Table 7.2: High Static Pressure Duct heating capacity (continued)
Capacity
(kW)
Outdoor air
temperature (°C
)
Indoor air temperature (°C DB)
16
18
20
21
22
24
TC
TC
TC
TC
TC
TC
WB
DB
kW
kW
kW
kW
kW
kW
28.0
-20
-19.8
17.64
17.64
17.64
17.64
17.64
17.64
-19
-18.8
18.90
18.90
18.90
18.90
18.90
18.90
-17
-16.7
19.85
19.85
19.85
19.85
19.85
19.85
-15
-14.7
20.48
20.48
20.48
20.48
20.48
20.48
-13.00
-12.60
21.74
21.74
21.74
21.74
21.74
21.74
-11.00
-10.50
22.05
22.37
22.37
22.37
22.37
22.37
-10.00
-9.50
23.00
23.00
23.00
23.00
23.00
23.00
-9.10
-8.50
23.63
23.63
23.63
23.63
23.63
23.63
-7.60
-7.00
23.94
23.94
23.94
23.94
23.94
23.94
-5.60
-5.00
24.89
24.89
24.89
24.89
24.89
24.89
-3.70
-3.00
26.15
26.15
26.15
26.15
26.15
26.15
-0.70
0.00
28.04
28.04
28.04
28.04
28.04
26.46
2.20
3.00
29.61
29.61
29.61
29.61
28.98
26.46
4.10
5.00
30.56
30.56
30.56
30.56
28.98
26.46
6.00
7.00
31.50
31.50
31.50
30.56
28.98
26.46
7.90
9.00
32.45
32.45
31.50
30.56
28.98
26.46
9.80
11.00
33.39
33.39
31.50
30.56
28.98
26.46
11.80
13.00
34.65
34.02
31.50
30.56
28.98
26.46
13.70
15.00
35.60
34.02
31.50
30.56
28.98
26.46
40.0
-20
-19.8
25.20
25.20
25.20
25.20
25.20
25.20
-19
-18.8
27.00
27.00
27.00
27.00
27.00
27.00
-17
-16.7
28.35
28.35
28.35
28.35
28.35
28.35
-15
-14.7
29.25
29.25
29.25
29.25
29.25
29.25
-13.00
-12.60
31.05
31.05
31.05
31.05
31.05
31.05
-11.00
-10.50
31.50
31.95
31.95
31.95
31.95
31.95
-10.00
-9.50
32.85
32.85
32.85
32.85
32.85
32.85
-9.10
-8.50
33.75
33.75
33.75
33.75
33.75
33.75
-7.60
-7.00
34.20
34.20
34.20
34.20
34.20
34.20
-5.60
-5.00
35.55
35.55
35.55
35.55
35.55
35.55
-3.70
-3.00
37.35
37.35
37.35
37.35
37.35
37.35
-0.70
0.00
40.05
40.05
40.05
40.05
40.05
37.80
2.20
3.00
42.30
42.30
42.30
42.30
41.40
37.80
4.10
5.00
43.65
43.65
43.65
43.65
41.40
37.80
6.00
7.00
45.00
45.00
45.00
43.65
41.40
37.80
7.90
9.00
46.35
46.35
45.00
43.65
41.40
37.80
9.80
11.00
47.70
47.70
45.00
43.65
41.40
37.80
11.80
13.00
49.50
48.60
45.00
43.65
41.40
37.80
13.70
15.00
50.85
48.60
45.00
43.65
41.40
37.80
Abbreviations:
TC: Total capacity
Notes: