14 – TEMPERATURE SETBACK DELAY - COOL
00-120
(20* factory setting) Select the time delay (in minutes) for which the room
that is in the guest occupancy mode needs to be unoccupied before the temperature
setback is initiated.
This feature prevents initiating temperature setback prematurely while the guest is
still in the room but in an area where occupancy cannot be detected by the occupancy
sensor.
Setting the “Temperature Setback Delay - Cool” to “00”, disables the setback in the
cool mode. Set to “00” to disable EMS.
15 – MAXIMUM SETBACK TEMPERATURE
72-92 (78°F* factory setting) Select the “Maximum Setback Temperature” in °F.
Setback temperature is calculated by measuring PTAC unit’s ability to attain “Recovery
Temperature - Cool” within “Temperature Recovery Time”.
If recovery is disabled (“Temperature Recovery Time” is set to “0”) or if setback
temperatures have not yet been calculated, the “Maximum Setback Temperature” value
will be used as the setback temperature for cooling.
If calculated setback temperature for air conditioning is higher than “Maximum Setback
Temperature”, then the “Maximum Setback Temperature” will be used as setback
temperature for air conditioning.
This feature allows defining the maximum temperature in a room when room is
unoccupied and the thermostat is in the setback mode.