2010 PERFORMANCE DATA 

*

Sleeve / Chassis Dimensions

27" Sleeve

Height (inches)

16 3/4

16 3/4

16 3/4

Width (inches)

27

27

27

Depth (inches)

16 3/4

16 3/4

Friedrich WSC 

Sleeve

Fedders A 

Sleeve

Fedders B Sleeve*

Sleeve Dimensions

Width

Max. Depth

WSD Sleeve

16 3/4

27

16 3/4

23

7 1/2

9/16

17 1/4

27 1/4

15  5/16

Chassis

15 3/4

26 1/2

21

22

-

-

-

-

-

Depth

with

Front

Minimum

Extension

Into Room

Minimum

Extension

Outside

Height

TTW Finished Hole

Height

Width

Depth

Model

WALLMASTER

Specifications

WallMaster Heat Pump heating information 

(

shown in

 

red)

 indicates heat pump heating performance. WallMaster Electric Heat heating information 

(shown in red)

 

indicates electric heat strip performance. For WallMaster Heat Pump electric heating performance refer to corresponding WallMaster Electric Heat model.

Estar

Model

 Cooling 

Capacity Btu

 Heating 

Capacity Btu

Volts 

Rated

 

Cooling 

Amps

Cooling Watts

Heating 

Amps

Heating 

Watts

Energy 

Efficiecy Ratio

EER

Moisture 
Removal
Pints/HR

Room 

Side Air 

Circulation 

CFM

Sleeve

Net Weight 

Lbs

WALLMASTER

Cool only

WS08C10

*

7800

NA

115

7.1

788

NA

NA

9.9

1.2

250

WSD

93

WS10C10

*

9700

NA

115

10.0

1032

NA

NA

9.4

2.4

257

WSD

103

WS12C10

*

11900

NA

115

11.8

1266

NA

NA

9.4

3.3

295

WSD

112

WS10C30

*

9500/9200

NA

230/208

4.5/4.7

989/958

NA

NA

9.6/9.6

1.5

300

WSD

101

WS13C30

*

12600/12300

NA

230/208

6.3/6.7

1340/1309

NA

NA

9.4/9.4

3.6

290

WSD

109

WS15C30

*

14500/14500

NA

230/208

8.3/8.2

1706/1706

NA

NA

8.5/8.5

4.2

290

WSD

119

Heat Pumps

WY09C33

*

9300/9000

7300/7300

230/208

4.4/4.7

989/957

3.8/4.0

839/793

9.4/9.4

2.1

250

WSD

103

WY12C33

*

12000/11800

9350/9200

230/208

6.1/6.4

1395/1372

4.8/5.1

1062/1010

8.6/8.6

2.6

275

WSD

111

Cool with Electric Heat

WE10C33

*

9500/9200

11000/9100

230/208

4.5/4.7

989/958

16.0/14.7

3550/2950

9.6/9.6

1.5

300

WSD

121

WE13C33

*

12600/12300

11000/9100

230/208

6.3/6.7

1340/1309

16.0/14.7

3550/2950

9.4/9.4

3.6

290

WSD

107

WE15C33

*

14500/14500

11000/9100

230/208

8.3/8.8

1706/1706

16.0/14.7

3550/2950

8.5/8.5

4.2

290

WSD

116

DEFROST CONTROL:  Initiated at 30°F (outdoor coil temperature for two 
consecutive minutes) and terminated at  43°F  (outdoor  coil  temperature).  During 
defrost,  the  compressor  stops  and the electric heat starts,  then operates with 
the fan to maintain indoor comfort. The unit remains in electric heat mode.

DEFROST DRAIN:  Drain automatically opens at approximately 50°F to prevent 
condensate from freezing inside drain pan.

Note: all models will produce condensate. If condensate disposal is desired, an 
optional drain kit is available.

As an 

 partner, Friedrich Air Conditioning Co. has determined that the selected 

(

 

 ) meet the 

 guidelines for ener

gy efficienc

y.

