16
1)
25
EN-US
Summary of Contents for 10.0-3 208-240
Page 2: ......
Page 13: ...Preparation 13...
Page 14: ...14...
Page 20: ...1 2 20...
Page 21: ...AC 21...
Page 22: ...22...
Page 31: ...DC 31...
Page 32: ...32...
Page 41: ...Laying Solar Net Cables 41...
Page 42: ...42...
Page 43: ...Data communication Lay data commu nication cables 1 2 3 4 5 22 lbf in 2 5 Nm 6 43 EN US...
Page 45: ...1 2 1 3 TX20 10 6 lbf in 1 2 Nm 1 2 4 5 45 EN US...
Page 46: ...46...
Page 47: ...Finally 47...
Page 48: ...48...
Page 51: ...4 3 in 1 ON OFF Lock 22 1 lbf in 2 5 Nm 2 3 4 51 EN US...
Page 52: ...22 1 lbf in 2 5 Nm 5 6 AC ON 2 ON OFF Lock 1 7 52...
Page 55: ...Options 55...
Page 56: ...56...
Page 62: ...62...
Page 63: ...Care and maintenance 63...
Page 64: ...64...
Page 66: ...66...
Page 67: ...67 EN US...