HEATING ELEMENT - See Figure 12
All heat pumps and electric heat models are equipped
with a heating element with the exception of the
YS09J10. The "YS", "ES" and "EK12" models are
equipped with a 3.3 KW element. The "YM", "EM" and
"EK18" models are equipped with a 4.0 KW element.
The "YL" and "EL" models are equipped with a 5.2 KW
element.
The heating element contains a fuse link and a heater
limit switch. The fuse link is in series with the power
supply and will open and interrupt the power when the
temperature reaches 161.6°F, or a short circuit occurs
in the heating element. Once the fuse link separates, a
new fuse link must be installed. NOTE: Always re-
place with the exact replacement.
The heater element has a high limit control. This con-
trol is a bimetal thermostat mounted in the top of the
heating element.
Figure 12: HEATING ELEMENT
Should the fan motor fail or filter become clogged, the
high limit control will open and interrupt power to the
heater before reaching an unsafe temperature condi-
tion.
The control is designed to open at 110°F ±6°F. Test
continuity below 110°F and for open above 110°F.
The heating element for the "Y" model is energized by
an outdoor thermostat. The outdoor thermostat is ad-
justed at a predetermined temperature to bring on the
heating element and turn off the compressor. The room
thermostat will then control the cycling of the element
when the selected indoor temperature is reached.
Testing of the elements can be made with an ohmme-
ter across the terminals after the connecting wires have
been removed. A cold resistance reading of approxi-
mately 14.5 ohms for the 3.3 KW heater, 11.9 ohms for
the 4.0 KW heater and 9.15 ohms for the 5.2 KW heater
should be registered.
DEFROST THERMOSTAT
(Heat Pump Models Only)
This thermostat (Figure 13) is single pole - double throw
with contacts between terminals "2" and "3" closing on
temperature rise and contacts between terminals "2"
and "1" closing on temperature fall. When the contacts
between terminals "2" and "1" make, power is supplied
to the heater element.
This control is dual purpose control that acts as an out-
door thermostat and defrost control.
When the sensing bulb, attached to the condenser coil,
senses enough icing on the outdoor coil, it will interrupt
power to the compressor and supply power to the heat-
ing element until the coil temperature reaches above
43°, then the heater will shut off and the unit will re-
sume operating in the reverse cycle mode.
When the outdoor coil temperature drops below 20°,
the unit will operate in electric heat mode continuously
until the outdoor coil temperature rises above 43°.
The fan motor will not turn off when defrost occurs, and
the 4-way valve will not reverse.
Figure 13: DEFROST THERMOSTAT
(Heat Pump Models)
Summary of Contents for YL24J35
Page 7: ...TTJ 0197 1 97 Page 7 of 64 COOLING LOAD ESTIMATE FORM...
Page 9: ...TTJ 0197 1 97 Page 9 of 64...
Page 14: ...Page 14 of 64 TTJ 0197 1 97...
Page 26: ...Page 26 of 64 TTJ 0197 1 97...
Page 27: ...TTJ 0197 1 97 Page 27 of 64...
Page 28: ...Page 28 of 64 TTJ 0197 1 97...
Page 29: ...TTJ 0197 1 97 Page 29 of 64...
Page 30: ...Page 30 of 64 TTJ 0197 1 97...
Page 31: ...TTJ 0197 1 97 Page 31 of 64...
Page 32: ...Page 32 of 64 TTJ 0197 1 97...
Page 33: ...TTJ 0197 1 97 Page 33 of 64...
Page 34: ...Page 34 of 64 TTJ 0197 1 97...
Page 35: ...TTJ 0197 1 97 Page 35 of 64...
Page 36: ...Page 36 of 64 TTJ 0197 1 97...
Page 37: ...TTJ 0197 1 97 Page 37 of 64 WIRING DIAGRAM FOR MODELS YS13J33 YM18J34A YL24J35...
Page 39: ...TTJ 0197 1 97 Page 39 of 64...
Page 40: ...Page 40 of 64 TTJ 0197 1 97...
Page 46: ...Page 46 of 64 TTJ 0197 1 97...
Page 47: ...TTJ 0197 1 97 Page 47 of 64...
Page 52: ...Page 52 of 64 TTJ 0197 1 97...
Page 53: ...TTJ 0197 1 97 Page 53 of 64...
Page 57: ...TTJ 0197 1 97 Page 57 of 64...
Page 58: ...Page 58 of 64 TTJ 0197 1 97...