All models use

environmentally 

friendly R-410A 

refrigerant.

R-410A

WS08C10

*

 

57

23

55

60

129

167

65

98

11

31

154

462

7.1

32.0

32.5

257

1085

15

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

WS10C10

*

53

27

53

53

134

177

63

98

10

36

145

500

10.0

40.0

37.0

260

1080

15

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

WS12C10

*

54

26

52

55

128

169

60

106

11

28

145

500

11.8

57.0

45.0

300

1380

15

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

WS10C30

*

55

25

55

60

123

165

66

100

14

28

155

440

4.5

18.5

39.0

300

1400

15

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

WS13C30

*

51

29

51

51

134

179

59

100

8

40

138

535

6.3

26.0

40.0

280

1300

15

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

WS15C30

*

45

35

45

46

135

181

54

101

9

40

130

545

8.3

41.0

49.0

250

1345

15

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 WY09C33

*

54

26

54

54

123

164

65

101

12

22

150

450

4.4

3.8

20.0

40.5

251

1335

20

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

WY12C33

*

51

29

51

51

127

147

58

101

12

26

145

475

6.1

4.8

 

33.0

265

1330

20

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

WE10C33

*

56

24

56

56

128

150

58

110

4

24

153

477

4.5

16.0

18.5

39.0

260

1455

20

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

WE13C33

*

46

34

46

46

128

174

55

99

9

34

135

500

6.3

16.0

26.0

40.0

240

1350

20

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

WE15C33

*

45

35

45

46

135

181

54

101

9

40

130

545

8.3

16.0

41.0

43.0

250

1345

20

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

*

 

Due to continuing research and technology, performance data and 8th character (engineering) are subject to change without notice.

** Rating Conditions: 80 degrees F, room air temp. & 50% relative humidity, with 95 degree F, outside air temp & 40% relative humidity, all systems use R410A

Dischar

ge 

Temp

Suction 

Temp

Liquid 

Temp

Super 

Heat

Evap 

CFM

Motor 

RPM

Locked 

Rotor Amps

Charge in 

OZ.

BREAKER 

FUSE

60 Hertz 

Amps

Sub-

Coolin

g

OPERATING 

PRESSURES

ELECTRICAL RATINGS

R410A

Suction

Dischar

ge

Amps 

Cool

Amps 

Heat

W

A

L

L

M

A

S

T

E

R

EVAPORATOR AIR TEMP. 

DEG. F

EVAPORATOR TEMP. 

DEG. F

CONDENSER 

TEMPERATU

RE DEG. F

Discharge Air

Temp. Drop 

F.

T(in)

T(out)

COOLING 

PERFORMANCE 

DATA** 

19 3/4

* Due to continuing research in new energy-saving technology, specifi cations are subject to change without notice.

Due to continuing research in new energy-saving technology, performance data and 8th and 9th character are subject to change without notice.

Summary of Contents for WallMaster WE10C33

Page 1: ...at Back Up WallMaster Money Fan Timer Operation Set Hr Stop Start Temperature Fan Cool Power Cooler Warmer Only Speed Saver Heat Air Conditioners and Heat Pumps Thru the wall Last character may vary 1...

Page 2: ...ration Repairs Charging 17 20 Hermetic Components Check 21 Reversing Valve Description Operation 22 Testing the Coil and Reversing Valve 23 24 Compressor Checks 25 26 Compressor Replacement 27 28 Rout...

Page 3: ...sistant if possible Capacitors even when disconnected from the electrical power source retain an electrical charge potential capable of causing electric shock or electrocution Handle discharge and tes...

Page 4: ...t contact with liquid refrigerant can result in minor to moderate injury Be extremely careful when using an oxy acetylene torch Direct contact with the torch s flame or hot surfaces can cause serious...

