27
Par
t 3 - I
nstalla
tion and F
ield S
ettings
1.3 Parameters setting
Menu
Parameters
Setting range
Default value
Adjustment range
Project menu
TWO_COOL_DIFF
1°C~5°C
2°C
1°C
TWO_HEAT_DIFF
1°C~5°C
2°C
1°C
TIM_CAP_ADJ
60~360s
80s
20s
TW_COOL_DIFF
1°C~5°C
2°C
1°C
TW_HEAT_DIFF
1°C~5°C
2°C
1°C
RATIO_COOL_FIRST
0~100%
50%
5%
RATIO_HEAT_FIRST
0~100%
50%
5%
T_DIFF_PRO
8~15°C
12°C
1°C
TWI_O_ABNORMAL
1~5°C
2°C
1°C
T_FROST
20~120 min
35 min
5min
T_DEFROST_IN
-5~5°C
0°C
1°C
T_FROST_OUT
-10~+10°C
0°C
1°C
E9 PROTECT TIME
2~20s
5s
1
E9 DETECTION METHOD
1~2
1
1
MIN RATIO
40~100%
75%
5%
MAX RATIO
70~100%
100%
5%