16
4.2 Cooling Capacity Tables
DB
LWT
5
7
10
13
15
20
CC
PI
EER
CC
PI
EER
CC
PI
EER
CC
PI
EER
CC
PI
EER
CC
PI
EER
-15
-
-
-
-
-
-
75.1 13.3 5.6 80.3 13.6 5.9 83.8 13.8 6.1 92.5 14.2 6.5
-10
-
-
-
-
-
-
75.8 18.6 4.1 80.8 17.2 4.7 84.0 16.4 5.1 92.3 14.2 6.5
-5
-
-
-
-
-
-
75.9 16.0 4.8 80.8 16.1 5.0 84.1 16.2 5.2 92.3 16.4 5.6
0
-
-
-
-
-
-
76.6 15.2 5.0 81.0 16.2 5.0 84.0 16.9 5.0 91.3 18.6 4.9
5
-
-
-
-
-
-
75.8 17.4 4.4 81.3 14.4 5.6 84.1 14.8 5.7 91.1 14.6 6.2
9
-
-
-
-
-
-
79.1 16.6 4.8 82.5 14.2 5.8 86.4 14.8 5.9 93.0 14.8 6.3
11
93.4 27.3 3.4 98.7 31.4 3.1 105.2 28.0 3.8 114.4 29.7 3.8 122.7 26.1 4.7 128.2 26.8 4.8
15
93.1 27.3 3.4 98.8 27.4 3.6 111.7 29.5 3.8 120.5 27.4 4.4 127.2 28.1 4.5 133.9 28.7 4.7
20
91.8 28.7 3.2 97.8 31.1 3.1 107.6 31.5 3.4 113.5 31.8 3.6 117.3 29.3 4.0 127.1 29.4 4.3
25
90.3 27.8 3.2 96.2 22.5 4.3 102.9 27.5 3.7 109.0 25.9 4.2 111.7 25.6 4.4 121.3 23.5 5.2
30
87.4 29.5 3.0 92.1 30.0 3.1 99.9 30.3 3.3 106.1 29.8 3.6 108.3 25.2 4.3 117.3 24.7 4.7
35
80.9 32.2 2.5 84.8 28.3 3.0 93.7 33.0 2.8 100.8 32.0 3.2 104.2 28.4 3.7 112.4 27.5 4.1
40
69.9 30.2 2.3 73.8 26.9 2.7 81.6 27.7 3.0 87.1 27.5 3.2 92.6 28.0 3.3 102.3 27.9 3.7
43
60.9 28.2 2.2 65.8 25.1 2.6 72.2 24.2 3.0 77.7 23.8 3.3 81.8 24.0 3.4 92.1 25.3 3.6
45
48.5 24.2 2.0 57.8 22.7 2.6 62.9 22.4 2.8 67.5 23.0 2.9 72.8 23.4 3.1 80.7 22.2 3.6
48
29.3 16.5 1.8 39.3 18.7 2.1 45.1 19.2 2.4 51.0 17.6 2.9 55.0 17.8 3.1 60.9 19.3 3.1
50
15.2 12.1 1.3 17.2 12.3 1.4 19.6 12.4 1.6 23.6 12.3 1.9 26.0 12.5 2.1 33.0 12.2 2.7
Abbreviations:
LWT: Leaving water temperature (°C )
DB: Dry-bulb temperature for outdoor air temperature (°C )
CC: Total cooling capacity (kW)
PI: Power input (kW)
Notes:
Performance specifications measured with water pump operating at rated water flow rate.