Page 5: ...an or the underside of the unit Failure to follow these instructions can result in result in damage to the unit and or minor to serious property damage 4 INTRODUCTION This service manual is designed t...

Page 6: ...ts 3 230 208 Volts 7th DIGIT 0 Straight Cool Heat Pump Models 3 3 KW Heat Strip Nominal 8th DIGIT Marketing Suffix Indicates Modification Subject to change 9th DIGIT Engineering Suffix Indicates Modif...

Page 7: ...the compressor stops and the electric heat starts then operates with the fan to maintain indoor comfort The unit remains in electric heat mode DEFROST DRAIN Drain automatically opens at approximately...

Page 8: ...ogram can be certain that the AHAM Certification Seal accurately states the unit s cooling and heating capacity rating the amperes and the energy efficiency ratio ELECTRICAL DATA ELECTRIC SHOCK HAZARD...

Page 9: ...ur Power PM Cool Fan Only Heat Clock Start Time Stop Time Smart Fan Fan Speed Mode Timer On Off Money Saver Set Hour 2 3 4 1 6 5 7 9 8 10 11 12 14 13 Figure2 WY WEModelheat coolcontrolpanel Figure 1 W...

Page 10: ...ns constantly If Indoor temp is 1 5 F above set point compressor turns ON If 1 5 F below set point compressor turns OFF Cool Mode with Money Saver ON Fan cycles with the compressor ON OFF operation If...

Page 11: ...tton once to see the current clock setting Continue pressing the button until you arrive at the current time Hour only Minutes are not shown on the display Make sure that the A M P M setting is correc...

Page 12: ...ive presses will scroll through all error codes stored Press the Temp Hour button to see the reverse order of the error codes When the end of the stored error codes is reached the temperature Set Poin...

Page 13: ...OPEN OR SHORT Normal operation is allowed Replace probe see note below E5 CONDENSER TEMPERATURE PROBE OPEN OR SHORT Normal operation is allowed Replace probe E7 MOTOR OPERATION E9 HEAT PUMP ERROR Dur...

Page 14: ...illustrations below If the outdoor coil thermister reaches 43 degrees and the compressor has waited the standard delay time of 180 240 seconds the control will 1 Turn off the backup electric heat 2 W...

Page 15: ...tor Connections The starting winding of a motor can be damaged by a shorted and grounded running capacitor This damage usually can be avoided by proper connection of the running capacitor terminals Fr...

Page 16: ...sed changed to a Liquid before leaving the condenser coil The refrigerant leaves the condenser Coil through the liquid line as a warm high pressure liquid It next will pass through the refrigerant dri...

Page 17: ...410A equipment To prevent moisture absorption and lubricant contamination do not leave the refrigeration system open to the atmosphere longer than 1 hour Weigh in the refrigerant charge into the high...

Page 18: ...igerant and oil under high pressure Proper safety procedures must be followed and proper protective clothing must be worn when working with refrigerants Failure to follow these procedures could result...

Page 19: ...FREEZE HAZARD Proper safety procedures must be followed and proper protective clothing must be worn when working with a torch Failure to follow these procedures could result in moderate or serious in...

Page 20: ...evaporator will not be encountered because the refrigerant will boil later if at all Gauges connected to system will usually have higher head pressure depending upon amount of over charge Suction pres...

Page 21: ...a partial restriction there may be gurgling sounds at the metering device entrance to the evaporator The evaporator in a partial restriction could be partially frosted or have an ice ball close to th...

Page 22: ...posite port liquid line to the indoor coil Refer to refrigerant flow chart This directs the refrigerant through the filter drier and cooling capillary tube to the indoor coil In the heating mode of op...

Page 23: ...side of the system The other two are connected to the indoor and outdoor coils Small capillary tubes connect each end of the main valve cylinder to the A and B portsofthepilotvalve Athirdcapillaryisac...

Page 24: ...the mid position part of the discharge gas from the compressor is directed back to the suction side resulting in excessively high suction pressure Should the valve fail to shift from coooling to heat...

