The 2
nd
Generation DC Series VRF Indoor Units
Ka
ysun
2
nd
Gener
ation DC Series Duct VRF Indoor Un
its Engineering Da
ta Book
201805 3
KPDHF-112 DN4.0 / KPDHF-140 DN4.0 / KPDHF-160 DN4.0
Table 1.2: KPDHF-112(140,160)DN4.0 specifications
Model name
KPDHF-112 DN4.0
KPDHF-140 DN4.0
KPDHF-160 DN4.0
Power supply
1-phase, 220-240V, 50Hz
Cooling
1
Capacity
kW
11.2
14
16
kBut/h
38.2
47.8
54.6
Input
W
380
420
700
Heating
2
Capacity
kW
12.5
16
17
kBut/h
42.7
54.6
58
Input
W
380
420
700
Fan motor
Model
WZDK750-38G-W
WZDK750-38GS-W
WZDK750-38GS-W
Type
DC
Brand
Pansonic/ Welling
Speed (H/M/L)
r/min
1113/1066/1012/971/
925/876/840
1019/981/941/902/
855/808/765
1080/1046/996/954/
910/869/825
Coil
Number of rows
925/876/840
1019/981/941/902/
4
Tube pitch × row pitch
mm
855/808/765
1080/1046/996/954/
25.4×22
Fin spacing
mm
910/869/825
1.6
1.6
Fin type
Hydrophilic aluminum
Tube OD and type
mm
Ф9.53 Inner groove
Dimensions (L×H ×W)
mm
700×356×66
996×356×88
996×356×88
Number of circuits
7
7
7
Airflow rate
3
m
3
/h
1870/1783/1697/1610/
1523/1437/1350
2240/2133/2027/1920/
1813/1707/1600
2660/2530/2400/2270/
2140/2010/1880
External static pressure
4
Pa
100 (30~ 200)
Sound pressure level
5
dB(A)
48/47/46/45/43/42/41
45/44/43/42/41/40/40
46/45/44/43/42/41/40
Sound power level
dB(A)
66/65/64/63/61/60/59
63/62/61/60/59/58/58
64/63/62/61/60/59/58
Unit
Net dimensions
6
(W×H×D)
mm
952×420×690
1300×420×690
1300×420×690
Packed dimensions
(W×H×D)
mm
1090×440×768
1436×450×768
1436×450×768
Net/Gross weight
kg
51/57
63/70
63/70
Refrigerant type
R410A
Throttle
Type
Electronic expansion valve
Model
BD20FKS(L)
Design pressure (H/L)
MPa
4.4/2.6
Pipe
connections
Liquid/Gas pipe
mm
Ф9.53/Ф19.1
Drain pipe
mm
OD Ф25
Notes:
1. Indoor temperature 27°C DB, 19°C WB; outdoor temperature 35°C DB; equivalent refrigerant piping length 7.5m with zero level difference.
2. Indoor temperature 20°C DB; outdoor temperature 7°C DB, 6°C WB; equivalent refrigerant piping length 7.5m with zero level difference.
3. Fan motor speed and air flow rate are from the highest speed to the lowest speed, total 7 rates for each model.
4. Stable operation external static pressure range. (Note: setting external static pressure outside the unit’s optimal static pressure range may lead to higher
noise levels and lower airflow rate. For the optimal external static pressure range refer to the unit’s installation manual.)
5. Sound pressure level is from highest level to lowest level, total 7 levels for each model. Sound pressure level is measured 1.4m below the unit in a semi-
anechoic chamber.
6. Unit body dimensions given are the largest external dimensions of the unit, including hanger attachments.