4 | Technical information
28
M1980822_en | Installation instructions Wood chip boiler T4e 20-180
Description
T4e 80 – 110 ESP
80
90
100
108
110
Fuel efficiency at 30% of rated heat output (η
p
)
84.5
84.9
85.3
85.1
85.1
Auxiliary current consumption at rated heat output
(el
max
)
kW
0.158
0.176
0.194
0.196
0.196
Auxiliary current consumption at 30% of rated heat
output (η
p
)
0.085
0.093
0.101
0.100
0.100
Auxiliary current consumption in standby mode (P
SB
)
0.012
0.015
0.017
0.019
0.019
Regulation (EU) 2015/1189 – emissions in [mg/m³]
1)
Annual space heating emissions of dust (PM)
≤ 30
Annual space heating emissions of gaseous organic compounds
(GOC)
≤ 20
Annual space heating emissions of carbon monoxide (CO)
≤ 380
Annual space heating emissions of nitrogen oxides (NO
x
)
≤ 200
1. The emissions of dust, gaseous organic compounds, carbon monoxide and nitrogen oxides are stated in a standardised form based on dry flue gas with a oxygen content of 10 % and
under standard conditions at 0°C and 1013 millibar