Page 25: ...excess braze from all tubing so that they will slip into fittings on new valve 5 Remove solenoid coil from new valve The use of a torch requires extreme care and proper judgment Follow all safety rec...

Page 26: ...ated within the compressor shell usually due to recycling of the motor is slow to dissipate It may take anywhere from a few minutes to several hours for the overload to reset Checking the External Ove...

Page 27: ...is obtained the compressor is grounded and must be replaced Check the complete electrical system to the compressor and compressor internal electrical system check to be certain that compressor is not...

Page 28: ...em will need to be cleaned up following proper procedures 7 Install the replacement compressor 8 Pressurize with a combination of R 410A and nitrogen and leak test all connections with an electronic o...

Page 29: ...ll refrigerant and oil from the system Remove compressor capillary tube and filter drier from the system Flush evaporator condenser and all connecting tubing with dry nitrogen or equivalent Use approv...

Page 30: ...o dry thoroughly before reinstalling them ELECTRONIC ELECTRICAL MECHANICAL Periodically at least yearly or bi yearly inspect all control components electronic electrical and mechanical as well as the...

Page 31: ...outside to ensure that the unit s clearances have not been compromised or altered ROUTINE MAINTENANCE Continued Do not drill holes in the bottom of the drain pan or the underside of the unit Not foll...

Page 32: ...OR AMBIENT TEMPERATURE F RELATIVE HUMIDITY RH INDOOR COOL HEAT DISCHARGE AIR TEMPERATURE INDOOR F F RETURN AIR TEMPERATURE INDOOR F F DIFFERENTIAL F F OUTDOOR TEMPERATURE OUTDOOR AMBIENT TEMPERATURE F...

Page 33: ...Trips Reset Button Pops Out The LCDI power cord can trip Reset button pops out due to disturbances on your power supply line Press and release RESET listen for click Reset button latches and remains...

Page 34: ...re sized to meet the cooling load and heater size is then selected to meet the heating load In extreme northern climates room air conditioners may not be able to be used as a primary source of heat Un...

Page 35: ...P m e l b o r P Fan motor does not run Inoperative system button Broken loose or incorrect wiring Refer to applicable wiring diagram Repair Open capacitor Test capacitor replace if inoperative Fan sp...

Page 36: ...to appropriate wiring diagram Defective thermistor Replace thermistor or electronic control board e s u a C e l b i s s o P m e l b o r P Noisy operation Poorly installed Refer to Installation Manual...

Page 37: ...M n i e t a r e p O t i n u d e z i s r e v O Inadequate vapor barrier in building structure particularly floors Advise customer e s u a C e l b i s s o P m e l b o r P Unit short cycles Defective th...

Page 38: ...it undersized Check heat rise across coil If unit operates efficiently check if insulation can be added to attic or walls If insulation is adequate recommend additional unit or larger one Outdoor t st...

Page 39: ...lve Defective electronic control board Replace electronic control board e s u a C e l b i s s o P m e l b o r P Heating insufficient Heating capillary tube partially restricted Check for partially sta...

Page 40: ...UCTION PRESSURE HIGH SUCTION PRESSURE LOW HEAD PRESSURE HIGH HEAD PRESSURE LOW SUCTION PRESSURE HIGH SUCTION PRESSURE LOW HEAD PRESSURE HIGH HEAD PRESSURE PROBLEM PROBLEM PROBLEM PROBLEM PROBLEM PROBL...

Page 41: ...AT PUMP ELECTRIC SHOCK HAZARD WARNING Turn off electric power before service or installation Extreme care must be used if it becomes necessary to work on equipment with power applied Failure to do so...

Page 42: ...Hot Warm Warm Hot TVB Hot Not enough pressure differential at start of stroke or not enough fl ow to maintain pressure differential Check unit for correct operating pressures and charge Raise head pr...

Page 43: ...WALLMASTER WIRING DIAGRAM ELECTRONIC CONTROL COOL ONLY MODELS 115 Volt WS08C10 WS10C10 WS12C10 230 Volt WS10C30 WS13C30 WS15C30 42 Last character may vary...

Page 44: ...WALLMASTER WIRING DIAGRAM ELECTRONIC CONTROL COOL WITH ELECTRIC HEAT MODELS 230 Volt WE10C33 WE13C33 WE15C33 43 Last character may vary...

Page 45: ...WALLMASTER WIRING DIAGRAM ELECTRONIC CONTROL HEAT PUMP WITH ELECTRIC HEAT MODELS 230 Volt WY09C33 WY12C33 44 Last character may vary...

Page 46: ...l i ngi nas l eeve deepert han 16 3 4 deep s uch as Fedder sBs l eeve 193 4 deep IDK Internal Drain Kit New cons t r uct i onappl i cat i onswher e acondensat edr ai n syst em hasbeen bui l ti nt ot h...

Page 47: ...ry walls to support the material above the WSD SLEEVE The following considerations should also be given A Adjustable SUB BASE SB 89 or other unit support must be provided for panel wall type construct...

Page 48: ...e WSD SLEEVE in the wall opening following the instructions given in the INSTALLATION REQUIRE MENTS section Attach the SLEEVE to the INSIDE WALL by driving two 12A x 2 screws in each side of the SLEEV...

Page 49: ...RD WARNING Be careful with the sharp edges and corners Wear protective clothing and gloves etc Failure to do so could result in serious injury CUT SEVER HAZARD 48 INSTALLATION INSTRUCTIONS FOR BAFFLE...

Page 50: ...the orange backing from the gasket and apply it to the base of the sleeve see fig B Once the gasket has been properly applied the sleeve is ready for the air conditioner to be installed per the instal...

Page 51: ...S THE DRAIN PLATE DOWN TO FORM A WATERTIGHT SEAL AGAINST THE SLEEVE BASE 4 DRILL A 625 DIAMETER HOLE IN THE BOTTOM OF THE BASE PAN AS SHOWN IN THE ILLUSTRATION THIS HOLE ALLOWS CONDENSATE TO ENTER THE...

Page 52: ...loves etc Failure to do so could result in serious injury CUT SEVER HAZARD EXCESSIVE WEIGHT HAZARD WARNING Use two people to lift or carry the unit and wear proper protective clothing Failure to do so...

Page 53: ...L HAZARD WARNING Be careful with the sharp edges and corners Wear protective clothing and gloves etc Failure to do so could result in serious injury CUT SEVER HAZARD INSTALLATION INSTRUCTIONS SUBBASE...

Page 54: ...L HAZARD WARNING Be careful with the sharp edges and corners Wear protective clothing and gloves etc Failure to do so could result in serious injury CUT SEVER HAZARD INSTALLATION INSTRUCTIONS ARCHITEC...

Page 55: ...54 54 MECHANICAL HAZARD WARNING Be careful with the sharp edges and corners Wear protective clothing and gloves etc Failure to do so could result in serious injury CUT SEVER HAZARD...

Page 56: ...ts from improper installation wiring electrical current characteristics or maintenance or caused by accident misuse or abuse fire flood alterations and or misapplication of the product and or units in...

Page 57: ...T CONTACT INFORMATION 56 FRIEDRICH AIR CONDITIONING CO 10001 Reunion Place Ste 500 San Antonio TX 78216 210 546 0500 877 599 5665 x 261 FAX 210 546 0731 Email tac friedrich com www friedrich com Print...

Page 58: ...NOTES...

Page 59: ...NOTES...

Page 60: ...FRIEDRICH AIR CONDITIONING CO 10001 Reunion Place Ste 500 San Antonio TX 78216 P 210 546 0500 F 210 546 0731 www friedrich com Printed in the U S A WM ServMan 01 11...

Reviews: