t 2 - Engineering Da
ta
4 Capacity Tables
4.1 Heating Capacity Tables
DB
LWT
30
35
40
45
50
54
TC
PI
COP
TC
PI
COP
TC
PI
COP
TC
PI
COP
TC
PI
COP
TC
PI
COP
-20
43.9 21.7
2.0
42.7 24.8
1.7
39.7 26.6
1.5
-
-
-
-
-
-
-
-
-15
55.8 23.4
2.4
53.6 25.9
2.1
51.0 27.6
1.8
45.8 26.9
1.7
-
-
-
-
-
-
-7
72.4 24.2
3.0
70.2 26.2
2.7
68.0 28.6
2.4
64.1 30.6
2.1
48.0 28.0
1.7
-
-
-
2
88.3 26.6
3.3
86.3 26.4
3.3
84.9 28.8
2.9
81.5 31.3
2.6
70.0 32.1
2.2
59.9 33.3
1.8
7
98.3 22.7
4.3
95.4 24.1
4.0
92.7 27.0
3.4
90.5 28.1
3.2
83.3 34.4
2.4
71.0 34.0
2.1
15 102.9 23.7
4.3 100.4 24.9
4.0
99.1 25.8
3.8
97.7 28.2
3.5
84.7 27.2
3.1
73.9 27.0
2.7
20 103.0 22.3
4.6 100.3 23.5
4.3
99.6 24.9
4.0
98.0 25.0
3.9
79.1 22.2
3.6
70.2 21.2
3.3
25 101.9 20.5
5.0 100.2 19.7
5.1
99.3 20.3
4.9
96.8 22.0
4.4
69.6 20.7
3.4
58.9 15.7
3.8
30
99.2 18.1
5.6
96.0 18.3
5.2
94.6 18.7
5.1
84.9 18.8
4.5
63.0 17.1
3.7
47.0 14.4
3.3
35
92.8 15.4
6.0
89.0 16.7
5.3
85.0 16.0
5.3
76.8 16.2
4.7
-
-
-
-
-
-
40
88.9 14.0
6.3
80.0 13.3
6.0
71.4 11.4
6.3
66.0 12.4
5.3
-
-
-
-
-
-
43
88.0 13.8
6.4
78.6 12.4
6.4
70.1 10.7
6.5
64.3 12.2
5.3
-
-
-
-
-
-
Abbreviations:
LWT: Leaving water temperature (°C )
DB: Dry-bulb temperature for outdoor air temperature (°C )
HC: Total heating capacity (kW)
PI: Power input (kW)
Notes:
Performance specifications measured with water pump operating at rated water flow rate.