background image

4

5

G

ENERAL

 I

NFORMATION

 – PH S

ERIES

Model

                                                           

PH07K         PH07R         PH09K         PH09R         PH12K        PH12R       PH15K        PH15R

 

POWER  

                                                                                                                                                                                                                                  

VOLTAGE (1 PHASE, 60 Hz)                                230/208            265            230/208             265             230/208             265           230/208            265 
VOLT RANGE                                                        253-198         292-239         253-198         292-239         253-198         292-239       253-198        292-239 
POWER (WATTS)                                                 590/574            590            791/774             791           1121/1023          1121        1581/1559         1559 
CURRENT (AMPS)                                                     3                   3                  3.9                  3.9                 5.1                 5.1               6.6                6.6 
POWER FACTOR                                                      0.9                 0.9                 0.9                  0.9                 0.9                 0.9               0.9                0.9 
AMPS L.R.                                                                 18                 18                22.2                22.2               26.3               26.3               38                  38 
AMPS F.L.                                                                   3                   3                  3.9                  3.9                 5.1                 5.1               6.8                6.8 
HORSEPOWER                                                      1/15.             1/15.              1/12.               1/12.              1/10.              1/10.             1/10.              1/10. 
R-22 CHARGE (OZ)                                                  27                 27                  32                   32                 34.5               34.5               33                  33 

PERFORMANCE

                                                                                                                                                                                                                     

COOLING BTUh                                                  7200/7000         7000         9100/8900          9100        12000/11800       12000     14700/14500      14700 
REVERSE HEATING BTUh                                 6400/6200         6400         8100/7900          8100        10800/10600       10800     13500/13300      13500 
INDOOR CFM                                                          250               250                300                 300                325                325               350                350 
SENSIBLE HEAT RATIO                                          0.79               0.79               0.76                0.76               0.76               0.76             0.75              0.75 
VENT CFM                                                                60                 60                  60                   60                  70                  70                 70                  70

 

G

ENERAL

 I

NFORMATION

 – PE S

ERIES

Model

                                            

              PE07K         PE07R         PE09K         PE09R         PE12K         PE12R        PE15K         PE15R 

POWER 

                                                                                                                                                                                                            

VOLTAGE (1 PHASE, 60 Hz)                               230/208             265             230/208             265             230/208             265           230/208             265
VOLT RANGE                                                       253-198          292-239          253-198         292-239         253-198         292-239        253-198          292-239 
POWER (WATTS)                                                615/598             615             800/783             800           1091/1073          1091        1579/1578          1579 
CURRENT (AMPS)                                                     3                    3                   3.9                  3.9                 5.1                 5.1                6.6                  6.6 
POWER FACTOR                                                     0.9                  0.9                  0.9                  0.9                 0.9                 0.9                0.9                  0.9 
AMPS L.R.                                                                 18                  18                 22.2                22.2               26.3               26.3                38                  38 
AMPS F.L.                                                                   3                    3                   3.9                  3.9                 5.1                 5.1                6.8                  6.8 
HORSEPOWER                                                      1/15.              1/15.              1/12.               1/12.               1/10.               1/10.             1/10.              1/10. 
R-22 CHARGE (OZ)                                                  27                  27                  30                   30                   28                   28                 28                  28 

PERFORMANCE

                                                                                                                                                                                                                     

COOLING BTUh                                                 7500/7300          7500          9200/9000          9200        12000/11800        12000     15000/14800       15000 
INDOOR CFM                                                          250                250                300                 300                 325                 325               350                350 
SENSIBLE HEAT RATIO                                         0.79                0.79                0.76                0.76               0.76               0.76              0.75                0.75 
VENT CFM                                                                60                  60                  60                   60                   70                   70                 70                  70

Summary of Contents for WallMaster PE07K

Page 1: ...P2K23 DM 4 03 Standard Unit Seacoast Protected Unit Remote Thermostat Unit Service Manual WallMaster P SERIES Packaged Terminal Air Conditioners Packaged Terminal Heat Pumps...

Page 2: ...4 Overcharged Refrigerant Systems 15 Restricted Refrigerant Systems 18 Capillary Tube Systems 17 Reversing Valve Operation 17 Electrical Circuit And Coil 18 Checking Reversing Valve 18 Touch Test In H...

Page 3: ...all Sleeve Condenser Coil Condenser Shroud Compressor Basepan Control Panel Front Cover Control Door Filters Gasket Gasket The information contained in this manual is intended for use by a qualified s...

