3.4  Important control steps 

 

 Push-button 

Notes 

Start system 

Press green button (I) 
or open the insulating 
door 

 

 

The main switch must be switched on 

Shut down the system 

Burn-off must 

not 

be stopped. After burn-off 

the boiler automatically goes into shut down 
mode. 

CAUTION DANGER: 
Never stop the boiler using the main 
switch! 

1. Select 

menu 

 

ZURÜC

ZURÜCK

EINGABE

You will find an overview of the menu 
structure in chapter 5 Menu overview 

2. Select 

parameters 

 

 
 
 

3.  Press the “Enter” 

key 

 

EINGABE

A question mark appears next to the 
parameter value. The value can now be 
changed.  

4.  Change the value 

 

The “up-arrow” key increases the value. 

 

The “down-arrow” key decreases the 
value. 

Changing parameters 
and values 

5. Confirm 

with 

the 

“Enter” key  

 

EINGABE

Value is saved. 

If the “Back” key is pressed instead of the 
“Enter” key, the change is not applied.  

 

3.5  Changing the target boiler temperature 

Set boiler temp.
 80°

 

3x 

 

EINGABE

To switch from the display menu to the parameter display, press 
the 

ENTER

 key 

three times

 

Set boiler temp.
 80°? 

 

EINGABE

If you press the

 ENTER 

key once more, a question mark will 

appear beside the parameter value.  

Set boiler temp.
 75°? 

 

You can now change the target boiler temperature using the 
“arrow up” and “arrow down” keys.  

Set boiler temp.
 75°

 

 

EINGABE

Confirm the desired value by pressing 

ENTER

Heating 
Boiler temp. 73°

 

3x

 

ZURÜC

ZURÜCK

 

To return to the display menu, press the 

Back 

button three times.

 

BACK 

ENTER 

ENTER 

ENTER 

ENTER 

ENTER 

ENTER 

BACK 

Summary of Contents for Lambdatronic S 3100

Page 1: ...NG 4 PUMPE 1 PUMPE 2 PUMPE 3 GEBL SE EINGABE 0 A HEIZUNG 1 PUMPE HZG 0 L GEBL SE 2 3 4 1 2 3 2 3 4 5 6 7 8 9 1 1 Two line display 2 Menu buttons 3 Button Start Stop 4 Status LED 5 Operating display fo...

Page 2: ...e instructions and advice could cause damage to the appliance and personal injury Main switch RISK Never stop the boiler using the main switch Do not stop burn off The main switch may only be activate...

Page 3: ...ments The system is operated using a 4 button control unit with a clear menu structure All of the parameters necessary for operation are at the customer s disposal ZUR C ZUR CK EINGABE Feuer Aus Kesse...

Page 4: ...er value The value can now be changed 4 Change the value The up arrow key increases the value The down arrow key decreases the value Changing parameters and values 5 Confirm with the Enter key EINGABE...

Page 5: ...child lock or 1 for customer confirm by pressing Enter If you enter the wrong code the code for child lock will automatically be used User code The name of the set user level will appear briefly Off...

Page 6: ...prog 1 Enter Back Heating phase1 start Heating phase1 end Heating phase2 start Heating phase2 end Heating prog 2 Heating prog 14 same as heating prog 1 Heating circuit 1 Enter Back Heating curve Ente...

Page 7: ...en the set temperature is reached in the DHW the DHW loading pump switches off Set DHW temp 2 55 When the set temperature is reached in the DHW the DHW loading pump 2 switches off Reload if boiler und...

Page 8: ...ue during the drawdown phase is only visible with remote control Flow temperature reduction 15 The flow temp is reduced by this value in the drawdown phase Ex temp heating limit 18 If the outside temp...

Page 9: ...limination of the error has been acknowledged by pressing the ENTER key the status LED returns to green Chapter 7 2 Error message list contains a list of possible error messages 7 Troubleshooting What...

Page 10: ...per closed On actuator swap connection for left with right Check dampers can turn Check cable and connection Storage temp low RELOAD W Top storage tank temperature insufficient for heat supply Info on...

Page 11: ...heating times here Heating phase 1 Heating phase 2 Heating phase 1 Heating phase 2 Start End Start End Start End Start End Heating prog 1 Heating prog 8 Heating prog 2 Heating prog 9 Heating prog 3 He...

Page 12: ...g session 14 00 End of the second loading session 16 00 Heat only once day N Legionella heating65 Y Legionella heating day Sat Solar Set hot water temp 55 Heating circuit 1 Flow temp at outer 10 C 60...

Page 13: ...Lambdatronic S 3100 Control System SERVICE INSTRUCTIONS B 018 10 04 FR LING Heizkessel und Beh lterbau GmbH Page 24 of 24 A 4710 Grieskirchen Industriestra e 12 Tel 43 0 7248 606 0 Notes...

Page 14: ...bdatronic S 3100 SERVICE INSTRUCTIONS FR LING Heizkessel und Beh lterbau GmbH B 018 10 04 A 4710 Grieskirchen Industriestra e 12 Tel 43 0 7248 606 0 Page 23 of 24 10 List of parameter changes Paramete...

Page 15: ...ng circuit pump 0 or as an oil boiler contact depending on the system settings Connecting a HCP 0 up to 2 Ampere Connecting a HCP 0 up to 5 Ampere External feed Connection as an oil boiler contact NOT...

Page 16: ...not be longer than 20 m Console RBG 3100 also includes a room sensor which sends the current room temperature to the control Note RXD and TXD must be crossed over RXD on TXD TXD on RXD 9 10 PC Visuali...

Page 17: ...6 pin 9 7 Flue gas sensor 9 8 Remote control The remote control also contains a room sensor which sends the current room temperature to the control Switch settings Override circuit ignores the reduct...

Page 18: ...eating circuit pump 9 4 Jumper setting for actuators The jumpers on the motherboard 3100 must be adjusted to the type of actuator in the air dampers Actuator Jumpers on motherboard 3100 without feedba...

Page 19: ...RC 3 Remote control 3 RC 4 Remote control 4 FS 3 Flow sensor 3 FS 1 Flow sensor 1 ES 1 External sensor 1 FS 2 Flow sensor 2 RC 1 1 Remote control RC 2 Remote control 2 Mixer 3 Mixer 1 Mixer 4 Mixer 2...

Page 20: ...or 3 Sensor 2 Sensor 1 Sensor 4 Sensor 5 HCP 0 N PE1 PE2 A W H A A HCP oil Lambda board 3100 optional View of bottom level Control element 3100 Flat ribbon cable to expansion board 1 Flat ribbon cable...

Page 21: ...onnection for left with right Check dampers can turn Check cable and connection Storage temp low RELOAD W Upper storage tank temperature insufficient for heat supply Info only no error automatic ackno...

Page 22: ...will need to set the secondary air by way of an emission measurement using the Sec air MAX parameter in the air settings If you have a Lambda control it is recommended you carry out an emissions measu...

Page 23: ...hecking the door sensor switch Door sensor A 0 door closed switch activated A 1 door open switch not activated If the insulating door is open the ID fan will start up 6 7 Checking the tightness and sy...

Page 24: ...Press the Enter button A question mark will appear Now enter the code for the Installer or Service user level Confirm by pressing Enter If you enter the wrong code the code for child lock will automat...

Page 25: ...Please note that heating circuits 1 and 3 can be used for solar element 5 8 2 System parameters The actual number of parameters of those listed below depends on the system settings Bypass pump av Yes...

Page 26: ...bda probe is available FHG Turbo 30 FHG Turbo 40 Comb chamb sensor av N Y if a combustion chamber sensor is available FHG Turbo 50 FHG Turbo 70 Actuator with feedback N Y Actuators with feedback have...

Page 27: ...PEN A 0 Primary air damper OPEN Prim fl CLOSED A 0 Primary air damper CLOSED Sec fl OPEN A 0 Secondary air damper OPEN Sec fl CLOSED A 0 Secondary air damper CLOSED A 0 Automatic OFF A AUTOMATIC A 1 A...

Page 28: ...pressing the ENTER key Short red flashes Warning or error persists not acknowledged Long red flashes Warning or error persists but acknowledged Warning The status LED automatically changes to green as...

Page 29: ...e flue gas temperature Top load point to ensure adequate efficiency if this temperature is exceeded the output will be reduced Flue gas temp start add 20 Flue gas target value increase when heating up...

Page 30: ...each like heating prog 1 You can program up to 14 heating times each with two heating phases These are assigned to the individual days of the week in the parameter Heating circuit 1 4 weekly program...

Page 31: ...switched off Oil boiler Oil boiler storage temp diff 10 The minimum temperature difference between the oil boiler and storage tank which releases the oil boiler loading pump output Oil boiler start d...

Page 32: ...rage temp diff 10 Temperature difference for launching storage tank loading process Residual heat use N This function can only be used in conjunction with a bypass pump return feed mixer The residual...

Page 33: ...iler temperature is exceeded by a set value the status of the boiler will be maintained glow Once the temperature goes back down below the target boiler value the boiler s status will return to heatin...

Page 34: ...100 Mixer Ty 240s ID fan 36 Solar Primary air 76 ERROR DISPLAY Heating times Prim damp pos 77 Heating circuit 1 O2 content 7 9 Heating circuit 2 O2 controller 78 Heating circuit 3 Sec air 77 Sec damp...

Page 35: ...ontrol 17 9 Connection instructions 19 9 2 Mains connection 19 9 3 Heating circuit pumps for underfloor or wall heating 19 9 4 Jumper setting for actuators 19 9 5 Jumper setting for solar control 19 9...

Page 36: ...UMPE 2 PUMPE 3 GEBL SE EINGABE 0 A HEIZUNG 1 PUMPE HZG 0 L GEBL SE 2 3 4 1 2 3 1 Two line display 2 Menu buttons 3 Button Start Stop 4 Status LED 5 Operating display for pumps 6 Fan 7 Switch heater 0...

Reviews: