Friedrich Hazardgard SH15L30-A Service & Parts Manual Download Page 9

9

 NOTE: This procedure can be sped up by the 
use of heat lamps, or by breaking the vacuum 
with refrigerant or dry nitrogen at 5,000 microns.  
Pressure system to 5 PSIG and leave in the sys-
tem a minimum of 10 minutes. Recover refriger-
ant, and proceed with evacuation to a pressure 
of 200 microns or a minimum of 10%.

11. Break the vacuum by charging the system from 

the high side with the correct amount of refrigerant 
specifi ed.  This will prevent boiling the oil out of the 
crankcase.

 

NOTE: If the entire charge will not enter the high 

side, allow the remainder to enter the low side 
in small increments while operating the unit.

12. Restart the unit several times after allowing 

pressures to stabilize.  Pinch off the process tubes, 
cut and solder the ends.  Remove the pinch off tool, 
and leak check the process tube ends.

SPECIAL PROCEDURES IN THE CASE OF 
COMPRESSOR MOTOR BURNOUT

1.  Recover all refrigerant and oil from the system.

2.  Remove the compressor, capillary tube and fi lter 

drier from the system.

3.  Flush the evaporator, condenser and all connecting 

tubing with dry nitrogen, or equivalent, to remove all 
contamination from the system.  Inspect the suction 
and discharge lines for carbon deposits.  Remove 
and clean if necessary.

4.  Reassemble the system, including a new drier-

strainer and capillary tube.

5.  Proceed with processing as outlined under hermetic 

component replacement.

HERMETIC COMPONENT REPLACEMENT

The following procedure applies when replacing 
components in the sealed refrigeration circuit or 
repairing refrigerant leaks.  (Compressor, condenser, 
evaporator, capillary tube, refrigerant leaks, etc.)

1.  Recover the refrigerant from the system at the 

process tube located on the high side of the system 
by installing a line tap on the process tube.  Apply 
the gauge from the process tube to EPA approved 
gauges from the process tube to the EPA approved 
recovery system.  Recover the CFC’s in the system 
to at least 5%.

2.  Cut the process tube below the pinch off in the 

suction side of the compressor.

3.  Connect the line from the nitrogen tank to the 

suction process tube.

4.  Drift dry nitrogen through the system and unsolder 

the more distant connection fi rst. (Filter drier, high 
side process tube, etc.)

5.  Replace the inoperative component, and always 

install a new fi lter drier.  Drift dry nitrogen through 
the system when making these connections.

6.  Pressurize  the  system  to  30  PSIG  with  proper 

refrigerant and boost the refrigerant pressure to 
150 PSIG with dry nitrogen.

7.  Leak test the complete system with the electric 

halogen leak detector, correcting any leaks 
found.

8.  Reduce the system to zero gauge pressure.

9.  Connect the vacuum pump to the high side and 

low side of the system with deep vacuum hoses, 
or copper tubing. (Do not use regular hoses.)

10. Evacuate the system to an absolute holding 

pressure of 200 microns or less.

Summary of Contents for Hazardgard SH15L30-A

Page 1: ...SH15L30 A SH20L30 A SH20L50 A HG SVC PRTS 05 4 05 Service Parts Manual Room Air Conditioners 50 60 Hz Models 2005...

Page 2: ...ontrol Switch 6 Run Capacitor 6 Thermostat 6 Low Ambient Bypass Valve 8 Sealed Refrigeration System Repairs 8 Hermetic Component Replacement 9 Special Procedure in the case of Compressor Motor Burn Ou...

Page 3: ...del Dimensions Inches Window Width Inches Thru The Wall Finished Hole Inches Circuit Rating Breaker or T D Fuse Weight Lbs Height Width Depth Overall Depth Hood to Louvers Minimum Extension Into Room...

Page 4: ...to high temperatures caused by 1 A locked rotor 2 Excessive running amps 3 High discharge temperature 4 Low refrigerant charge FIGURE 1 INTERNAL OVERLOAD LINE BREAK INTERNAL OVERLOAD OHMMETER FIGURE 2...

Page 5: ...side pressure B Above normal low side pressure C Low temperature difference across the coil The compressor valves are faulty replace the compressor GROUND TEST Use an ohmmeter set on its highest scale...

Page 6: ...in relation to the evaporator see Figure 8 FIGURE 8 SENSING BULB LOCATION CAPACITOR TEST 1 Remove the capacitor from the unit 2 Check for visual damage such as bulges cracks or leaks 3 For dual rated...

Page 7: ...n in this manual for additional information on thermostat testing TEST Remove the wires from the thermostat Turn the thermostat to its coldest position Check to see if there is continuity between the...

Page 8: ...t the bypass valve outlet which connects to the suction process tube When the low side pressure reaches approximately 50 psig the valve will begin to open and the tube will get hot This method will de...

Page 9: ...th processing as outlined under hermetic component replacement HERMETIC COMPONENT REPLACEMENT The following procedure applies when replacing components in the sealed refrigeration circuit or repairing...

Page 10: ...y into the low side The introduction of liquid into the low side without the use of a capillary tube will cause damage to the discharge valve of the rotary compressor ROTARY COMPRESSOR SPECIAL TROUBLE...

Page 11: ...ive fan motor Test and replace if inoperative COMPRESSOR RUNS CONTINUALLY DOES NOT CYCLE OFF Excessive heat load Test cooling performance of unit Unit undersized Restriction in line Check for partiall...

Page 12: ...OR DOES NOT START FAN MOTOR RUNS Thermostat contacts not closing Check continuity of thermostat at coldest setting Jump contacts if compressor runs replace thermostat Low voltage supply Check for name...

Page 13: ...blade and blower wheel clearance Compressor vibrating Check for deteriorated compressor grommets or missing mounting parts Loose cabinet parts improperly mounted components tubing rubbing Adjust and t...

Page 14: ...14 WIRING DIAGRAM MODELS SH15L30 A SH20L30 A SH20L50 A...

Page 15: ...15 HAZARDGARD CABINET PARTS...

Page 16: ...16 HAZARDGARD CHASSIS PARTS...

Page 17: ...399 RELAY SOLID STATE 61108800 2 2 2 399 6 THERMOSTAT 61825502 1 1 1 120 7 CAPACITOR 20 7 5 440 V 61080546 1 1 1 150 7 CAPACITOR 25 7 5 440 V 61080547 1 1 1 150 HARNESS WIRE COMP 61821308 1 1 1 399 R...

Page 18: ...1 772 LATCH INTAKE GRILLE 61989000 2 2 2 752 FILTER AIR 60865808 1 754 FILTER AIR 60865809 1 1 754 HOLDER FILTER 61823000 2 2 2 756 8 HOLDER THERMOSTAT 61829800 1 1 1 999 25 FAN MOTOR MOUNT 61802500 1...

Page 19: ...19...

Page 20: ...actory Certi ed Parts FRIEDRICH AIR CONDITIONING CO Post Office Box 1540 San Antonio Texas 78295 1540 4200 N Pan Am Expressway San Antonio Texas 78218 5212 210 357 4400 FAX 210 357 4480 www friedrich...

Reviews: