background image

WARNING

FIRE HAZARD

See the dryer use and care manual for the maximum allowable duct 

length. Exceeding the length of duct pipe or number of elbows 

allowed in the 

MAXIMUM LENGTH

 chart can cause an accumulation 

of lint in the exhaust system. Plugging the system could create a fire 

hazard, as well as increase drying times.

WARNING

FIRE HAZARD

•  DO NOT

 install flexible plastic or flexible foil venting material.

•  DO NOT

 exceed 8 ft. (2.4 m) of semi-rigid venting.

•  DO NOT

 use screws, rivets or other fasteners that extend into 

the duct to assemble the exhaust system.

Exhaust direction

Directional exhausting can be accomplished by installing a quick-

turn 90° dryer vent elbow directly to exhaust outlet of dryer. Dryer 

vent elbows are available through your local parts distributor or 

hardware store.

See also CLEARANCE

REQUIREMENTS.

NOTE

You are required to use a 90° quick-turn elbow 

 

to meet the minimum installation depth.

WARNING

FIRE HAZARD

DO NOT

 install the dryer where gasoline or other flammables are 

kept or stored. If the dryer is installed in a garage, it must be a 

minimum of 18 inches (45.7 cm) above the floor. Failure to do so 

can result in death, explosion, fire or burns.

In installations where the exhaust system is not described in the 

charts, the following method must be used to determine if the 

exhaust system is acceptable:

Correct

Incorrect

Install male fittings in correct direction:

1. 

Connect an inclined or digital manometer between the dryer 

and the point the exhaust connects to the dryer.

2.  Set the dryer timer and temperature to 

air fluff 

(cool down) 

and start the dryer.

3.  Read the measurement on the manometer. 
4.  The system back pressure MUST NOT be higher than 1.0 inch of 

water column. If the system back pressure is less than 1.0 inch 

of water column, the system is acceptable. If the manometer 

reading is higher than 1.0 inch of water column, the system is 

too restrictive and the installation is unacceptable.

Although vertical orientation of the exhaust system is acceptable, 

certain extenuating circumstances could affect the performance 

of the dryer:

• 

Only the rigid metal duct work should be used.

•  Venting vertically through a roof may expose the exhaust 

system to down drafts causing an increase in vent restriction.

•  Running the exhaust system through an uninsulated area may 

cause condensation and faster accumulation of lint. 

•  Compression or crimping of the exhaust system will cause an 

increase in vent restriction.

• 

The exhaust system should be inspected and cleaned a 

minimum of every 18 months with normal usage.

 The more 

the dryer is used, the more often you should check the 

exhaust system and vent hood for proper operation and that it 

is free of obstructions.

NOTE

See the dryer 

use and care

 manual for proper back pressure 

value for the dryer your installing.  See the manufacturer’s 

recommendations when conducting this method.

WARNING

Refer to your use and care manual for proper cleaning intervals 

of the exhaust system and dryer cabinet interior.

Summary of Contents for Smart Choice 5304492448

Page 1: ...ted outdoors DO NOT exhaust dryer into a chimney a wall a ceiling an attic a crawl space or any concealed space of a building A clothes dryer produces combustible lint If the dryer is not exhausted outdoors some fine lint will be expelled into the laundry area An accumulation of lint in any area of the home can create a health and fire hazard The dryer must be connected to an exhaust outdoors Regu...

Page 2: ...clined or digital manometer between the dryer and the point the exhaust connects to the dryer 2 Set the dryer timer and temperature to air fluff cool down and start the dryer 3 Read the measurement on the manometer 4 The system back pressure MUST NOT be higher than 1 0 inch of water column If the system back pressure is less than 1 0 inch of water column the system is acceptable If the manometer r...

Page 3: ...una pared un techo un ático un entretecho o cualquier espacio oculto de un edificio Una secadora de ropa produce pelusas combustibles Si la secadora no se ventila al aire libre algunas pelusas finas se expulsarán al área de lavandería Una acumulación de pelusas en cualquier área de la casa puede crear un peligro de incendio y para la salud La secadora debe estar conectada a un escape al exterior I...

Page 4: ...rios macho en la dirección correcta 1 Conecte un manómetro inclinado o digital entre la secadora y el punto en que el escape se conecta a la secadora 2 Configure el temporizador y la temperatura de la secadora a air fluff enfriar y encienda la secadora 3 Lea la medición en el manómetro 4 La contrapresión del sistema NO DEBE ser superior a 1 0 pulgada de columna de agua Si la contrapresión del sist...

Page 5: ...esanitaireoutoutespacedissimulé d unbâtiment Unesécheuseproduitdespeluchescombustibles Sil évacuation delasécheusenepeutsefaireàl extérieur despeluchesfines serontexpulséesdanslasalledelavage Uneaccumulationde peluchesdansn importequelespacedelamaisonpeutcréerun risquedesantéetd incendie Lasécheusedoitêtreraccordéeàuntuyaud évacuationextérieur Inspectezrégulièrementl ouvertured évacuationextérieur...

Page 6: ...1 Connecter un manomètre incliné ou numérique entre la sécheuse et le point où le conduit d évacuation est connecté à la sécheuse 2 Régler la minuterie et la température de la sécheuse sur air fluff peluches d air et mettre la sécheuse en marche 3 Lire la mesure sur le manomètre 4 La contre pression du système NE DOIT PAS être supérieure à 1 po 2 54 cm de colonne d eau Si la contre pression est in...

Reviews: