3.2 Technical specifications
Description
TX
150
200
250
Rated heat output
kW
150
199
250
Output range
kW
45 – 150
59 - 199
75 – 250
Electrical connection
400V / 50Hz /
C20A
400V / 50Hz / C35A
Total weight of boiler
kg
2730
3390
3390
Weight – retort
855
1120
1120
Weight - heat exchanger
1000
1280
1280
Boiler capacity (water)
l
440
570
570
Water pressure drop
(ΔT = 10 / 20 K)
mbar
36 / 12
55 / 18
74 / 25
Min. boiler return temperature
°C
65
Max. permitted operating temperature
°C
90
Permitted operating pressure
bar
3
Boiler class as per EN 303-5:1999
(pr EN 303-5:2012)
3 (5)
Permitted fuel as per EN 14961
1)
Part 2: Wood pellets class A1 / D06
Part 4: Wood chips class A2 / P16A-P45A
Airborne sound level
dB(A)
< 70
150
200
250
Testing institute
TÜV
2)
TÜV
3) 4)
TÜV
2)
Test report no.
10-UW/Wels-
EX-119
13-U-032/SD
11-UW/Wels-
EX-249
1.Detailed information on the fuel is included in the operating instructions, in the section on "Permitted fuels"
2.TÜV Austria Services GmbH, Geschäftsbereich Umweltschutz, Am Thalbach 15, A-4600 Thalheim/Wels
3.As per EN 303-5, Section 5.1.3 type test: for a boiler from a range with a consistent structure it is sufficient, if the ratio of rated heat output from the largest to the smallest boiler ≤2 : 1,
to carry out the tests with the smallest and the largest boilers. The boiler manufacturer must ensure that all boilers, including those that have not been tested in the range, whose
values have been determined depending on the rated heat output by interpolation, fulfil the requirements of the norm
4.Values for the types TX 200 are interpolated between the types TX 150 and TX 250, test protocol 10-UW/Wels-EX-119 and 11-UW/Wels-EX-249!
Test data wood chips - Emissions in [mg/MJ] (RL / PL)
Carbon monoxide (CO)
mg/MJ
<4 / 35
5 / 33
7 / 30
Nitrous oxide (NOx)
mg/MJ
78 / 63
74 / 61
69 / 58
Organic hydrocarbons (OGC)
mg/MJ
<1 / <1
<1 / <2
<1 / <2
Dust
mg/MJ
23 / 15
20 / 17
17 / 19
Boiler efficiency
%
92,1 / 92,3
92,9 / 92,5
93,7 / 92,8
Test data wood chips - Emissions in [mg/m³]
1)
(RL / PL)
Carbon monoxide (CO)
mg/m³
<6 / 52
8 / 48
11 / 44
Nitrous oxide (NOx)
mg/m³
115 / 93
108 / 89
101 / 85
Organic hydrocarbons (OGC)
mg/m³
<1 / <2
<1 / <2
<1 / <2
Dust
mg/m³
34 / 22
29 / 25
25 / 28
Boiler efficiency
%
92,1 / 92,3
92,9 / 92,5
93,7 / 92,8
1.Emissions values based on dry flue gas at standard temperature and pressure (0°C, 1013 mbar) with a volume content of oxygen of 13%