Settlement of outdoor unit
Anchor the outdoor unit with
a bolt and nut 10 or 8 tightly
and horizontally on a concrete
or rigid mount.
Drain joint installation
Fit the seal into the drain elbow, then
insert the drain joint into the base pan
hole of outdoor unit, rotate 90 to
securely assemble them.
Connecting the drain joint with an
extension drain hose (Locally
purchased), in case of the water
draining off the outdoor unit during the
heating mode.
Flaring work
Main cause for refrigerant leakage is
due to defect in the flaring work.
Carry out correct flaring work using
the following procedure:
1. Cut the pipes and the cable.
A) Use the piping kit accessory or
pipes purchased locally.
B) Measure the distance between the
indoor and the outdoor unit.
C) Cut the pipes a little longer than
the measured distance.
D) Cut the cable 1.5m longer than the
pipe length.
2. Burr removal
A) Completely remove all burrs from
the cut cross section of pipe/tube.
B) Put the end of the copper
tube/pipe in a downward direction as
you remove burrs in order to avoid
dropping burrs into the tubing.
3. Putting nut on
A) Remove flare nuts attached to
indoor and outdoor unit, then put
them on pipe/tube having completed
burr removal.(not possible to put them
on after flaring work)
Refrigerant pipe connection
Air inlet
Air
inlet
Air outlet
A
B
Base pan hole
of outdoor unit
Seal
Drain joint
Seal
Drain pipe
+
=
Pipe
Correct
Wrong
Oblique Roughness Burr
Pipe
Reamer
Point
down
Flare nut
Cooper tube
Outdoor unit dimension
mm - (WxHxD)
Mounting dimensions
A(mm)
B(mm)
700x540x240
685x430x260
780x540x250
760x590x285
775x545x310
845x700x320
670x540x250
760x590x285
820x590x330
845x700x320
458
460
459
530
560
600
481
530
523
560
250
276
276
290
335
320
276
290
340
335
24k Btu models