Page 4: ...C Seacoast Protection X Seacoast Remote Nominal Heater Size 230V or 265V 0 No Heater 2 2 5 KW 3 3 4 KW 5 5 0 KW Voltage K 230 208V 1Ph 60 Hz R 265V 1Ph 60 Hz UNIT IDENTIFICATION PTAC Serial Number Id...

Page 5: ...3300 13500 INDOOR CFM 250 250 300 300 325 325 350 350 SENSIBLE HEAT RATIO 0 79 0 79 0 76 0 76 0 76 0 76 0 75 0 75 VENT CFM 60 60 60 60 70 70 70 70 GENERAL INFORMATION PE SERIES Model PE07K PE07R PE09K...

Page 6: ...essure liquid It next will pass through the refrigerant drier if so equipped It is the function of the drier to trap any moisture present in the system contaminants and large particulate matter The li...

Page 7: ...only Electrical Rating Tables All 230 208 volt units are equipped with power cords Electric shock hazard Turn off electric power before service or installation All electrical connections and wiring MU...

Page 8: ...s to the desired location 5 Replace the knob when the desired range has been set 6 Replace the control panel EXAMPLE To set a maximum temperature range of approximately 64 to 86 F move the screws to t...

Page 9: ...ed Terminal G should be energized whenever a call for heating or cooling is made Typically a heat cool thermostat designed for use with electric heat systems will meet this requirement Honeywell Therm...

Page 10: ...ype In all cases no matter how simple or complex they are simply a switch or series of switches designed to turn equipment or components ON or OFF at the desired conditions An improperly operating or...

Page 11: ...n the control circuit W using a low range 0 2 0 Amps ammeter After measuring the current draw simply set the heat anticipator to match that value Electronic thermostats do not use a resistance type an...

Page 12: ...ging continues Not enough refrigerant undercharge on the other hand will cause the temperature of the suction gas to increase to the point where it does not provide sufficient cooling for the compress...

Page 13: ...ong enough to establish working pressures in the system 15 to 20 minutes During the cooling cycle you can listen carefully at the exit of the metering device into the evaporator an intermittent hissin...

Page 14: ...ow over the evaporator coil may indicate some of the same symptoms as an overcharged system An over charge can cause the compressor to fail since it would be slugged with liquid refrigerant The charge...

Page 15: ...ith a partial restriction there may be gurgling sounds at the metering device entrance to the evaporator The evaporator in a partial restriction could be partially frosted or have an ice ball close to...

Page 16: ...mall capillary tubes connect each end of the main valve cylinder to the A and B ports of the pilot valve A third capillary is a common return line from these ports to the suction tube on the main valv...

Page 17: ...test the heat relay and the reversing valve relay 3 STANDARDHEATPUMPUNITS Checkforlinevoltage at system switch terminal 7 and thermostat terminal 2 If voltage is not present test the system switch Tes...

Page 18: ...d within a few seconds since the pressures in the system will not have had time to equalize Voltage should be at or above minimum voltage of 197 VAC as specified on the rating plate If less than minim...

Page 19: ...o determine why the compressor failed Many compressor failures are caused by the following conditions 1 Improper air flow over the evaporator 2 Overcharged refrigerant system causing liquid to be retu...

Page 20: ...resistor across terminals When checking a dual capacitor with a capacitor analyzer or ohmmeter both sides must be tested Capacitor Check With Capacitor Analyzer The capacitor analyzer will show wheth...

Page 21: ...hould the thermostat fail any part of this check it should be replaced Some thermostats may have the terminals identified by the letters C H and L Cooling Only Models Cooling Heating Models CONTACTS M...

Page 22: ...e table below Should the fan cycle switch fail any part of this check it should be replaced Fan Speed Switch Continuity Check Remote Models Only Remove and label all wires from the fan speed switch Co...

Page 23: ...e unit to cycle between compressor and electric heat operation Electric Heat Switch Check Out The switch may be checked out with an ohmmeter Remove and label the three wires from the switch Terminal 2...

Page 24: ...ms Allow all items to dry thoroughly before reinstalling them 3 Periodically at least yearly or bi yearly inspect all control components both electrical and mechanical as well as the power supply Use...

Page 25: ...Conditions High Load Conditions Low Air Flow Across High Air Flow Across Refrigerant System Low Air Flow Across Indoor Coil Indoor Coil Restriction Outdoor Coil Refrigerant System Reversing Valve not...

Page 26: ...em Restriction Reversing Valve not Fully Seated Low Airflow Across Indoor Coil Low Airflow Across Outdoor Coil Outdoor Ambient Too High for Operation in Heating Refrigerant System Restriction Outdoor...

Page 27: ...Reversing Valve Stuck Replace the Reversing Valve Replace the Solenoid Coil NO Is the Solenoid Coil Good Is Line Voltage Present at the Solenoid Valve Is the Selector Switch Set for Heat NO SYSTEM CO...

Page 28: ...28 Wiring Diagram PTAC Models PE 07 09 12 15 KOOSA 1 Wiring Diagram PTAC Models PH 07 09 12 15 K 2 3 5 SA 1...

Page 29: ...29 Wiring Diagram PTAC Models PH 07 09 12 15 KOOSA 1 Wiring Diagram PTAC Models PE 07 09 12 15 K 2 3 5 SA 1...

Page 30: ...30 Wiring Diagram PTAC Models PH 07 09 12 15 K 2 3 5 RA 1 Wiring Diagram PTAC Models PE 07 09 12 15 K 2 3 5 RA 1...

Page 31: ...31 Wiring Diagram PTAC Models PE 07 09 12 15 KOORA 1 Wiring Diagram PTAC Models PE 07 09 12 15 R00SA 1...

Page 32: ...32 Wiring Diagram PTAC Models PE 07 09 12 15 R 2 3 5 SA 1 Wiring Diagram PTAC Models PH 07 09 12 15 R 2 3 5 SA 1...

Page 33: ...33 Wiring Diagram PTAC Models PE 07 09 12 15 R 2 3 5 RA 1 Wiring Diagram PTAC Models PH 07 09 12 15 R 2 3 5 RA 1...

Page 34: ...OOTH WIRE POWER F A N 5 H E R M c 3 4 1 C 2 L 3 H 1 S C R H 1 L 3 C 2 9 5 L 6 COM H L1 L2 3 1 8 2 7 4 1 3 2 RED BLACK FAN HEATER SOLENOID CAPACITOR HOT START SENSOR BROWN RED BROWN YELLOW TO INNERWALL...

Page 35: ...LD SUPPLIED 24 WIRING HARNESS POWER TERMINAL L1 TERMINAL L2 TO UNIT SWITCH SUPPLIED BLACK WIRE SUPPLIED WHITE WIRE TO UNIT SWITCH 24V 240V 208V COM H E R M YELLOW RED FAN 2 1 BLACK RED MOTOR TERM BOAR...

Page 36: ...E WIRE FIELD SUPPLIED 24 VOLT WIRES WIRING HARNESS Existing Black Line White Line Supplied Transformer 277V To Unit COM To Fuse Terminal H E R M YELLOW RED FAN 2 1 BLACK RED MOTOR TERM BOARD PURPLE YE...

Page 37: ...OLT WIRES FIELD SUPPLIED 24 WIRING HARNESS RIBBED WIRE SMOOTH WIRE POWER CORD To Unit Transformer 230V COM F A N H E R M c S C R H 1 L 3 C 2 4 L 3 COM H L1 L2 1 2 COMP 1 3 2 RED BLACK FAN CAPACITOR BR...

Page 38: ...WIRES FIELD SUPPLIED 24 WIRING HARNESS To Fuse Terminal White Line Supplied Black Line F A N 5 H E R M c 3 4 1 C 2 L 3 H 1 S C R H 1 L 3 C 2 9 5 L 6 COM H L1 L2 3 1 8 2 7 4 1 3 2 RED BLACK FAN HEATER...

Page 39: ...sformer WHITE WIRE BLACK WIRE SUPPLIED Existing 277V COM 3 2 1 3 R Y W B G 3 1 2 4 1 4 3 1 1 3 6 2 2 4 4 2 F A N H E R M 3 5 4 1 L 3 H 1 C 2 S R C COM 24V COM 277V C GREEN YELLOW YELLOW RED BROWN YELL...

Page 40: ...4 03 FRIEDRICH AIR CONDITIONING CO Post Office Box 1540 San Antonio Texas 78295 1540 4200 N Pan Am Expressway San Antonio Texas 78218 5212 210 357 4400 FAX 210 357 4480 www friedrich com Printed in t...