Kühl Q Chassis
Performance Testing Installation and Test Method
continued
®
Test Unit Settings
Louver position:
•
Louvers shall be kept in the recessed position (not extended)
•
Louvers shall be centered (not directed left or right) and pointed upward.
Fan speed:
•
Fan shall be set to the highest speed setting
•
HIGH
System Operation:
•
Unit shall be operating in “Cool” Mode
Test Unit Installation
As per ANSI/ASHRAE Standard 16-1983 (RA 2009), section 4.2.2, this air conditioner shall be installed per the
instructions specified in this Installation & Operation Manual.