5.3.2 Recurrent check and cleaning
The boiler must be inspected and cleaned at appropriate intervals depending on the
operating hours and fuel quality.
Depending on the activity, inspection and cleaning must be repeated after 1000
operting hours or at least every six months or no later than 2500 operating hours or at
least once a year. For less efficient fuels (e.g. high ash content) this work needs to be
carried out more frequently.
WARNING
Inspection and cleaning work with the boiler switched on
Serious injuries from automatic startup of the boiler and severe burns from hot
parts and the flue gas pipe are possible.
Therefore:
❒ Only carry out work on the boiler when the main switch is turned off
❒ Always wear protective gloves when working on the boiler
❒ Only operate the boiler using the handles provided
❒ Follow the procedure below when starting and finishing inspection and
cleaning work
Before starting inspection and cleaning work
❒ Switch off the boiler by tapping “Boiler off”
➥ Boiler shuts down and switches to "Boiler off” status
❒ Allow the boiler to cool for at least 1 hour
❒ On the control, go to the “Manual operation” menu
NOTICE! See operating instructions for boiler controller
❒ Use the DOWN arrow to navigate to the
“Tip drive”
parameter
❒ Set parameter to
“ON”
➥ Combustion grate tips
❒ Turn off the main switch
After inspection and cleaning work
❒ Turn on the main switch
➥ Combustion grate previously opened manually now closes automatically and
the boiler switches to “Boiler off” status
❒ Activate “service mode” in the quick menu
➥ The boiler starts the cleaning module and removes any remaining ash in the
combustion chamber
➥ Once self-cleaning is finished the boiler switches to "Boiler off" status.
Servicing the system
5
Maintenance work by the operator
Operating Instructions T4e | B1560520_en
55