7 Capacity Tables
7.1 Cooling Capacity Table
Table 7.1: High Static Pressure Duct cooling capacity
Capacity
(kW)
Outdoor air
temperature
(°C DB)
Indoor air temperature (°C WB/DB)
14/20
16/23
18/26
19/27
20/28
22/30
24/32
TC
SC
TC
SC
TC
SC
TC
SC
TC
SC
TC
SC
TC
SC
kW
kW
kW
kW
kW
kW
kW
kW
kW
kW
kW
kW
kW
kW
7.1
10.0
4.9
4.3
5.8
4.7
6.7
5.3
7.1
5.4
7.5
5.4
8.4
5.6
9.2
5.6
12.0
4.9
4.3
5.8
4.7
6.7
5.3
7.1
5.4
7.5
5.4
8.4
5.6
9.1
5.5
14.0
4.9
4.3
5.8
4.7
6.7
5.3
7.1
5.4
7.5
5.4
8.4
5.6
9.0
5.5
16.0
4.9
4.3
5.8
4.7
6.7
5.3
7.1
5.4
7.5
5.4
8.4
5.6
8.9
5.4
18.0
4.9
4.3
5.8
4.7
6.7
5.3
7.1
5.4
7.5
5.4
8.4
5.6
8.7
5.2
20.0
4.9
4.3
5.8
4.7
6.7
5.3
7.1
5.4
7.5
5.4
8.4
5.6
8.5
5.2
21.0
4.9
4.3
5.8
4.7
6.7
5.3
7.1
5.4
7.5
5.4
8.4
5.6
8.4
5.1
23.0
4.9
4.3
5.8
4.7
6.7
5.3
7.1
5.4
7.5
5.4
8.3
5.6
8.3
5.0
25.0
4.9
4.3
5.8
4.7
6.7
5.3
7.1
5.4
7.5
5.4
8.2
5.5
8.2
5.0
27.0
4.9
4.3
5.8
4.7
6.7
5.3
7.1
5.4
7.5
5.4
8.2
5.5
8.2
5.0
29.0
4.9
4.3
5.8
4.7
6.7
5.3
7.1
5.4
7.5
5.4
8.1
5.4
8.1
5.0
31.0
4.9
4.3
5.8
4.7
6.7
5.3
7.1
5.4
7.5
5.4
8.0
5.4
7.8
4.8
33.0
4.9
4.3
5.8
4.7
6.7
5.3
7.1
5.4
7.5
5.4
8.0
5.3
7.8
4.8
35.0
4.9
4.3
5.8
4.7
6.7
5.3
7.1
5.4
7.5
5.3
7.7
5.1
7.7
4.8
37.0
4.9
4.3
5.8
4.7
6.7
5.3
7.1
5.4
7.4
5.3
7.7
5.1
7.6
4.8
39.0
4.9
4.3
5.8
4.7
6.7
5.3
7.1
5.4
7.2
5.2
7.4
5.0
7.6
4.8
42.0
4.9
4.3
5.8
4.7
6.7
5.3
7.1
5.4
7.2
5.2
7.4
5.0
7.6
4.8
44.0
4.9
4.3
5.8
4.7
6.7
5.3
7.1
5.4
7.2
5.2
7.4
5.0
7.6
4.8
46.0
4.9
4.3
5.8
4.7
6.7
5.3
7.1
5.4
7.2
5.2
7.4
5.0
7.6
4.8
Abbreviations:
TC: Total capacity
SC: Sensible capacity
Notes:
1. Shaded cells indicate rating condition.